background image

14

228-1692 REV 8

 090418

KEPCO, INC. 



 131-38 SANFORD AVENUE 



  FLUSHING, NY. 11355 U.S.A.



  TEL (718) 461-7000



 FAX (718) 767-1102

http://www.kepcopower.com   



 email: [email protected]

WARNING

Accessing the BOP after the output
is disabled in BATTERY mode is
hazardous because (1) high current
arcing is possible and (2) either the
external battery voltage, or the volt-
age (±Voltage Protection max) on
the BOP output terminals may be
dangerous. Therefore, for battery
and constant-voltage-type active
electronic loads it is recommended
that two properly rated external
switches be installed for safety:
one in series with the battery, and
one across the BOP output. After
the unit is set to OFF, first open the
switch in series with the battery,
then close the switch across the
BOP output to ensure safety before
handling BOP connections. When
connecting the battery, the switch
across the output should be
opened after the connections are
complete and then the switch in
series with the battery should be
closed. If the constant-voltage-type
active electronic load is adjusted to
zero before handling the power
supply-to-load connections, only
the switch across the BOP output
is required.

Battery

. This mode is necessary for the power sup-

ply to function properly and safely with either battery

or constant-voltage-type active electronic loads. This
mode prevents the battery from discharging during
the OFF state. When the output is disabled (set to
OFF), the BOP will go to current mode, current will
be set to zero, with voltage protect and current limit
set to maximum. In this way the battery will not be
discharged while the output is OFF. For constant-
voltage-type active electronic loads this mode stops
energy flow during the OFF state. Table 5 indicates
how the power supply responds to a command to go
from Output ON to OFF. 

CONFIGURE LOAD TYPE. 

To configure, press

%

 from the power-up screen, then highlight Load

Type and press 

!

 to modify. (If a Password is

required, see Operator’s Manual for instructions.)
Highlight Active, Resistive or Battery (see explana-
tions and associated WARNINGS above) and press

$

 to save. Then press 

$

 to save for power-up,

#

 to abort, or 

%

 to apply the changes (without

saving for power-up) and exit. After configuring, the
new setting will be effective when the power supply
goes from output on to output off.

To restore factory default (Active), press 

%

 from the

power-up screen, highlight Load Type, press 

!

,

then press 

@

 to restore default. Press 

$

 to save

for power-up or 

%

 to exit

ENABLING/DISABLING OUTPUT POWER. 

The BOP output can be disabled (OFF) or enabled
(ON) by toggling the 

STANDBY

 key in local mode.

The behavior of the unit when disabled depends on
the Load Type setting (See “Max/Min Setting Menu”
on page 13. 6 and Table 5 for details). 

IX — ADDITIONAL FEATURES.

 The user is urged to refer to the Operator’s Manual
for full explanations all BOP 1KW features, includ-
ing:

Passwords - three independent levels of
access

Changing the Default Power up Settings

Digital Remote Operation - using SCPI com-
mands via RS 232, GPIB or LAN ports; opera-
tion via web pages

Analog Remote Operation - via Analog I/O
port

Details about Protect Limits and Software-
controlled limits

Storing/Recalling Power Supply Output Set-
tings

Waveform Generation - Sine, Triangle,
±Ramp, Square and Level segments. Local
operation allows up to 16 waveforms, maxi-
mum 10 segments per waveform. Remote
operation allows 1 waveform, maximum of
126 segments, or using LIST commands.

Operator Testing

Calibration - via either local keypad or remote
SCPI commands

Parallel/Series Configurations -increase cur-
rent capability, voltage capability, or both.

Summary of Contents for BOP 10-100MG/ME

Page 1: ...units the GPIB interface is replaced with a LAN interface Unless otherwise noted this guide applies to both models ACCESSING MANUALS First determine your Firmware Version see below then download the B...

Page 2: ...or current and a 1 to 10V input for the limit channels BOP models are suitable for driving inductive loads such as large magnets or motors and for exercising batteries They are also suitable for chara...

Page 3: ...el 1 d c Output Range Closed Loop Gain Output Impedance Voltage 2 V d c Current A d c Voltage Channel GV V V Current Channel GI A V Voltage Mode Series R L Current Mode Parallel R C Rd c mOhms L H Rd...

Page 4: ...4 228 1692 REV 8 090418 KEPCO INC 131 38 SANFORD AVENUE FLUSHING NY 11355 U S A TEL 718 461 7000 FAX 718 767 1102 http www kepcopower com email hq kepcopower com FIGURE 1 BOP OUTPUT CHARACTERISTICS...

Page 5: ...n to IEEE 1118 BITBUS port 142 0485 Kepco KMDLA 5P Kycon Inc IEEE 488 Cable 1 meter long For MG models only Connects BOP power supply to GPIB bus SNC 488 1 IEEE 488 Cable 2 meter long For MG models on...

Page 6: ...operation voltage or current output volt age or current and establish positive and negative voltage and current limits An output analog corre sponding to output current is also provided Refer to Oper...

Page 7: ...LS AND INDICATORS RS 232 CONNECTIONS Connect the BOP 1KW to a modem using a Null Modem patch cable at the RS 232 port located on the rear panel See Fig ure 3 A Null Modem cable is not required for old...

Page 8: ...1355 U S A TEL 718 461 7000 FAX 718 767 1102 http www kepcopower com email hq kepcopower com FIGURE 3 BOP 1KW SERIES REAR PANEL VIEW LINKS INSTALLED FOR LOCAL SENSING FIGURE 4 LOAD CONNECTION A LOCAL...

Page 9: ...ng an item on the list and pressing the View Modify function key Menus and submenus will display a list of parameters with the top one high lighted The function key assignments can vary but generally...

Page 10: ...g and output Calibration Voltage Current and External and Controls calibration Shows Firmware versions for Display Serial GPIB LAN and analog Power up Settings Mode Voltage Cur rent External Main chan...

Page 11: ...channels one to set output voltage or current and one to set the corre sponding protection limit The main channel is deter mined by the MODE key in local mode which alternately selects either Voltage...

Page 12: ...ral Setup menu then highlight Max Min Set tings 2 Press to enter the Max Min Settings submenu Figure 6 If a Password is required see Opera tor s Manual for instructions 3 Highlight the voltage or curr...

Page 13: ...afety fea tures constant current type active electronic loads must be adjusted to zero and the BOP front panel LCD must read 0V minimum cur rent before handling the power supply to load connections Re...

Page 14: ...flow during the OFF state Table 5 indicates how the power supply responds to a command to go from Output ON to OFF CONFIGURE LOAD TYPE To configure press from the power up screen then highlight Load T...

Page 15: ...copower com email hq kepcopower com FIGURE 1 BOP 1KW OUTLINE DIMENSIONS SHEET 1 OF 2 20 000 508 00 21 439 544 54 22 800 579 11 21 564 547 73 22 000 558 79 23 863 606 12 18 235 463 16 18 985 482 21 1 4...

Page 16: ...FLUSHING NY 11355 U S A TEL 718 461 7000 FAX 718 767 1102 http www kepcopower com email hq kepcopower com FIGURE 1 BOP 1KW OUTLINE DIMENSIONS SHEET 2 OF 2 SLIDES TRAVEL DISTANCE 23 000 584 2 22 000 5...

Reviews: