KEY RK-2001W2N Operation Manual Download Page 1

OPERATION MANUAL

RK-2001W2N

SOLID FUEL FIRED

BOILER TEMPERATURE CONTROLLER

Version C112

Summary of Contents for RK-2001W2N

Page 1: ...OPERATION MANUAL RK 2001W2N SOLID FUEL FIRED BOILER TEMPERATURE CONTROLLER Version C112...

Page 2: ......

Page 3: ...ate sockets in the rear of the controller The temperature sensor should be placed in a measurement hole in the boiler Picture 2 shows diagram of electrical connection of the controller CAUTION Before...

Page 4: ...50 c hold up of burning in WORK mode 50 U heating of hot water in SUMMER mode 70 d total bacteria control heating up of hot water up to 75 C 4 Setting up the user parameters Holding OK button enters t...

Page 5: ...tton E g 70 d will appear on the display After reaching 75 C in the hot water tank the controller will return to its state before choosing this option CAUTION the total bacteria control function can s...

Page 6: ...r 1 hot water priority 2 no hot water priority 3 mixing pump 0 3 1 0 L 45 Minimum boiler temperature 30 65 1 C 45 H 85 Maximum boiler temperature 80 90 1 C 85 h 2 Boiler temperature hysteresis 1 10 1...

Page 7: ...ter When this parameter is set to a value between 0 and 10 it defines time in minutes of gradual increase of fan speed from its minimum value n 40 to value r 50 for smooth start Fan work time n15 time...

Page 8: ...ater pump working with priority ur 2 value hot water tank working without priority ur 3 value means controlling of the returning water mixing pump in the boiler with the launch temperature of u 50 and...

Page 9: ...rm by pressing STOP button 5 7 Additional output Additional output work mode Ar 0 the controller is equipped with a multipurpose output that can work in one of following modes Ar 0 mode output may con...

Page 10: ...put allowing to connect any kind of room thermostat with contact output When temperature in the room is below desired temperature the central heating pump is turned on and the room thermostat indicato...

Page 11: ...oiler remove the controller from the slot in the boiler disconnect all connectors with leads from the controller 9 Specifications Voltage 230V 10 50Hz Power consumption 4VA Temperature measurement ran...

Page 12: ...12 Picture 2 RK 2001W2N connection diagram...

Page 13: ...p hot water desired temperature uh 5 Hot water heating hysteresis ur 0 Work mode of hot water pump 0 no hot water 1 hot water priority 2 no hot water priority 3 mixing pump L 45 Minimum boiler tempera...

Page 14: ...14...

Page 15: ......

Page 16: ...Producer P W KEY 11 200 Bartoszyce ul Bohater w Warszawy 67 tel 89 763 50 50 fax 89 763 50 51 www pwkey pl e mail pwkey onet pl...