KEY RK-2001W2N Operation Manual Download Page 8

8

The work mode and pause time of CH pump [Pc 2]

- in STOP mode or when the

room thermostat circuit is not shorted, CO pump is turned on for 30 seconds to move

water in the heating system. This parameter controls the repeat time. Setting this

parameter to „--” turns this function off. In case of some heating systems the pump

should work independently of room thermostat. In such case the parameter should be

set to value „F”.

5.3. Preparation of hot tap water

The hot water tank temperature [u 50]

– temperature value which will be kept in the

hot water tank.

The heating hysteresis of the hot water tank [uh 5]

– valve which the temperature

in the tank has to decrease by so that the hot water pump turnes on in order to heat up

the water in the tank.

Work mode of hot water pum [ur 0]

the

[ur 0]

value indicates no sensor or hot water pump. The sensor is not taken

into account in testing failures, i.e. it can remain unconnected and in the user

parameter menu there is only the desired boiler thermostat temperature

displayed.

[ur 1]

value - hot water pump working with priority

[ur 2]

value - hot water tank working without priority

[ur 3]

value - means controlling of the returning water mixing pump in the

boiler with the launch temperature of [u 50] and hysteresis [uh 5].

5.4. Boiler work temperature setting.

Minimum boiler temperature [L 45]

- minimum temperature which you can set with

the boiler thermostat knob.

Maximum boiler temperature [H 85]

- maximum temperature which you can set with

the boiler thermostat knob.

Boiler temperature hysteresis [h 2]

- this parameter defines what value should

temperature of water in the boiler decrease by, below temperature set with the

thermostat knob so that the fan turns on.

5.5. Boiler overheating protection.

Boiler overheating temperature [A 99]

- value, exceeding which causes permanent

turn off of the fan to prevent boiler overheating. After the temperature increases above

80°C the central heating pump is turned on to cool down the boiler. Overheating mode

is indicated by displaying error [E 2] on the display. It can be turned off by pressing

STOP button, but only when temperature decreases below this temperature. Fan turn

off also occurs in case of damage of the boiler temperature sensor which is displayed

on the display with error [E 1].

Summary of Contents for RK-2001W2N

Page 1: ...OPERATION MANUAL RK 2001W2N SOLID FUEL FIRED BOILER TEMPERATURE CONTROLLER Version C112...

Page 2: ......

Page 3: ...ate sockets in the rear of the controller The temperature sensor should be placed in a measurement hole in the boiler Picture 2 shows diagram of electrical connection of the controller CAUTION Before...

Page 4: ...50 c hold up of burning in WORK mode 50 U heating of hot water in SUMMER mode 70 d total bacteria control heating up of hot water up to 75 C 4 Setting up the user parameters Holding OK button enters t...

Page 5: ...tton E g 70 d will appear on the display After reaching 75 C in the hot water tank the controller will return to its state before choosing this option CAUTION the total bacteria control function can s...

Page 6: ...r 1 hot water priority 2 no hot water priority 3 mixing pump 0 3 1 0 L 45 Minimum boiler temperature 30 65 1 C 45 H 85 Maximum boiler temperature 80 90 1 C 85 h 2 Boiler temperature hysteresis 1 10 1...

Page 7: ...ter When this parameter is set to a value between 0 and 10 it defines time in minutes of gradual increase of fan speed from its minimum value n 40 to value r 50 for smooth start Fan work time n15 time...

Page 8: ...ater pump working with priority ur 2 value hot water tank working without priority ur 3 value means controlling of the returning water mixing pump in the boiler with the launch temperature of u 50 and...

Page 9: ...rm by pressing STOP button 5 7 Additional output Additional output work mode Ar 0 the controller is equipped with a multipurpose output that can work in one of following modes Ar 0 mode output may con...

Page 10: ...put allowing to connect any kind of room thermostat with contact output When temperature in the room is below desired temperature the central heating pump is turned on and the room thermostat indicato...

Page 11: ...oiler remove the controller from the slot in the boiler disconnect all connectors with leads from the controller 9 Specifications Voltage 230V 10 50Hz Power consumption 4VA Temperature measurement ran...

Page 12: ...12 Picture 2 RK 2001W2N connection diagram...

Page 13: ...p hot water desired temperature uh 5 Hot water heating hysteresis ur 0 Work mode of hot water pump 0 no hot water 1 hot water priority 2 no hot water priority 3 mixing pump L 45 Minimum boiler tempera...

Page 14: ...14...

Page 15: ......

Page 16: ...Producer P W KEY 11 200 Bartoszyce ul Bohater w Warszawy 67 tel 89 763 50 50 fax 89 763 50 51 www pwkey pl e mail pwkey onet pl...

Reviews: