Installation Instructions
1.3.1 Cooling Systems
The KEB COMBIVERT F5 is available for different cooling systems:
•
Standard
Standard design with heat sink and fan (below described).
The dissipation of the power loss must be guaranteed by the machine
builder.
•
Flat rear
The heat sink is omitted at this design. The unit must be mounted onto
an appropriate base to ensure the heat dissipation.
•
Water-cooling
This design is laid out for the connection to an existing cooling system.
The dissipation of the power loss must be guaranteed by the machine
builder. To avoid moisture condensation the minimum inlet temperature
may not fall below the room temperature. The maximum inlet
temperature shall not exceed 40°C. Measurements against
contamination and calcifying must be taken externally. The maximum
pressure on the cooling system shall not exceed 4 bar (special version
with higher pressures on request).
•
Convection (through-mount version)
At this design the heat sink is moved through a section of the control
cabinet to the outside.
General
Standard
Special versions