Keyscan Inc. – Technical Guide (PC109x - 04.15) 

67 

Table 7 – CIM Specifications 

Operating Voltage 

12 VDC 

Current Draw 

CIM only – 150 mA; CIM and NETCOM2P/6P – 290 mA 

Dimensions 

4 5/8 " x 3.0 " (11.7 cm x 7.6 cm) 

Operating Environment 

32° F – 140° F (0° C - 60° C) 

Cables 

CIM to CIM – CAT 5, 2 twisted pairs - maximum cable distance first CIM to last CIM - 3280 
ft (1000 m) @ 9600 bps 
CIM to ACU - ribbon cable to communication header H2 
CIM 0 to PC direct serial – 5 conductor shielded 22 AWG – maximum 49.2 ft (15 m) @ 
9600 bps 
CIM 0 to NETCOM2P/6P* – plugs directly into CIM, no cable required 
* If configuring CIM 0 with a NETCOM2P or NETCOM6P, ensure the NETCOMP version is a 
PC1051 or later printed circuit board. 

CAN Bus 

CAN Bus 1 – PC to ACU communication 
CAN Bus 2 – ACU to ACU communication for global functions and CIM to CIM 

Topology 

Linear (does not support star or ring topologies) 

Inter-building Connectivity 

Yes 

Firmware 

Requires control board with EPROM versions 7.40/8.20 or higher 

BPS/CAN Bus Distance Chart 

Select bit rates based on the cable distance of CAN Bus 1. The PC and ACU bit rates must be the same. 
Determine CAN Bus 1 distances before setting baud rate jumpers as outlined under Serial Bit Rate Jumpers J9 
– J11. 

Table 8 – BPS/CANBUS Distance Chart 

PC/ACU Bit Rate 

CAN Bus 1 / CAT 5 Distance 

RS-232 Serial Distance 

9600  

3280 ft (1000 m) 

100 ft (30 m) 

19,200 

3280 ft (1000 m) 

49.2 ft (15 m) 

57,600 

984.25 ft (300 m) 

26.2 ft (8 m) 

115,200 

262.46 ft (80 m) 

9.84 ft (3 m) 

 

Summary of Contents for CA250B

Page 1: ......

Page 2: ...on may be reproduced or transmitted in any form or by any means without the expressed written permission of Keyscan Inc Keyscan Inc 901 Burns Street East Whitby Ontario Canada L1N 0E6 Phone 1 888 539...

Page 3: ......

Page 4: ...ure 16 Mounting the PC109x Control Board to Metal Standoffs 18 Mounting Power Supplies 20 Grounding Communication Cable Shield 22 Control Board Mounting Locations 22 Connect Enclosure Tamper Switch to...

Page 5: ...CIM Installation Guidelines 70 CIM Connection Diagrams 70 Serial Communication 73 Network Communication via Optional NETCOM2P or NETCOM6P Encrypted 74 Network Communication via Optional NETCOM2 or NET...

Page 6: ...IEEX2 120 Appendix E Accessibility HC Relay 125 Accessibility HC Output Relays 125 Appendix F Pre alert Relay 129 Pre alert 129 Appendix G Global Output Relay 133 OCB 8 Global IO Assignments 133 Curre...

Page 7: ...ure 13 Enclosure Ground Strap Connection 26 Figure 14 Securing the Enclosure Cover 26 Figure 15 Typical Door Layout 27 Figure 16 Typical Door Strike Connection 28 Figure 17 Typical Magnetic Lock Conne...

Page 8: ...6 CIM Overview 65 Figure 47 CIM Jumper Locations 68 Figure 48 CIM to ACU Connections 71 Figure 49 CIM to CIM CANBUS Connections 72 Figure 50 PC Serial Connection with multiple CIMs ACUs 73 Figure 51 N...

Page 9: ...g 115 Figure 81 Indala PXK 501 Wiring 116 Figure 82 WSSKP 1 Keypad Connection 118 Figure 83 WSSKP 1 Keypad Reader Combination Connections 119 Figure 84 Wiegand Extender Overview 122 Figure 85 WIEEX2 R...

Page 10: ...Codes 78 Table 14 ACU Supply Current Calculation Table 81 Table 15 AUX RDR Supply Current Calculation Table 81 Table 16 Control Board Test Points Voltages 84 Table 17 Communication Voltage Test Points...

Page 11: ...SA STD C22 2 No 205 M1983 Signal Equipment CE Standards EN 55022 RF Emissions EN 55024 RF Immunity EN 60950 1 Equipment Safety FCC Subpart B RF Emissions Industry Canada ICES 003 Emissions Product Lis...

Page 12: ...ies with their duration times for access control and reader power are listed on page 20 Important The power supply included is for the exclusive use of the access control unit and the readers Do not u...

Page 13: ...a 500 ft 152 4 m 2 pairs 22 AWG Shielded wire not required CIM CAN Bus 1 3280 ft 1000 m 9600 BPS 3280 ft 1000 m 19 200 BPS 984 ft 300 m 57 600 BPS 262 ft 80 m 115 200 BPS CAT 5 2 twisted pairs Maximum...

Page 14: ...ol Board ACU 2 Shield Shield Green Black Red ACU 3 Control Board Shield CIM 0 EGND EGND CIM CIM EGND Tape back shields CAT 5 Ground Lug RS 232 Common Ground Wire CAT 5 Common Ground Wire Tape back shi...

Page 15: ...on the control board use the Keyscan DPS 15 to power the control board and readers ensure 2 x 16V 40VA transformers or 2 x 16 5V 37VA transformers are connected to the Keyscan DPS 15 power supply loca...

Page 16: ...are within their maximum allowable distances For knockout and mounting hole locations dimensions see the diagram on the next page Figure 2 Mounting the Metal Enclosure Ground Lug Side View Front View...

Page 17: ...aces 1 375 1 750 Dia Knockout 7 Places 5 50 13 97 cm 1 50 3 81 cm 3 75 9 525 cm Front 1 50 3 81 cm 1 50 3 81 cm 3 75 9 525 cm 1 50 3 81 cm 5 50 13 97 cm 1 50 3 81 cm 1 50 3 81 cm 3 75 9 525 cm Front 1...

Page 18: ...09x Control Board to 3 8 Male Female Standoffs Important Finger tighten the screws with a screwdriver Do not use a power screwdriver or apply excessive force tightening screws into the metal standoffs...

Page 19: ...andoff Internal Tooth Star Washer Long Screw Control Board Stand off locations on PC109x control board Ground Lug Front View Cover removed diagram not to scale Alternate Ground Lug Mounts 3 8 male fem...

Page 20: ...he battery circuit The transformers must be located within 30 feet of the Keyscan power supply Do not mount the transformers inside the ACU metal enclosure All warranties are voided if non compliant t...

Page 21: ...Off Figure 6 Mounting Power Supplies STAND OFF into enclosure hole into circuit board KI 00106E 07 11 Hex Nuts x 2 Bolts x 2 Top of ACU Enclosure x 2 Control Board Top mount location for DPS 15 power...

Page 22: ...te the ground lug inside the metal enclosure to minimize the length of shield used Note Keep all shield wires and cables away from the control board Control Board Mounting Locations The following diag...

Page 23: ...e terminal block connections only not 9 pin male connector NETCOM refers to NETCOM2 NETCOM6 PC109x Parts DPS 15 power supply KI 00111E 09 12 Optional NETCOM Locations Front View Cover not shown Tamper...

Page 24: ...y KI 00113E 09 12 Optional NETCOM Locations NETCOM use terminal block connections only not 9 pin male connector NETCOM refers to NETCOM2 NETCOM6 CIM or NETCOM Front View Cover not shown Tamper Switch...

Page 25: ...erminal Front View Cover not shown Tamper Switch 1 x EC2500B control board 2 x OCB 8 1 x DPS 15 power supply 1 x metal enclosure EC2500B Control Board OCB 8 Optional OCB 8 Locations Ground Lug OCB 8 N...

Page 26: ...Ground Strap Connection Figure 14 Securing the Enclosure Cover Enclosure Ground Strap Enclosure Cover Metal Enclosure Use the enclosed star washers and nuts to secure both ends of the cable to the stu...

Page 27: ...with local authorities The following diagram shows a single conduit to the access control unit For high voltage readers greater than 150 mA avoid running the communication cables in the same conduit...

Page 28: ...local officials such as the fire department to ensure the installation conforms to municipal state or provincial safety regulations Permits may be required before installing magnetic locks Use a batte...

Page 29: ...el with AC wiring or across fluorescent light fixtures this causes AC induction and transmission interference Figure 18 Door Contacts Exit Buttons PIRs Auxiliary Inputs Exit Push Button 1 1 Door Conta...

Page 30: ...l surface consult with the manufacturer s documentation If a door reader is located beyond the maximum cable length to the ACU use a Keyscan WIEEX2 extender kit to a maximum distance of 4000 feet 1219...

Page 31: ...densing Terminate Lock Wiring Use a separate power supply for door strikes and other 12 VDC equipment The power supply should have battery backup for continued operation during a power failure When ad...

Page 32: ...n wire Diodes must be installed for proper operation Fail Safe Fail Secure Lock Devices The power supply s positive output connects to the common door relay outputs which are labeled on the relay boar...

Page 33: ...common on DC power supply Relay board Relay board Door Strike Lock State of Fail Safe Device DC Supply Lock to Normally Closed positon on relay to supply to common on DC power supply to supply KI 0012...

Page 34: ...or HC Output 2 Do not use relays for both functions Ground Lug CONTRO L 5 OCB 8 powered through ribbon cable with J1 Relay Power set on ACU DTR DCD RD TD GND TAMPER TB3 SWITCH KI 00126E 10 14 CONTRO L...

Page 35: ...tch 2 Door Output 3 DIP Switch 3 Door Output 4 DIP Switch 4 Aux Output 1 DIP Switch 5 Aux Output 2 DIP Switch 6 Aux Output 3 DIP Switch 7 Aux Output 4 DIP Switch 8 Relay Power Fire Contact Door 1 Door...

Page 36: ...with J1 Relay Power set on ACU RS 232 COM4 CTS DTR DCD RD TD GND TAMPER TB3 SWITCH KI 00128E 10 14 CONTRO L 5 CONTROL 4 S1 TB1 J1 OUTPUT CONTROL BOARD K1 K2 K3 K4 K5 K6 K7 K8 LED ON RELAY ENERGIZ ED...

Page 37: ...ed door for its defined door relay unlock time and overrides the alarm input during its defined door held open time Examples of exit devices are exit push buttons or motion sensors PIR etc Keyscan rec...

Page 38: ...Diagram illustrates CA8500B Connections also apply to CA250B CA4500B CA250B up to 2 door inputs CA4500B up to 4 door inputs CA8500B up to 8 door inputs Supervision level set in Client software System...

Page 39: ...Exits CA8500B up to 8 Request To Exits RTE Push Button COM NO NO Normally Open 1K 3K COM NO to Request to Exit to Common Return 1K COM NO Cut View of CA8500B Door Inputs A RTE Inputs B 8 7 6 5 4 3 2...

Page 40: ...ns NO COM PIR Request To Exit Lens NO COM Lens NO COM to Request to Exit NO Normally Open PIR RTE Request to Exit second pulse Determines the amount of time the output relays will energize when motion...

Page 41: ...l to each other Single end of line supervision to Request to Exit to Common Return Double end of line supervision 1K 3K COM NO to Request to Exit to Common Return 1K COM NO Note If using supervision i...

Page 42: ...CA4500B up to 16 Supervised Auxiliary Alarm Inputs CA8500B up to 16 Supervised Auxiliary Inputs NC COM NC COM NC COM NC Normally Closed to Supervised Auxiliary Alarm Input Cut View of CA8500B Door In...

Page 43: ...dware conforms to federal state provincial or municipal building codes and fire regulations Table 4 OCB 8 to EC1500B Ribbon Cable Connections OCB Terminal Elevator Control Board Terminal Elevator Floo...

Page 44: ...X 12 V or ACU 12 V on DPS 15 Elevator Board Cut View CONTROL 2 CONTROL 5 RS 232 COM4 CTS DTR DCD RD TD GND TAMPER TB3 SWITCH CONTROL 4 S1 TB1 J1 OUTPUT CONTROL BOARD K1 K2 K3 K4 K5 K6 K7 K8 LED ON REL...

Page 45: ...V on DPS 15 Elevator Board Cut View CONTROL 2 CONTROL 5 RS 232 COM4 CTS DTR DCD RD TD GND TAMPER TB3 SWITCH CONTROL 4 S1 TB1 J1 OUTPUT CONTROL BOARD K1 K2 K3 K4 K5 K6 K7 K8 LED ON RELAY ENERGIZ ED O...

Page 46: ...Inputs Dry Contact Relay N O Call Button Status 24 of 40 Normally Open Dry Contact Relay N O Call Button Status 2 of 40 Normally Open Dry Contact Relay N O Call Button Status 13 of 40 Normally Open C...

Page 47: ...power For readers that draw more current connect the red wire directly to the power supply Black Ground GND Brown Light emitting diode LED on reader Green Data output bit 0 White Data output bit 1 Blu...

Page 48: ...D D1 White D0 Green PWR Red GND Black Enclosure KEYSCAN Cable in through knockout READER PWR ACU PWR Power terminal on control board Blue used for pre alert otherwise isolate and tape back Orange not...

Page 49: ...ne Figure 35 Terminate Auxiliary Outputs CA250B Normally Closed N C Normally Open N O alarm panel input or CCTV input time zone lock unlock CA250B Control Board Cut View OCB 8 ribbon cable connects to...

Page 50: ...TB3 SWITCH KI 00140E 10 14 CONTROL 4 S1 TB1 J1 OUTPUT CONTROL BOARD K1 K2 K3 K4 K5 K6 K7 K8 LED ON RELAY ENERGIZ ED O N 1 2 3 4 5 6 7 8 ACU EXT 12V GND H1 TB2 TB3 TB4 OCB8 PC1102 RELAY REV NORMAL KEYS...

Page 51: ...h ribbon cable with J1 Relay Power set on ACU TAMPER TB3 SWITCH KI 00141E 10 14 CONTROL 4 S1 TB1 J1 OUTPUT CONTROL BOARD K1 K2 K3 K4 K5 K6 K7 K8 LED ON RELAY ENERGIZ ED O N 1 2 3 4 5 6 7 8 ACU EXT 12V...

Page 52: ...Communication Mode Keyscan control boards support serial network and reverse network communication modes Reverse network is a Keyscan proprietary application and requires the purchase of a license S2...

Page 53: ...d in the table S2 6 Lockdown This function enables a control unit to lockdown all connected doors or floors via the Client software or a lockdown input Refer to Lockdown Door Floors document on Keysca...

Page 54: ...PB 10 2 or CB 485 not supported not applicable for reverse network S2 4 S2 5 Alternate Panel Serial Selection 0 0 Factory assigned serial Leave on factory assigned setting unless prompted in the Clien...

Page 55: ...0 Vantage 0 1 Future use 0 Off 1 On Notes on Communication Settings The 9600 bit s communication setting is recommended for the CPB 10 2 only Aurora does not support this communication setting The 19...

Page 56: ...19 or higher Vantage version 8 1 18 or higher Circuit Board Card Capacity PC1097 and higher circuit boards are defaulted for 45 000 Aurora and 32 000 System VII and Vantage card storage capacity names...

Page 57: ...the factory default settings whenever you have performed one or more of the following procedures to a control board when a control board has been newly installed when an EPROM or reader PROM has been...

Page 58: ...ress S1 wait 5 seconds Hold down the tamper switch and then momentarily press S3 within 10 seconds Then release the tamper switch This clear memory procedure is shorter in duration for restoring the f...

Page 59: ...ing Communication on a WAN A point to point private network is required where NETCOMs are used on a LAN WAN TCP IP that integrates building to building communication For reverse network communication...

Page 60: ...of most Keyscan products Typically the red wire of the RS 232 cable which is the transmit data output of the PC is connected to the RD pin of most Keyscan products Exceptions NETCOMs When connecting t...

Page 61: ...t used Tape back separately Brown Shield Green Black Red White RS 232 5 conductor 22 AWG shielded cable Maximum 100 Ft 30 M TD RD DCD DTR CTS Red to ground lug Shield Parts List RS 232 Data Cable Cont...

Page 62: ...232 wires tape back shield Note USB communication is slower than direct serial or NETCOM communication Do not connect USB adaptor to modem RS 232 22 AWG shielded cable Maximum 100 ft 30 M Green Black...

Page 63: ...tive cover is re affixed before applying power PC 10 100 Base T Cable Control Board NETCOM2P or NETCOM6P to network Host PC with Communication Manager Parts List to network 10 or 100 Base T Current Dr...

Page 64: ...is isolated TD RD DCD DTR CTS Red IOCB COM1 RX TX Parts List KI 00163E 10 14 Control Board S2 DIP switches 7 8 OFF PC 1097 or later or J16 pins F G OFF PC 1094 PC 1095 12VDC RESET GND TD RD DTR DCD I...

Page 65: ...yscan s reverse network communication Keyscan recommends CAN Bus 1 and CAN Bus 2 are connected on all CIM units Figure 46 CIM Overview CIM Conventions Before connecting please be aware of the followin...

Page 66: ...wing control board firmware EPROM version 7 40 8 20 or higher door control units EPROM version 7 97 8 77 or higher elevator control units supports global time zones only If using a NETCOM2P or NETCOM6...

Page 67: ...COMP version is a PC1051 or later printed circuit board CAN Bus CAN Bus 1 PC to ACU communication CAN Bus 2 ACU to ACU communication for global functions and CIM to CIM Topology Linear does not suppor...

Page 68: ...rol unit See note below CIM Slave J3 0 Note On a communication bus with elevator control units only a global master CIM is not applicable Do not place a jumper on J3 CIM 0 Jumper J4 Jumper J4 must be...

Page 69: ...CIM has selectable serial bit rates The jumper settings are outlined in the following table Bit rates are governed by CAN Bus 1 distances and RS 232 distances Refer to the BPS Distance Chart Set CIM...

Page 70: ...nal on TB1 of each CIM is connected to an earth ground to protect the circuit board and the system from high voltage transients Set the jumpers accordingly on the CIM depending on whether it is a glob...

Page 71: ...on AUX Inputs E 24 23 22 21 20 19 18 17 H1 Connect the ribbon cable from HDR1 on the CIM to the H2 terminal on control board CIM powered from control board via H2 terminal KI 00264E 07 12 TD1 RD1 TD2...

Page 72: ...2 RD2 GND RTS CTS GND RTS CTS B3 B2 B1 B0 Diag J2 RESET CAN2 EGND CAN1 GND V 12V SCKT1 PC106x J1 J7 J8 J6 J5 CAN2 CAN1 1 2 1 2 1 2 1 2 Rx COM COM CAN CAN Tx J3 J4 J9 J12 Power Good COM1 COM2 HDR1 J10...

Page 73: ...B1 B0 Diag J2 RESET CAN2 EGND CAN1 GND V 12V SCKT1 PC106x J1 J7 J8 J6 J5 CAN2 CAN1 1 2 1 2 1 2 1 2 Rx COM COM CAN CAN Tx J3 J4 J9 J12 Power Good Fault HDR1 J10 J11 Black Green Red to COM port CIM 0 CI...

Page 74: ...in order to function Refer to the NETCOM2P CIM or NETCOM6P CIM Programming Guides for programming instructions When configuring CIM 0 with a NETCOM2P or NETCOM6P ensure the NETCOMP version is a PC1051...

Page 75: ...al Master Termination Jumpers ON J5 J6 J7 J8 first last CIM Connect EGND terminal on all CIMs to ground lugs in ACU metal enclosures Global Master Jumper ON J3 CAT 5 CAN Bus Slave Jumper OFF J3 H2 H2...

Page 76: ...nnection is referred to as CIM 0 This CIM unit must have a jumper on J4 Important The NETCOM2 must be programmed with the Keyscan NETCOM Program Tool utility in order to function Refer to the NETCOM2...

Page 77: ...2 Shield to ACU ground lug Insulate shield with PVC tubing such as Alpha p n PVC10516 16 AWG or comparable insulator RS 232 5 conductor shielded 22 AWG cable CAT 5 CAN Bus Termination Jumpers ON J5 J6...

Page 78: ...ostic LED Codes LED Trouble Indication Code Fault B3 B2 B1 B0 0 0 0 0 0 None 0 0 0 1 1 5V logic voltage low 0 0 1 0 2 12V input voltage low 0 0 1 1 3 5V isolated logic supply low 0 1 0 0 4 CAN Bus 1 f...

Page 79: ...y in this mode longer if it is auto matching the bit rate of the ACU or is unable to communicate to the ACU via the global communication port 7 0111 the CIM has entered CIM 0 mode It has been set to p...

Page 80: ...wire connections ensure no short circuits exist when measuring voltages verify the DC polarity is correct for all equipment ensure backup battery is fully charged Following the above guidelines ensure...

Page 81: ...total current Refer to the reader tables in the appendices for current ratings Opposite Add on Board enter the name of the module in the Product Description column and the board s current requirement...

Page 82: ...ion do not mount the transformers or bring 120 240 VAC inside the ACU metal enclosure repeat battery and transformer connections for additional power supplies check ACU voltage test points after power...

Page 83: ...PWR FAIL ACU PWR FAIL READER 8 PC109x Control Board Keyscan p n CAS6105 CAS6105 Cable Use Keyscan p n CAS6105 plug in cable included with DPS15 to connect control board with power supply Diagram shows...

Page 84: ...set to VDC V ohms to test points Com to ground lug in metal enclosure Table 16 Control Board Test Points Voltages Board Test Point Voltage Instructions Notes Reader Terminal D1 WHT 5 VDC White data 1...

Page 85: ...55 Control Board Test Points Voltages READER PWR ACU PWR FAIL FAIL TP1 TP2 TP3 TP4 TP5 Cut View PC109x Control Board ACU Protective Cover Test Point Voltages TP1 12V Reader TP2 12V ACU TP3 12V ACU Fu...

Page 86: ...st Points Communication Test Point Voltage Instructions Notes CA EC Communication Terminal RS 232 connected to ACU Connect voltmeter COM to GND on ACU communication terminal block or green on data cab...

Page 87: ...in attempt to resolve Illuminated abnormal condition Follow restore factory defaults S3 procedure in attempt to resolve RD 1 Red Flashing normal If IOCB function disabled in Client software main proce...

Page 88: ...g normal Control board sending data via communication path determined by S2 switches 7 8 to Client Communication Mgr Not Illuminated If CIM module connected to H2 header for communication with the Cli...

Page 89: ...The CA or EC control board is in clear memory mode The on board piezo emits a cycle of 2 short beeps and then a pause while the control board is in this mode Amber solid The CA or EC control board ha...

Page 90: ...digit 1s count the 2nd binary digit Example If the 10s LED blinks 3 times and the 1s LED blinks 6 times the card has 36 binary bits 36 bit Wiegand card Figure 59 Location of Wiegand Bit Counter LEDs...

Page 91: ...lation on page 80 Some readers require an independent power supply as noted in the table Power Specifications The following table outlines reader power specifications Table 20 Keyscan HID Reader Power...

Page 92: ...12 VDC 75 mA 900P KRP15SE 12 VDC 75 mA 910P KRP40SE 12 VDC 85 mA 920P KRPK40SE 12 VDC 95 mA 921P Installation Notes on Proximity Readers Do not run reader cables in same conduit with AC power or signa...

Page 93: ...e with 00 LED If readers are single LED type 06 substitute the brown wire in place of the orange wire S16 5 ON dual LED 00 S16 5 OFF single LED 06 C1 Beep When the pre alert wire is connected to C1 Be...

Page 94: ...ug D1 White D0 Green PWR Red GND Black LED Brown Reader terminal on control board Blue used for pre alert otherwise isolate and tape back If connecting external sound device see Pre Alert Relay Option...

Page 95: ...D Brown PWR Red D0 Green Pre alert Blue Pre alert Blue 6 conductors shielded 22 AWG Maximum 500 feet 152 4 m Orange wire not used Isolate tape back Orange Reader terminal on control board LED D1 WHT D...

Page 96: ...Pre alert Blue 6 conductors shielded 22 AWG Maximum 500 feet 152 4 m Orange wire not used Isolate tape back Orange Diagram applies to PC109x or newer control board For Rev 10 or older control boards...

Page 97: ...e recommended mode which offers higher security when connected read mode set for secure sector or CSN If secure sector unrecognized subsequently reads the CSN sector of card Connect to GND Black wire...

Page 98: ...hite D0 Green PWR Red GND Black LED Orange Reader terminal on control board LED D1 WHT D0 GRN PWR RED GND BLK C1 BEEP Pre alert Yellow Pre alert Yellow Yellow Beeper used for pre alert otherwise isola...

Page 99: ...round Lug D1 White D0 Green PWR Red GND Black LED Orange Reader terminal on control board LED D1 WHT D0 GRN PWR RED GND BLK C1 BEEP Pre alert Yellow Pre alert Yellow Yellow Beeper used for pre alert o...

Page 100: ...ded 22 AWG 500 ft 152 4 m maximum Reader terminal on control board LED D1 WHT D0 GRN PWR RED GND BLK C1 BEEP LED D1 White D0 Green PWR Red GND Black Pre alert Yellow D1 White D0 Green PWR Red GND Blac...

Page 101: ...ft 152 4 m HID 5375 DIP Switches Jumpers SW5 switches 1 2 ON switches 3 to 8 OFF SW2 switch 1 ON switches 2 to 8 OFF SW1 switches 1 to 4 ON switches 5 to 8 OFF P4 jumper ON pins 1 2 P3 jumper ON pins...

Page 102: ...2 5 8 0 3 6 9 Black position of DIP switch head 6 conductors shielded 22 AWG Maximum 500 ft 152 4 m Reader terminal on control board LED D1 WHT D0 GRN PWR RED GND BLK C1 BEEP To LED Green terminal Pre...

Page 103: ...d LED D1 WHT D0 GRN PWR RED GND BLK C1 BEEP LED Orange D1 White D0 Green PWR Red GND Black Pre alert Yellow Pre alert Yellow Yellow Beeper used for pre alert otherwise isolate and tape back If connect...

Page 104: ...1 White D0 Green PWR Red GND Black Pre alert Yellow Yellow Beeper used for pre alert otherwise isolate and tape back If connecting external sound device see Pre Alert Relay Option or refer to ACU cut...

Page 105: ...S 485 UART R Do not connect to Keyscan P2 5 Violet Open Collector Do not connect to Keyscan P2 4 White Wiegand Data 1 P2 3 Green Wiegand Data 0 P2 2 RS 485 USB D Do not connect to Keyscan P2 1 RS 485...

Page 106: ...ED terminal on ACU reader terminal Connect shield to ACU ground lug 18 or 22 AWG shielded cable acceptable LED Orange D1 White D0 Green PWR Red GND Black Pre alert Yellow Shield ACU Ground Lug D1 Whit...

Page 107: ...shielded 18 AWG 500 ft 152 4 m maximum P2 1 DC P2 2 Ground Shield P2 3 Green LED Control P1 7 Data 1 P1 6 Data 0 P1 5 Ground Shield ACU Ground Lug White Green Red Black 2 Brown Black 1 Black Black 2...

Page 108: ...ange D1 White D0 Green PWR Red GND Black Pre alert Yellow Yellow Beeper used for pre alert otherwise isolate and tape back If connecting external sound device see Pre Alert Relay Option or refer to AC...

Page 109: ...LED Orange D1 White D0 Green PWR Red GND Black Pre alert Yellow Yellow Beeper used for pre alert otherwise isolate and tape back If connecting external sound device see Pre Alert Relay Option or refe...

Page 110: ...ange D1 White D0 Green PWR Red GND Black Pre alert Yellow Yellow Beeper used for pre alert otherwise isolate and tape back If connecting external sound device see Pre Alert Relay Option or refer to AC...

Page 111: ...White D0 Green PWR Red GND Black Pre alert Yellow Yellow Beeper used for pre alert otherwise isolate and tape back If connecting external sound device see Pre Alert Relay Option or refer to ACU cut s...

Page 112: ...X 620 24 VDC 1 2 A Requires 18 AWG cable Connect to separate 24 VDC 2 Amp linear power supply Not supplied with ACU kit PXK 501 12 VDC 80 mA 20 mA interface 100 mA Current consumption includes interfa...

Page 113: ...with electrical tape 6 conductors shielded 22 AWG Maximum 500 ft 152 4 m LED Brown D1 White D0 Green PWR Red GND Black Pre alert Blue Blue Beeper used for pre alert otherwise isolate and tape back If...

Page 114: ...1 2 Shield not connected Isolate with electrical tape 6 conductors shielded 22 AWG 500 ft 152 4m maximum Shield ACU Ground Lug White Green Red Black 2 Brown Black 1 Black to separate DC power supply P...

Page 115: ...PX 620 requires tuning tune only once Excessive tuning may permanently damage the reader Refer to the Indala documentation for instructions on tuning Brown White Green Red Black 1 2 Shield Shield ACU...

Page 116: ...nd tape back If connecting external sound device see Pre Alert Relay Option or refer to ACU cut sheet enclosed with panel for ACU OCB8 relay assignments Pre alert Blue Shield not connected Isolate wit...

Page 117: ...conduit with AC power or signal cables Keep keypad cables at a minimum distance of 12 inches or 30 centimetres from AC computer data telephone data or electric lock device cables Do not install keypa...

Page 118: ...d memory stores 28 personal identification numbers PIN If orange wire is not used tape back See instructions with WSSKP 1 keypad for connections with third party devices Brown White Green Blue Black S...

Page 119: ...a reader keypad combination is required for a new installation Brown White Green Red Black Shield not connected Isolate with electrical tape Shield ACU Ground Lug Brown White Green Red Black 6 conduc...

Page 120: ...lower receivers and transmitters WIEEX2 Functions The following table outlines the functions and capabilities of WIEEX2 extenders Table 23 WIEEX2 WIEEX2 Functions Capabilities WIEEX2 firmware 6 00 or...

Page 121: ...the reader door contact request to exit device auxiliary input and door lock whichever are applicable Connect the WIEEX2 receiver RX to the appropriate ACU terminals Power the transmitter with a 12 VD...

Page 122: ...ure 84 Wiegand Extender Overview Reader Exit Device Transmitter WIEEX2 Tx Receiver WIEEX2 Rx ACU Auxiliary Input Reader Exit Device Auxiliary Input Communication Tx Rx Door Unlock Output Door Contact...

Page 123: ...ly local 12 VDC Control Board Reader Terminal J1 shorted J1 shorted Trigger for Transmitter RA2 OC D1 White D0 Green GND Black DC Supply 12 VDC COM Maximum 4000 Connect H1 to OCB 8 Door 1 2 1 2 1 2 3...

Page 124: ...x Receiver RB5 RB4 Connect to GND RB4 RB5 with switch to change OCB 8 relay 2 3 connected on WIEEX Tx GND OCB 8 Relay 1 Follows LED BRN used for P3 signalling 3rd party devices Relay 2 Follows RB4 Doo...

Page 125: ...additional OCB 8 is required Accessibility HC Output Relays Ensure that the accessibility HC output relay matches the door output as indicated below Table 26 Accessibility HC Relay Door Assignment Co...

Page 126: ...DTR DCD RD TD GND OCB 8 powered through ribbon cable with J1 Relay Power set on ACU TAMPER TB3 SWITCH KI 00227E 10 14 CONTROL 4 S1 TB1 J1 OUTPUT CONTROL BOARD K1 K2 K3 K4 K5 K6 K7 K8 LED ON RELAY ENER...

Page 127: ...Power set on ACU CONTROL 4 KI 00228E 10 14 CONTROL 2 CONTROL 5 TAMPER TB3 SWITCH S1 TB1 J1 OUTPUT CONTROL BOARD K1 K2 K3 K4 K5 K6 K7 K8 LED ON RELAY ENERGIZ ED O N 1 2 3 4 5 6 7 8 ACU EXT 12V GND H1...

Page 128: ...00229E 10 14 CONTROL 2 CONTROL 5 TAMPER TB3 SWITCH S1 TB1 J1 OUTPUT CONTROL BOARD K1 K2 K3 K4 K5 K6 K7 K8 LED ON RELAY ENERGIZ ED O N 1 2 3 4 5 6 7 8 ACU EXT 12V GND H1 TB2 TB3 TB4 OCB8 PC1102 RELAY R...

Page 129: ...r contact as indicated in the following table Table 27 Pre alert Relay to Door Assignments Control Board OCB 8 Pre alert Outputs Pre alert Relay on OCB Door Contact Ribbon Cable Connection CA250B OCB...

Page 130: ...d at door DC Supply TAMPER TB3 SWITCH KI 00230E 10 14 CONTROL 4 S1 TB1 J1 OUTPUT CONTROL BOARD K1 K2 K3 K4 K5 K6 K7 K8 LED ON RELAY ENERGIZ ED O N 1 2 3 4 5 6 7 8 ACU EXT 12V GND H1 TB2 TB3 TB4 OCB8 P...

Page 131: ...oor DC Supply KI 00231E 10 14 CONTROL 4 S1 TB1 J1 OUTPUT CONTROL BOARD K1 K2 K3 K4 K5 K6 K7 K8 LED ON RELAY ENERGIZ ED O N 1 2 3 4 5 6 7 8 ACU EXT 12V GND H1 TB2 TB3 TB4 OCB8 PC1102 RELAY REV NORMAL K...

Page 132: ...KI 00232E 10 14 S1 S2 S3 O N 1 2 3 4 5 6 7 8 9 10 11 12 S1 TB1 J1 OUTPUT CONTROL BOARD K1 K2 K3 K4 K5 K6 K7 K8 LED ON RELAY ENERGIZ ED O N 1 2 3 4 5 6 7 8 ACU EXT 12V GND H1 TB2 TB3 TB4 OCB8 PC1102 R...

Page 133: ...global inputs and outputs refer to the Global Inputs Outputs Time Zones Setup Guide on the Keyscan documents CD OCB 8 Global IO Assignments The following table outlines global output relay assignment...

Page 134: ...CCTV etc OCB 8 Control Board Note DIP switches set relays for normal or reverse as indicated by the arrows S1 TB1 J1 OUTPUT CONTROL BOARD K1 K2 K3 K4 K5 K6 K7 K8 LED ON RELAY ENERGIZ ED O N 1 2 3 4 5...

Page 135: ...ased on 12 VDC Do not exceed the recommended operating maximum of a power supply See tables for Keyscan HID and Indala reader voltage current ratings Table 29 Circuit Board Current Ratings Circuit Boa...

Page 136: ...ed OFF Aux Output Relay Normal Door Held Open Alarm Aux Output Relay Normal Alarm Tripped Aux Output Relay Reversed Door Held Open Alarm Aux Output Relay Reversed Alarm Tripped Aux Output Relay Normal...

Page 137: ...ty Relay Reversed Normal Elevator Relay Normal Unsecured ON Elevator Relay Normal Secured OFF Elevator Relay Reversed Unsecured ON Elevator Relay Reversed Secured OFF Legend LED On LED Off Manual Outp...

Page 138: ...r liability concerning this product In no event shall Keyscan be liable for any direct indirect or consequential damages loss of anticipated profits loss of time or any other losses incurred by the bu...

Page 139: ...ds 15 G global outputs 133 ground lugs 22 grounding 13 H HID readers connections 91 power specifications 91 I Indala readers connections 112 power specifications 112 J jumpers restore ACU default sett...

Page 140: ...Keyscan Inc Technical Guide PC109x 04 15 140 Wiegand Extenders WIEEX 120...

Reviews: