5.1. Fan work parameters.

Fan power [Π100]

- this value defines power of the fan. When „Π” parameter is set to

„0-10” this is the maximum power of the fan which can be achieved during automatic

fan control.

Minimum fan power [n 40]

- lowest fan power which can be used when automatic

fan speed control is on and when fan speed is gradually increased during boiler start.

Fan speed decrease coefficient [Πh 2]

- this parameter influences the way fan

speed is reduced when boiler tremperature is approaching its desired value. E.g.

setting this parameter to 2 means that when the controller is in WORK mode and

boiler temperature is 2°C lower than desired boiler temperature the fan will work with

its maximum power [Π100]. Further increase of boiler temperature will cause fan

speed to be reduced gradually to its minimum power [n 40].

Automatic fan speed control [Πr 0]

- it is on, when this parameter is set to „0-10”

and causes automatic fan speed decrease when temperature of water in the boiler

reaches desired temperature. If this parameter is set to „-”, the fan automatic smooth

speed control is disabled and the fan can work with power set by „Π” parameter. When

this parameter is set to a value between 0 and 10 it defines time (in minutes) of

gradual increase of fan speed from its minimum value [n 40] to value [r 50] for smooth

start.

Fan work time [Πn15]

- time of turning the fan on for a while, to remove accumulated

gases. Setting the parameter to „--” turns this function off. This function can be active

in WORK mode.

Fan pause time [Nu 6]

- time between fan work periods.

Maximum fan speed during boiler start [r 50]

- this parameter sets maximum fan

power used during boiler start. If parameter [Πr 0] is set to „0", then this parameter

sets the fan power used during boiler start.

Boiler start completed hysteresis [rh 5]

- this parameter defines, how many degrees

before reaching desired temperature boiler start phase is considered to be finished.

Finishing start mode causes the controller to enter work mode.

5.2. Central heating pump parameters.

Central heating pump launch temperature [P 40]

– the value of temperature of the

water in the boiler which causes start of the central heating pump. Central heating

pump works independently from the control process and is launched additionally in

case of boiler overheat.

Central heating pump launch hysteresis [Ph 2]

- this parameter defines what value

should temperature decrease by, below central heating pump launch temperature so

that the pump turns off.

Summary of Contents for RK-2001W2N

Page 1: ...OPERATION MANUAL RK 2001W2N SOLID FUEL FIRED BOILER TEMPERATURE CONTROLLER Version C112...

Page 2: ......

Page 3: ...ate sockets in the rear of the controller The temperature sensor should be placed in a measurement hole in the boiler Picture 2 shows diagram of electrical connection of the controller CAUTION Before...

Page 4: ...50 c hold up of burning in WORK mode 50 U heating of hot water in SUMMER mode 70 d total bacteria control heating up of hot water up to 75 C 4 Setting up the user parameters Holding OK button enters t...

Page 5: ...tton E g 70 d will appear on the display After reaching 75 C in the hot water tank the controller will return to its state before choosing this option CAUTION the total bacteria control function can s...

Page 6: ...r 1 hot water priority 2 no hot water priority 3 mixing pump 0 3 1 0 L 45 Minimum boiler temperature 30 65 1 C 45 H 85 Maximum boiler temperature 80 90 1 C 85 h 2 Boiler temperature hysteresis 1 10 1...

Page 7: ...ter When this parameter is set to a value between 0 and 10 it defines time in minutes of gradual increase of fan speed from its minimum value n 40 to value r 50 for smooth start Fan work time n15 time...

Page 8: ...ater pump working with priority ur 2 value hot water tank working without priority ur 3 value means controlling of the returning water mixing pump in the boiler with the launch temperature of u 50 and...

Page 9: ...rm by pressing STOP button 5 7 Additional output Additional output work mode Ar 0 the controller is equipped with a multipurpose output that can work in one of following modes Ar 0 mode output may con...

Page 10: ...put allowing to connect any kind of room thermostat with contact output When temperature in the room is below desired temperature the central heating pump is turned on and the room thermostat indicato...

Page 11: ...oiler remove the controller from the slot in the boiler disconnect all connectors with leads from the controller 9 Specifications Voltage 230V 10 50Hz Power consumption 4VA Temperature measurement ran...

Page 12: ...12 Picture 2 RK 2001W2N connection diagram...

Page 13: ...p hot water desired temperature uh 5 Hot water heating hysteresis ur 0 Work mode of hot water pump 0 no hot water 1 hot water priority 2 no hot water priority 3 mixing pump L 45 Minimum boiler tempera...

Page 14: ...14...

Page 15: ......

Page 16: ...Producer P W KEY 11 200 Bartoszyce ul Bohater w Warszawy 67 tel 89 763 50 50 fax 89 763 50 51 www pwkey pl e mail pwkey onet pl...

Reviews: