background image

3

WIRING

WIRING CONNECTIONS

AC / DC CONNECTIONS:
NOTE: Connect power only after other con-
 nec tions are fi n ished.  Do not touch the live AC 
power ter mi nals.  The unit has been de signed 
with an isolated AC input, therefore polarity is 
not a concern for the AC power.  The chassis 
is plastic, therefore earth ground is not used.  
For DC operation, cDC to terminal 10 
and -DC to terminal 3.

Although the unit is designed to be im mune 
from line or RF interference, the unit is con-
 trolled by a microprocessor and an elec tri cally 
"noisy"  environment  could  cause  op er at ing 
problems.  The input power lines should not 
be com mon to power lines for motors, pumps, 
contactors, etc.

Four sources of noise can occur:

1)  AC  power  line  noise-  If  the  unit  cannot 
be connected to an electrically clean power 
source, an inductive load suppressing device 
(MOV as GE#V130LA1 or Resistor Capacitor 
as Paktron# .2uf/220 ohm @ 400V) can be 
installed.   Although  locating  the  suppressor 
across the AC supply at the unit should help, 
best results  are obtained by connecting the 
suppressor across the leads of the "load" at 
the device causing the spikes.

2)  Input  line  noise-  The  noise  is  carried  on 
the  input  and  DC  ground  lines.    Make  sure 
the input wires are not run into the unit in a 
bundle with power input lines.  We recommend 
using shielded cable.  Connect the shield to 
DC signal ground of the unit and "earth" at one 
point in the circuit preferably at the DC ground 
ter mi nal of the unit.

3)  Output  lines- The  unit  has  two  open  col-
 lec tor outputs.  When these outputs are used 
to run external relays or solenoids, spikes can 
be generated upon activation.  This noise can 
spread through the instrument causing operat-
ing problems.  If the source is a D.C. operated 
device,  a  gen eral  purpose  diode  (IN4004) 
placed across the solenoid prevents electrical 
noise spikes.  Connect the cathode (banded 
side) to the more positive side of the coil.  If 
the source is an A.C. operated device, use a 
Resistor Ca pac i tor or MOV across the coil.

4) 24 VDC output supply- Noise can be gen-
 er ated on the 24 VDC output supply if it is used 
to drive inductive loads or if the current draw 
exceeds 50mA.  Insure that all inductive loads 
have a diode (such as IN4004) across the coil 
and that the current does not exceed 50mA.
  

REAR   VIEW

1 2 3 4 5 6 7 8 9 10

10 11 12

12

13

13 14

14 15

15 15

15 17

17 18

18

1• Reset In
2• Analog Out (Sink)
3• Signal GRD (-DC)
4• (Current) +I in
5• (Voltage) +V in
6• Not Used
7• +24V Out
8• Preset B Collector
9• Preset A Collector
10• +DC In
11• AC Neutral
12• AC Line

Summary of Contents for ES-756

Page 1: ...756 INSTALLATION OPERATING INSTRUCTIONS MODELS ES756 INT 69RT 99914 01 03 06 KESSLER ELLIS PRODUCTS 10 Industrial Way East Eatontown NJ 07724 800 631 2165 732 649 7100 Fax 732 649 7099 http www kep c...

Page 2: ...internal circuit boards or devices Handling Procedure 1 Power to unit must be removed 2 Personnel must be grounded via wrist strap or other safe suitable means before any printed circuit board or othe...

Page 3: ...TYPICAL WIRING HOOKUPS 4 OPEN COLLECTOR 5 PROGRAMMING FLOWCHART 6 DEFINITIONS 7 FRONT PANEL OPERATIONS 10 PROGRAMMING 10 SETTING PRESETS PANEL LOCK 15 TROUBLESHOOTING GUIDE 16 WARRANTY WARRANTY WARRAN...

Page 4: ...THIS PAGE IS BLANK...

Page 5: ...tive The unit can provide the DC source as long as the drop across the devices being driven does not exceed 21V Input Type Linear 0 20mA 4 20mA 0 5V 0 10V or 1 5V selectable from the front panel Input...

Page 6: ...e screws into the rear of the brackets Tighten the screws evenly and alternately A panel less than 0 1 may distort if the clamps are screwed too tightly Do not over tighten Anormal level of torque is...

Page 7: ...ied on the input and DC ground lines Make sure the input wires are not run into the unit in a bundlewithpowerinputlines Werecommend using shielded cable Connect the shield to DC signal ground of the u...

Page 8: ...urrent I in 5 Voltage V in 6 Not Used 7 24V Out 8 Preset B Collector 9 Preset A Collector 10 DC In 11 AC Neutral 12 AC Line 1 Reset In 2 Analog Out Sink 3 Signal GRD DC 4 Current I in 5 Voltage V in 6...

Page 9: ...90 10 below Preset Select PuL pulse output to use the output for remote totalizers When set to PuL a minimum duration in seconds 0 00 to 599 99 can be assigned to the time the output will remain energ...

Page 10: ...ter displayed value NOTE SEVERAL PROGRAMMING SELECTIONS WILL NOT APPEAR WITH RATE ONLY TOTAL ONLY UNITS OPTIONS NOT ORDERED WILL NOT APPEAR IN PROGRAM SELECTIONS For best results choose the highest re...

Page 11: ...ERESIS FOR OUTPUT A This value is the number of units below Preset A that the output will remain ON EXAMPLE Preset A set at 100 Hys set at 10 Output A will activate turn on when the rate equals 100 Ou...

Page 12: ...raging factor 00 0 to 99 9 Higher settings provide more nor malizing averaging for a more stable display Derived from the equation OLD DATA x NOR NEW DATA OLD DATA x NOR NEW DATA NOR 1 Sec SECONDS Thi...

Page 13: ...the left digit when viewing the Peak The peak value is the highest rate reading that the unit had displayed since the peak had been reset The peak is not retained in memory when power is lost uXXXXX U...

Page 14: ...20 i 0 20 E 1 5 E 0 5 or E 0 10 LiNEAR or S9RT PRESS FRONT PANEL OPERATIONS Press to RESET in operating mode Press to ENTER in pro gramming mode Press to view or change Preset A Press to view or chan...

Page 15: ...toggle between choices press the RST ENTERkeytoenterthedisplayed choice dur A the duration of time 0 01 to 599 99sec thatoutputAwillremainon or energized When durAis displayed hit any key to view or...

Page 16: ...G or LC ALL or LC ALL or CoDE Press any key to view or change the lock code PRESS This section of the menu is used to set up important operating variables RDEC rate decimal location Press the key unde...

Page 17: ...layed choice Entering a decimal will add resolution to the total i e tdec 100 will be displayed as 100 0 CFDEC Conversion Factor Decimal Press the arrow keys to enter in the desired conversion factor...

Page 18: ...tevaluerepresentedby the 20 mA end of the 4 20 mA output KeyinthedesiredvalueandpressRST ENTER to enter displayed value Press PRGM to recycle through list choices STEP 5 SETTING OPTIONS THE PROGRAM SE...

Page 19: ...the displayed value is not the desired preset press the key s under the digit to be changed Keyinthelockcode seeprogramming step 3 by pressing the keys under the digits to be changed Each time a key...

Page 20: ...ase is incorrect 2 Conversion factor is in correct 3 Total multiplier is incorrect 1 Recheck power wiring 1 Use a different power sup ply or install a surge sup pressor 1 Recheck input wiring 2 Rechec...

Page 21: ...any questions concerning our warranty repair modi cation or returned goods process please contact your local dis tributor WARRANTY This product is warranted against defects in materials and workmansh...

Page 22: ...CF Gallons Acre Feet 32 59 1 10 100 1000 0001 001 01 1 AFT Cubic Feet Acre Feet 2295 1 10 100 1000 0001 001 01 1 AFT Liters Liters 10 10 100 100 1000 LTR Cubic Meters 10 1 10 100 1000 1 1 10 100 CM C...

Reviews: