KEY RK-2001W2N Operation Manual Download Page 9

9

STB

- the controller has additional protection from overheating which is independent

from the processor. In case the temperature increases over 95°C, the control process

is turned off by turning the fan off and launching the central heating pump. The fan and

the pump are turned on to the control process again when temperature drops below

89°C. STB circuit enables more precise boiler work control and reduces overheating

possibility.

5.6. No fuel.

No-fuel testing time during fuel firing start [Fd2h]

- after switching to WORK mode,

if water temperature does not increase by 2°C in programmed time, the control

process will be turned off and the display will show the message:

[FUEL]

. You can

return to previous mode by pressing STOP button. No fuel testing time during fuel

firing is finished after the set temperature is achieved.

No-fuel testing time during work mode [Fb2h]

- in WORK mode, if temperature of

water in the boiler decreases below temperature set with the thermostat, by hysteresis

value, and does not increase by 2°C in the programmed time, the control process will

be turned off and the display will show the message:

[FUEL]

. You can cancel the

alarm by pressing STOP button.

5.7. Additional output.

Additional output work mode [Ar 0]

- the controller is equipped with a multipurpose

output that can work in one of following modes:

-

[Ar 0] mode

- output may control oil or gas boiler if such boiler exists in the

heating circuit. After switching the controller on with the main power switch, the

additional boiler is turned off and it turnes on again when there is no fuel in the solid

fuel boiler. This function is useful in heating systems where the solid fuel boiler is used

to cut heating costs. After erasing no fuel alarm by pressing STOP button, the

additional boiler is again turned off and the controller works again.

-

[Ar 1] mode

- output may control additional alarm signaling system. Boiler

temperature sensor malfunction, overheating or no fuel alarm will turn on the

additional alarm.

-

[Ar 2] mode

- output may control mixing valve servo-motor. Controlling the

mixing valve requires room thermostat to be connected to the controller. The mixing

valve is being opened and closed depending on the room thermostat input.

Additionally, mixing valve is opened in case of overheating or boiler temperature

sensor malfunction.

-

[Ar 3] mode

- output may control boiler emergency cooling system (e.g. pump).

In this mode the additional output is turned on in case of boiler overheating or boiler

temperature sensor error alarm.

Summary of Contents for RK-2001W2N

Page 1: ...OPERATION MANUAL RK 2001W2N SOLID FUEL FIRED BOILER TEMPERATURE CONTROLLER Version C112...

Page 2: ......

Page 3: ...ate sockets in the rear of the controller The temperature sensor should be placed in a measurement hole in the boiler Picture 2 shows diagram of electrical connection of the controller CAUTION Before...

Page 4: ...50 c hold up of burning in WORK mode 50 U heating of hot water in SUMMER mode 70 d total bacteria control heating up of hot water up to 75 C 4 Setting up the user parameters Holding OK button enters t...

Page 5: ...tton E g 70 d will appear on the display After reaching 75 C in the hot water tank the controller will return to its state before choosing this option CAUTION the total bacteria control function can s...

Page 6: ...r 1 hot water priority 2 no hot water priority 3 mixing pump 0 3 1 0 L 45 Minimum boiler temperature 30 65 1 C 45 H 85 Maximum boiler temperature 80 90 1 C 85 h 2 Boiler temperature hysteresis 1 10 1...

Page 7: ...ter When this parameter is set to a value between 0 and 10 it defines time in minutes of gradual increase of fan speed from its minimum value n 40 to value r 50 for smooth start Fan work time n15 time...

Page 8: ...ater pump working with priority ur 2 value hot water tank working without priority ur 3 value means controlling of the returning water mixing pump in the boiler with the launch temperature of u 50 and...

Page 9: ...rm by pressing STOP button 5 7 Additional output Additional output work mode Ar 0 the controller is equipped with a multipurpose output that can work in one of following modes Ar 0 mode output may con...

Page 10: ...put allowing to connect any kind of room thermostat with contact output When temperature in the room is below desired temperature the central heating pump is turned on and the room thermostat indicato...

Page 11: ...oiler remove the controller from the slot in the boiler disconnect all connectors with leads from the controller 9 Specifications Voltage 230V 10 50Hz Power consumption 4VA Temperature measurement ran...

Page 12: ...12 Picture 2 RK 2001W2N connection diagram...

Page 13: ...p hot water desired temperature uh 5 Hot water heating hysteresis ur 0 Work mode of hot water pump 0 no hot water 1 hot water priority 2 no hot water priority 3 mixing pump L 45 Minimum boiler tempera...

Page 14: ...14...

Page 15: ......

Page 16: ...Producer P W KEY 11 200 Bartoszyce ul Bohater w Warszawy 67 tel 89 763 50 50 fax 89 763 50 51 www pwkey pl e mail pwkey onet pl...

Reviews: