Table 1. User parameters list.

Disp.

Parameter

Min Max Step Factory

default

C 45 Boiler desired temperature.

L 45 H 85 1°C

L 45

co C Central heating pump work when „C” (pump off when „-”).

-

C

C

cu u Heating up „d” - total bacteria control in hot water tank.

u

d

u

50°C Water temperature in hot water tank.

End Exit from user mode.

4.1. Boiler water temperature.

The desired boiler temperature [C 45]

– is the temperature which the controller will

try to achieve in WORK mode. It is set by direct turning of the knob and is indicated by

a short display.

4.2. Central heating pump work [co C]

– WINTER/SUMMER mode – character „C”

indicates that the central heating pump is working. In summer time the heating can be

turned off by choosing the value “-“ with the (-) button which means turning off the

central heating pump.

4.3. Total bacteria control in the hot water tank [cu u]

– heating up - the controller

allows to manually launch the total bacteria control process in which the boiler reaches

the temperature of 75°C in the hot water tank. In order to start the total bacteria control

process the boiler should be in WORK mode (this mode can be turned on by START

button). E.g. [70°d] will appear on the display. After reaching 75°C in the hot water

tank the controller will return to its state before choosing this option.

CAUTION:

the total bacteria control function can switched on at night when the water

from the hot water tank is not used to prevent the users from burn injury.

4.4. Water temperature readout in hot water tank [ 50°]

– this parameter shows the

measured temperature value in the hot water tank.

4.5. Exit from user mode

– choosing the

[End]

on the display and pressing OK

button causes exit from the parameter setting. Exit from this mode will also occur if no

button is pressed for 1 minute.

5. Parameter setting – the service mode.

Holding OK button for more than 3 seconds enters the service mode where you can

review and change the parameters. It is indicated by flashing of the room thermostat

indicator. You can look through parameters with < and > arrow buttons. After choosing

the desired parameter (indicated by value of the parameter flashing slowly) you can

change the parameter value directly by turning the knob. The change of the value is

indicated by this value flashing. The change of the value will occur after pressing

– or + button. Pressing OK button will confirm the changes. After that the controller

allows to choose another parameter with < > buttons. If you do not want to change the

Summary of Contents for RK-2001W2N

Page 1: ...OPERATION MANUAL RK 2001W2N SOLID FUEL FIRED BOILER TEMPERATURE CONTROLLER Version C112...

Page 2: ......

Page 3: ...ate sockets in the rear of the controller The temperature sensor should be placed in a measurement hole in the boiler Picture 2 shows diagram of electrical connection of the controller CAUTION Before...

Page 4: ...50 c hold up of burning in WORK mode 50 U heating of hot water in SUMMER mode 70 d total bacteria control heating up of hot water up to 75 C 4 Setting up the user parameters Holding OK button enters t...

Page 5: ...tton E g 70 d will appear on the display After reaching 75 C in the hot water tank the controller will return to its state before choosing this option CAUTION the total bacteria control function can s...

Page 6: ...r 1 hot water priority 2 no hot water priority 3 mixing pump 0 3 1 0 L 45 Minimum boiler temperature 30 65 1 C 45 H 85 Maximum boiler temperature 80 90 1 C 85 h 2 Boiler temperature hysteresis 1 10 1...

Page 7: ...ter When this parameter is set to a value between 0 and 10 it defines time in minutes of gradual increase of fan speed from its minimum value n 40 to value r 50 for smooth start Fan work time n15 time...

Page 8: ...ater pump working with priority ur 2 value hot water tank working without priority ur 3 value means controlling of the returning water mixing pump in the boiler with the launch temperature of u 50 and...

Page 9: ...rm by pressing STOP button 5 7 Additional output Additional output work mode Ar 0 the controller is equipped with a multipurpose output that can work in one of following modes Ar 0 mode output may con...

Page 10: ...put allowing to connect any kind of room thermostat with contact output When temperature in the room is below desired temperature the central heating pump is turned on and the room thermostat indicato...

Page 11: ...oiler remove the controller from the slot in the boiler disconnect all connectors with leads from the controller 9 Specifications Voltage 230V 10 50Hz Power consumption 4VA Temperature measurement ran...

Page 12: ...12 Picture 2 RK 2001W2N connection diagram...

Page 13: ...p hot water desired temperature uh 5 Hot water heating hysteresis ur 0 Work mode of hot water pump 0 no hot water 1 hot water priority 2 no hot water priority 3 mixing pump L 45 Minimum boiler tempera...

Page 14: ...14...

Page 15: ......

Page 16: ...Producer P W KEY 11 200 Bartoszyce ul Bohater w Warszawy 67 tel 89 763 50 50 fax 89 763 50 51 www pwkey pl e mail pwkey onet pl...

Reviews: