KEY RK-2001W2N Operation Manual Download Page 4

4

Picture 1. Front plate of the RK-2001W2N controller

Basic operation of the controller is carried out by setting the desired temperature

with boiler thermostat knob, other functions are carried out according to parameters

programmed in service mode. The change in the boiler temperature setting is

displayed on the display for a few seconds, e.g.

[C 80]

and this value means the

temperature of the water in the boiler which the controller will be trying to achieve. You

can also check this value by pressing OK button for a short time. After pressing

START button the fan starts to work and the control process begins. STOP button

stops the fan for example to add fuel.

If the controller is not in user or service mode the display shows water temperature

in the boiler and the last character on the display defines the mode which the

controller is currently in:

for example:

[50º-] - STOP mode

[50ºC] - WORK mode

[50ºc] - hold up of burning in WORK mode

[50ºU] – heating of hot water in SUMMER mode

[70ºd] – total bacteria control – heating up of hot water

up to 75ºC.

4. Setting up the user parameters.

Holding OK button enters the user mode and allows to review and is indicated by

fast flashing of the room thermostat indicator. You can look through the parameters

with < and > arrow buttons. After choosing the desired parameter you can switch to

the change mode of the parameter by pressing OK button - it is indicated by the value

of the parameter flashing. Change of the parameter is done by pressing - or + buttons.

You can confirm new settings by pressing OK button and after that the controller

allows to choose another parameter (with < > buttons). If you do not want to change

the parameter value with the < or > button choose [End] and press OK or wait for 1

minute – the controller will exit the service mode and will indicate the temperature of

the water in the boiler.

CAUTION:

If in the controller the hot water pump is turned off in the user menu. After

pressing OK, you can only read the set temperature value of the boiler thermostat.

Summary of Contents for RK-2001W2N

Page 1: ...OPERATION MANUAL RK 2001W2N SOLID FUEL FIRED BOILER TEMPERATURE CONTROLLER Version C112...

Page 2: ......

Page 3: ...ate sockets in the rear of the controller The temperature sensor should be placed in a measurement hole in the boiler Picture 2 shows diagram of electrical connection of the controller CAUTION Before...

Page 4: ...50 c hold up of burning in WORK mode 50 U heating of hot water in SUMMER mode 70 d total bacteria control heating up of hot water up to 75 C 4 Setting up the user parameters Holding OK button enters t...

Page 5: ...tton E g 70 d will appear on the display After reaching 75 C in the hot water tank the controller will return to its state before choosing this option CAUTION the total bacteria control function can s...

Page 6: ...r 1 hot water priority 2 no hot water priority 3 mixing pump 0 3 1 0 L 45 Minimum boiler temperature 30 65 1 C 45 H 85 Maximum boiler temperature 80 90 1 C 85 h 2 Boiler temperature hysteresis 1 10 1...

Page 7: ...ter When this parameter is set to a value between 0 and 10 it defines time in minutes of gradual increase of fan speed from its minimum value n 40 to value r 50 for smooth start Fan work time n15 time...

Page 8: ...ater pump working with priority ur 2 value hot water tank working without priority ur 3 value means controlling of the returning water mixing pump in the boiler with the launch temperature of u 50 and...

Page 9: ...rm by pressing STOP button 5 7 Additional output Additional output work mode Ar 0 the controller is equipped with a multipurpose output that can work in one of following modes Ar 0 mode output may con...

Page 10: ...put allowing to connect any kind of room thermostat with contact output When temperature in the room is below desired temperature the central heating pump is turned on and the room thermostat indicato...

Page 11: ...oiler remove the controller from the slot in the boiler disconnect all connectors with leads from the controller 9 Specifications Voltage 230V 10 50Hz Power consumption 4VA Temperature measurement ran...

Page 12: ...12 Picture 2 RK 2001W2N connection diagram...

Page 13: ...p hot water desired temperature uh 5 Hot water heating hysteresis ur 0 Work mode of hot water pump 0 no hot water 1 hot water priority 2 no hot water priority 3 mixing pump L 45 Minimum boiler tempera...

Page 14: ...14...

Page 15: ......

Page 16: ...Producer P W KEY 11 200 Bartoszyce ul Bohater w Warszawy 67 tel 89 763 50 50 fax 89 763 50 51 www pwkey pl e mail pwkey onet pl...

Reviews: