background image

1. RECOMMENDED LOCATIONS FOR ALARMS

• Locate the first alarm in the immediate area of the sleeping rooms. Try to monitor the

exit path as the sleeping rooms are usually farthest from the exit. If more than one
sleeping area exists, locate additional alarms in each sleeping area.

• Locate additional alarms to monitor any stairway as stairways act like chimneys for

smoke and heat.

• Locate at least one alarm on every floor level.

• Locate an alarm in every sleeping room.

• Locate an alarm in every room where electrical appliances are operated (i.e. portable

heaters or humidifiers).

• Locate an alarm in every room where someone sleeps with the door closed.

The closed door may prevent an alarm not located in that room from waking the
sleeper.

• Smoke, heat, and combustion products rise to the ceiling and spread horizontally.

Mounting the smoke alarm on the ceiling in the center of the room places it closest
to all points in the room.

Ceiling mounting is preferred in ordinary residential

construction.

• For mobile home installation, select locations carefully to avoid thermal barriers that

may form at the ceiling. For more details, see MOBILE HOME INSTALLATION below.

• When mounting an alarm on the ceiling, locate it at a minimum of 10 cm (4”) from

the side wall. (see Figure 1).

• When mounting the alarm on the wall, use an inside wall with the top edge of the

alarm at a minimum of 10 cm (4”) and a maximum of 30.5 cm (10”) below the
ceiling. (see Figure 1).

• In homes that are not well insulated, extreme heat or cold can be transferred from

the outside to the inside through poorly insulated walls and roof. This may create a
thermal barrier which can prevent the smoke from reaching an alarm mounted on
the ceiling. If you are not sure about the insulation in your home, or if you notice that
the outer walls and ceiling are either hot or cold, install the alarm on an inside wall.
In such homes, install the smoke alarm with the top edge of the alarm at a minimum
of 4” (10 cm) and a maximum of 12” (30.5 cm) below the ceiling (see figure 1).

• Put smoke alarms at both ends of a bedroom hallway or large room if the hallway or

room is more than 9.1 m (30 feet) long.

• Install Smoke Alarms on sloped, peaked or cathedral ceilings at or within 0.9 m (3 ft)

of the highest point (measured horizontally). Smoke alarms in rooms with ceiling
slopes greater than .3 m in 2.4 m (1 foot in 8 feet) horizontally shall be located on
the high side of the room. A row of detectors shall be spaced and located within 0.9
m (3 ft) of the peak of the ceiling measured horizontally (see Figure 3).

• Install Smoke Alarms on tray-shaped ceilings (coffered ceilings) on the highest portion

of the ceiling or on the sloped portion of the ceiling within 12” (305mm) vertically
down from the highest point (see figure 4).

MOBILE HOME INSTALLATION

Modern caravans and mobile homes have been designed and built to be energy
efficient. Install smoke alarms as recommended (see Figures 1 and 2).

In older caravans and mobile homes that are not well insulated compared to present
standards, extreme heat or cold can be transferred from the outside to the inside
through poorly insulated walls and roof. This may create a thermal barrier which can
prevent the smoke from reaching an alarm mounted on the ceiling. In such units, install
the smoke alarm on an inside wall with the top edge of the alarm at a minimum of 10
cm (4”) and a maximum of 30.5 cm (12”) below the ceiling (see Figure 1).

0910-7207-03_R1.qxd:_  2009.8.13  6:52 PM  Page 2

Summary of Contents for 0910UK

Page 1: ...sooner than ionisation alarms Home fires develop in different ways and are often unpredictable For maximum protection Kidde recommends that both Ionisation and Photoelectric alarms be installed Insta...

Page 2: ...an prevent the smoke from reaching an alarm mounted on the ceiling If you are not sure about the insulation in your home or if you notice that the outer walls and ceiling are either hot or cold instal...

Page 3: ...nvironments In dusty areas Dust particles may cause nuisance alarm or failure to alarm In very humid areas Moisture or steam can cause nuisance alarms In areas where the Relative Humidity RH is above...

Page 4: ...ted it can be very effective in preventing smoke alarm removal or tampering NOTE The tamper resist feature is automatically engaged whenever the alarm is mounted to the mounting bracket Rotate the ala...

Page 5: ...dness 85 decibels of the alarm always stand an arms length away from the unit when testing 4 TESTING Test by pushing the test button on the cover and holding it down for a minimum of 5 seconds or unti...

Page 6: ...hire SL3 OHB This warranty shall not apply to the smoke alarm if it has been damaged modified abused or altered after the date of purchase or if it fails to operate due to improper maintenance THE LIA...

Page 7: ...at 01753 685148 or contact us at our website at www kiddesafetyeurope co uk Kidde Safety Europe Mathisen Way Colnbrook Slough Berkshire SL3 OHB UK Copyright Walter Kidde Portable Equipment 2005 All Ri...

Reviews: