DESCRIPTION & SPECIFICATIONS

Description:

Featuring 6 digits of bright, 7-seg ment LED dis plays, 
this  unit  is  an  integrating  to tal izer/rateme ter  which 
ac cepts  ana log  sig nal  in puts.    The  unit  can  be  fi eld 
pro grammed to ac cept 0-20mA, 4-20mA, 0-5V, 0-10V 
or 1-5V sig nals.  A 4-20mA out put op tion is avail able 
to  control  strip  re cord ers  or  other  peripherals.    Two 
as sign able set points are stan dard for two stage shut 
off.  The full scale setting is pro gram mable from the 
front  pan el.    By  press ing  the  "view"  but ton,  the  unit 
will display: in te grated to tal, rate, peak or valley.  

Specifi cations:
Display: 

6  digit,  .55"  high,  7  seg ment,  red  orange, 

LED.

Input Power: 

110 VAC ± 15% or 12 to 24VDC.

Current: maximum 300 mA DC or 8.0 VA at rated AC 
volt age.

Output Power: 

(AC pow ered units only) + 24VDC @ 

100mA regu lated ±5%

Temperature:

Operating: +41°F (5°C) to +130°F (+54°C).
Storage: -40°F (-40°C) to +200°F (93°C).

Memory

: EEPROM stores data for ten years if power 

is lost.

Reset

Front Panel: resets dis played val ues and control out-
 puts. 
Remote: 4-30VDC positive edge, resets totalizer and 
con trol out puts.

Output

:

Type: Open collector sinks 250mA from 30VDC when 
ac tive.
Usage:  rate  alarm,  total  alarm,  scaled  pulse  output 
for remote totalizers.

Analog  Out: 

The  full  scale  setting  is  pro gram mable 

from the front panel. A sink ing driver gen er ates a cor-
 re spond ing lin ear cur rent through the external devices.  
The out put up dates with each update of the rate.  Ac-
curacy is ±0.25% FS worst case.  Compliance volt age 
must  be  3  to  30  VDC  non  in duc tive.    (The  unit  can 
provide the DC source as long as the drop across the 
devices being driven does not ex ceed 21V).

Input:

Type:  Linear  0-20mA,  4-20mA,  0-5V,  0-10V  or  1-5V 
se lectable from the front panel.  

Input Impedance:

 Current: 100Ω; Voltage: 115KΩ

Calibration: 

The unit does all of the calibrations in ter -

nal ly.  There are no potentiometers to adjust and the 
unit never needs to be removed from the case.

Set Points: 

Two control set points are provided.  The 

set point outputs can be as signed to rate or total or pulse 
scaling.  The unit comes stan dard with two open col-
 lec tor control out puts.  The out puts are pro gram mable 
from  0.01  to  599.99  sec  or  latched  until  reset  when 
as signed to the total or pulse and a hys ter esis (alarm 
range) when as signed to the rate.

Rate Display:

 Updates 5 times per sec ond, Accurate 

to 4.5 dig its.  

Totalizer:

 Integrates from the rate reading and ac cu -

mu lates up to 6 digits of total count.  The time base (sec-
onds, minutes, hours  or days) and totalize conversion 
factor are fi eld pro gram mable from the front panel. 

Programming

:  Decimal  points,  Scal ing  from  0  to 

59999 units per se lected time base, set points, in put 
type, security lock code, and as sign ing out puts are all 
pro gram mable from the front panel.

Housing:

 Standard 1/8 DIN, high im pact ABS plastic 

case (NEMA 4/IP65 front panel).

Shipping Weight:

 2 lbs.

Overvoltage Protection:

50 V

Overcurrent Protection: 

50 mA

Resolution: 

14.5 Bits

Accuracy: 

RANGE

% FS ERROR 

% FS ERROR 

 

(worst case) 

(typical)

4-20 mA 

0.1% 

.05%

0-10 VDC 

0.2% 

0.1%

0-5 VDC 

.25% 

.15%

1-5 VDC 

.25% 

.15%

Square Law: (above 5% of bottom range) 0.1%
(5V inputs .4%) Worst case over complete range: 2%

Temperature Stability: 

Will not drift more than 20 

parts per million per °C from 5°C to 54°C 

Summary of Contents for ES-756

Page 1: ...756 INSTALLATION OPERATING INSTRUCTIONS MODELS ES756 INT 69RT 99914 01 03 06 KESSLER ELLIS PRODUCTS 10 Industrial Way East Eatontown NJ 07724 800 631 2165 732 649 7100 Fax 732 649 7099 http www kep c...

Page 2: ...internal circuit boards or devices Handling Procedure 1 Power to unit must be removed 2 Personnel must be grounded via wrist strap or other safe suitable means before any printed circuit board or othe...

Page 3: ...TYPICAL WIRING HOOKUPS 4 OPEN COLLECTOR 5 PROGRAMMING FLOWCHART 6 DEFINITIONS 7 FRONT PANEL OPERATIONS 10 PROGRAMMING 10 SETTING PRESETS PANEL LOCK 15 TROUBLESHOOTING GUIDE 16 WARRANTY WARRANTY WARRAN...

Page 4: ...THIS PAGE IS BLANK...

Page 5: ...tive The unit can provide the DC source as long as the drop across the devices being driven does not exceed 21V Input Type Linear 0 20mA 4 20mA 0 5V 0 10V or 1 5V selectable from the front panel Input...

Page 6: ...e screws into the rear of the brackets Tighten the screws evenly and alternately A panel less than 0 1 may distort if the clamps are screwed too tightly Do not over tighten Anormal level of torque is...

Page 7: ...ied on the input and DC ground lines Make sure the input wires are not run into the unit in a bundlewithpowerinputlines Werecommend using shielded cable Connect the shield to DC signal ground of the u...

Page 8: ...urrent I in 5 Voltage V in 6 Not Used 7 24V Out 8 Preset B Collector 9 Preset A Collector 10 DC In 11 AC Neutral 12 AC Line 1 Reset In 2 Analog Out Sink 3 Signal GRD DC 4 Current I in 5 Voltage V in 6...

Page 9: ...90 10 below Preset Select PuL pulse output to use the output for remote totalizers When set to PuL a minimum duration in seconds 0 00 to 599 99 can be assigned to the time the output will remain energ...

Page 10: ...ter displayed value NOTE SEVERAL PROGRAMMING SELECTIONS WILL NOT APPEAR WITH RATE ONLY TOTAL ONLY UNITS OPTIONS NOT ORDERED WILL NOT APPEAR IN PROGRAM SELECTIONS For best results choose the highest re...

Page 11: ...ERESIS FOR OUTPUT A This value is the number of units below Preset A that the output will remain ON EXAMPLE Preset A set at 100 Hys set at 10 Output A will activate turn on when the rate equals 100 Ou...

Page 12: ...raging factor 00 0 to 99 9 Higher settings provide more nor malizing averaging for a more stable display Derived from the equation OLD DATA x NOR NEW DATA OLD DATA x NOR NEW DATA NOR 1 Sec SECONDS Thi...

Page 13: ...the left digit when viewing the Peak The peak value is the highest rate reading that the unit had displayed since the peak had been reset The peak is not retained in memory when power is lost uXXXXX U...

Page 14: ...20 i 0 20 E 1 5 E 0 5 or E 0 10 LiNEAR or S9RT PRESS FRONT PANEL OPERATIONS Press to RESET in operating mode Press to ENTER in pro gramming mode Press to view or change Preset A Press to view or chan...

Page 15: ...toggle between choices press the RST ENTERkeytoenterthedisplayed choice dur A the duration of time 0 01 to 599 99sec thatoutputAwillremainon or energized When durAis displayed hit any key to view or...

Page 16: ...G or LC ALL or LC ALL or CoDE Press any key to view or change the lock code PRESS This section of the menu is used to set up important operating variables RDEC rate decimal location Press the key unde...

Page 17: ...layed choice Entering a decimal will add resolution to the total i e tdec 100 will be displayed as 100 0 CFDEC Conversion Factor Decimal Press the arrow keys to enter in the desired conversion factor...

Page 18: ...tevaluerepresentedby the 20 mA end of the 4 20 mA output KeyinthedesiredvalueandpressRST ENTER to enter displayed value Press PRGM to recycle through list choices STEP 5 SETTING OPTIONS THE PROGRAM SE...

Page 19: ...the displayed value is not the desired preset press the key s under the digit to be changed Keyinthelockcode seeprogramming step 3 by pressing the keys under the digits to be changed Each time a key...

Page 20: ...ase is incorrect 2 Conversion factor is in correct 3 Total multiplier is incorrect 1 Recheck power wiring 1 Use a different power sup ply or install a surge sup pressor 1 Recheck input wiring 2 Rechec...

Page 21: ...any questions concerning our warranty repair modi cation or returned goods process please contact your local dis tributor WARRANTY This product is warranted against defects in materials and workmansh...

Page 22: ...CF Gallons Acre Feet 32 59 1 10 100 1000 0001 001 01 1 AFT Cubic Feet Acre Feet 2295 1 10 100 1000 0001 001 01 1 AFT Liters Liters 10 10 100 100 1000 LTR Cubic Meters 10 1 10 100 1000 1 1 10 100 CM C...