7
DEFINITIONS
input
- INPUT; This section of the program menu assigns the type of input the unit will be using (0-20 mA, 4-
20 mA, 0-5 V, 0-10 V, 1-5 V, Linear or square root extraction).
i 4-20
- I 4-20; This sets the unit for a current input of 4 to 20 mA.
i 0-20
- I 0-20; This sets the unit for a current input of 0 to 20 mA.
E 1-5
- E 1-5; This sets the unit for a voltage input of 1 to 5 volts.
E 0-5
- E 0-5; This sets the unit for a voltage input of 0 to 5 volts.
E 0-10
- E 0-10; This sets the unit for a voltage input of 0 to 10 volts.
LiNEAR
- LINEAR; This sets the unit for linear input.
S9RT
- SQUARE ROOT; This sets the unit for square root extraction.
RELAYS
- RELAYS; This section of the program menu sets the control output variables (open col lec tor).
A RATE
- OUTPUT A FOR RATE; This assigns the A output to the rate.
HYS A
- HYSTERESIS FOR OUTPUT A; This value is the number of units below Preset A that the output will
remain "ON". EXAMPLE: Preset A set at 100, Hys set at 10. Output A will activate (turn on) when the
rate equals 100; Output A will deactivate (turn off) when the rate falls below 90 (10 below Preset A)
A tot
- OUTPUT A FOR TOTAL; This assigns the A output to the totalizer.
A PuL
- Relay A assigned to pulse output.
DuR A
- OUTPUT A DURATION; This is the duration of time (.01 to 599.99 sec) that Output A will remain ener-
gized. If 0.00 is entered the output will latch until reset. If a value other than 0.00 is entered the unit will
autorecycle at Preset A.
B RATE
- OUTPUT B FOR RATE; This assigns the B output to the rate.
HYS B
- HYSTERESIS FOR OUTPUT B; Same as HYS A.
b tot
- OUTPUT B FOR TOTAL; This assigns the B output to the totalizer.
B PuL
- Relay B assigned to pulse output.
DuR B
- OUTPUT B DURATION; This is the duration of time (.01 to 599.99 sec) that Output B will remain ener-
gized. If 0.00 is entered the output will latch until reset.