Keyscan Inc. – Technical Guide (PC109x - 04.15)
40
Figure 27 – Terminate Input Wiring – RTE PIR Motion Sensor
to
Request
to Exit
to Common Return
1K
Single end of line
supervision
to Common Return
1K
Double end of line
supervision
3K
Non-supervised
Notes
Diagram illustrates CA8500B. Connections also apply to
CA250B & CA4500B.
- CA250B
– up to 2 Request to Exits
- CA4500B
– up to 4 Request to Exits
- CA8500B
– up to 8 Request to Exits
Lens
NO
COM
PIR
(Request To Exit)
Lens
NO
COM
Lens
NO
COM
to
Request
to Exit
NO = Normally Open
PIR
RTE (Request to Exit)
– ½ second pulse
Determines the amount of time the output relays will energize when motion is detected.
Cut View of CA8500B
Door Inputs - A
RTE Inputs - B
8
7
6
5
4
3
2
1
Common
8
7
6
5
4
3
2
1
AUX Inputs - C
8
7
6
5
4
3
2
1
Common
Common
AUX Inputs - D
16
15
14
13
12
11
10
9
Common
AUX Inputs - E
24
23
22
21
20
19
18
17
KI-00131E-10-13
Supervision level set in Client software:
System VII & Vantage
– Site Unit Setup
Aurora
– Hardware Setup
Supervision level applied to all door inputs, RTE inputs, and auxiliary inputs.