KE2 Compressor 

Sequencer

Quick Start Guide

© Copyright 2018 KE2 Therm Solutions, Inc., Washington, Missouri 63090

Setpoints

Setpoint 

Description

Range / Options

Default

Fr

ont of Contr

oller

These can be ac

cessed fr

om fr

on

t of 

con

tr

oller

. A

ll other setpoin

ts ar

e ac

-

cessed on the c

on

tr

oller

’s w

eb page

.

SuCTION PRESSuRE

Suction Pressure setpoint to cycle the compressors

Min 0 psig

Most refrigerants: 150 psia;   R410A: 300 psig 

R744: 500 psig 

250 psig for 

R-744, 25 psig 

for all else

CuT OuT PRESSuRE

When below the cut out pressure, system turns off

Min 0 psig

Most refrigerants: 150 psia;    R410A: 300 psig 

R744: 500 psig 

5 psig

2ND SuCTION 

PRESSuRE

When enabled w. digital input (short across terminals), 

will control fans to run at this pressure, overriding nor-

mal operation until short removed from digital input

Min 0 psig

Most refrigerants: 150 psia;   R410A: 300 psig 

R744: 500 psig 

50 psig

TEmP uNITS

Temperature Units

Fahrenheit, Celsius

Fahrenheit

SuC PRESS DIFF

Suction Pressure Differential

0.1 to 5.0 psi

2.0 psi

REFRIgERANT

Type of refrigerant being used in the system.

R404A, R507, R407A,R407C, R422A, R422D, 

R134A, R22, R717, R438A, R408A, R409A, R407F, 

R410A, R744, R448A, R450A, R513A

404A

Rela

ys

RELAy#1

Relay controls the 1st stage

HG Defr Relay, LLS, Digital Comp*, Fixed Speed, 

Unloader for Cmp 2, Unloader for Cmp 3, 

Unloader for Cmp 4, Unloader for Cmp 5

Disabled

RELAy#2

Relay controls the 2nd stage

HG Defr Relay, LLS, Digital Comp*, Fixed Speed, 

Unloader for Cmp 1, Unloader for Cmp 3, 

Unloader for Cmp 4, Unloader for Cmp 5

Disabled

RELAy#3

Relay controls the 3rd stage

HG Defr Relay, LLS, Digital Comp*, Fixed Speed, 

Unloader for Cmp 1, Unloader for Cmp 2, 

Unloader for Cmp 4, Unloader for Cmp 5

Disabled

RELAy#4

Relay controls the 4th stage

HG Defr Relay, LLS, Digital Comp*, Fixed Speed, 

Unloader for Cmp 1, Unloader for Cmp 2, 

Unloader for Cmp 3, Unloader for Cmp 5

Disabled

RELAy#5

Relay controls the 5th stage

HG Defr Relay, LLS, Digital Comp*, Fixed Speed, 

Unloader for Cmp 1, Unloader for Cmp 2, 

Unloader for Cmp 3, Unloader for Cmp 4

Disabled

* Only one digital  compressor Digital Comp ON/OFF requires a solid state relay

COmP HP PER RELAy

labels the HP of each compressor

0.1 to 50 HP

None

Defr

os

Load

mAx LOAD

Maximum circuit concurrent load

6,000,000 Btu

15,000 Amps

0

uNITS

Units for heater load input

Btu/Amps

Amps

Refriger

ation

SuCTION PRESSuRE

(Also available from the front of 

the controller.)

Target Suction Pressure - Setpoint to cycle the com-

pressors

Min 0 psig

Most refrigerants: 150 psia;   R410A: 300 psig 

R744: 500 psig 

250 psig for 

R-744, 25 psig 

for all else

REFRIgERANT

(Also available from the front of 

the controller.)

Type of refrigerant being used in the system.

R404A, R507, R407A,R407C, R422A, R422D, 

R134A, R22, R717, R438A, R408A, R409A, 

R407F, R410A, R744, R448A, R450A, R513A

404A

mIN COmP RuN TImE

Min. run time to keep any compressor relay energized 0  to 240 seconds

60 seconds

mIN COmP OFF TImE

Minimum off time to keep any compressor relay de-

energized

0  to 240 seconds

60 seconds

mIN COmP SWITCH TImE Min. time between switching compressor on or off

0  to 240 seconds

15 seconds

2ND SuCTION 

PRESSuRE

(Also available 

from the front of the controller.)

When enabled w. digital input (short across terminals), 

controls fans to run at this pressure, overriding normal 

operation until short removed from digital input

Min 0 psig

Most refrigerants: 150 psia ;   R410A: 300 psig 

R744: 500 psig 

50 psig

CuT OuT PRESSuRE

(Also available from the front of 

the controller.)

When below the cut out pressure, system turns off

Min 0 psig

Most refrigerants: 150 psia;   R410A: 300 psig 

R744: 500 psig 

5 psig

mAx PumP OuT TImE

Sets time limit to reach cut out pressure

0 to 240 minutes

2 minutes

Aux TEmP TyPE

Options for using the auxiliary temperature sensor

Off (Disabled) /monitor/2nd liquid 

temperature for circuit #2

Disabled

TEmP uNITS

Temperature Units (can also be accessed from front of 

the controller)

Fahrenheit, Celsius

Fahrenheit

mIN SAFETy SuC SH

Safety for Minimum Suction Superheat

0 to 50ºF / 0 to 27.8K

0ºF /  0K

mAx SAFETy SuC TmP

Safety for Maximum Suction Temperature

5 to 90ºF / -15 to 32ºC

90º F / 

 

32ºC

mAx SAFETy PRESSuRE Safety for Maximum Pressure - when 

exceeded sends Alerts

0 to 500 psig

400 psig

Summary of Contents for 21710

Page 1: ...KE2 Compressor Se quencer can limit the amount of defrost load as dictated by the site s electrical requirements Part Numbers Controllers Accessories Part Number Description KE2 Compressor Sequencer 2...

Page 2: ...SH 0 150 psia pressure transducer for suction header T1 Suction 50 to 150 F Tempera ture sensor for suction header T2 Air Optional 50 to 150 F tempera ture sensor for space temperature Allows floating...

Page 3: ...ntroller wired and ready Superheat 0 0 F Suct Pressure 96 2 F Suct Temp 87 7 F Computer Tablet or Smart Phone Option A Option B Option C NOTE Computer requires Static IP See bulletin Q 5 11 This will...

Page 4: ...Superheat Superheat as calculated by the controller T1 Suction Temp Suction temperature as measured by the controller Saturation temp Saturation temperature as calculated by the controller Only one of...

Page 5: ...nloader for Cmp 3 Unloader for Cmp 4 Disabled Only one digital compressor Digital Comp ON OFF requires a solid state relay Comp HP per relay labels the HP of each compressor 0 1 to 50 HP None Defrost...

Page 6: ...Max Disch Pres Turns system of when exceeded 100 to 500 psig 450 psig Min Suction SH The lowest acceptable superheat Turns system off when exceeded 5 to 50 F 2 8 to 27 8K 15 F 8 3K Max Suction SH The...

Page 7: ...aximumDischarge Pressure Delay All stages will be turned off The controller will send a notification to the email address or phone number provided in the Address for Alerts field on the Settings page...

Page 8: ...luminated The controller will scroll High Superheat across the front panel High Discharge Pressure If the discharge pressure is above the Max Disch Pres Maximum Discharge Pressure for longer than the...

Page 9: ...e superheat reading is main taining above the Min Safety Suction Superheat the alarm will be cleared The controller will send a notification to the email address or phone number provided in the Addres...

Page 10: ...r to a system consisting of fixed speed compressors with or without unloading capabilities and one digital scroll the controller requires the user to assign a relay output for each compressor stage av...

Page 11: ...be sent If multiple digital inputs are selected for compressor module any compressor module input will control in manner described above Compressor Module If the Digital Input receives an Inactive si...

Page 12: ...ENTER for 3 seconds to save change To change settings To save setting changes To move through controller menus To return to Main Menu Indicator lights Red light critical alarm system is not running Am...

Page 13: ...splays number of users currently viewing this specific controller s webpage System alarms and messages are displayed DESCRIPTION Displays real time system information and shows the interaction of mult...

Page 14: ...tions Customer information is displayed Use to customize the User Name and Password from the default setting The KE2 Smart Access Settings are provided by KE2 Therm and are only needed when using KE2...

Page 15: ...d must be provided The default User Name ke2admin The default Password ke2admin For security reasons the User Name and Password should be changed from the default Once you are logged in go to the Sett...

Page 16: ...ld also be changed Network settings may be changed to match customer s environment IP address is Enabled or Disabled Enabled if selected IP is Dynamic Disabled if selected IP is Static Prevents unauth...

Page 17: ...Comp 5 Relay 2 5 Dropdown Options All Relay Options the same as Relay 1 except the list of Unloaders for the compressor never includes the active compressor R 404A R 507 R 407A R 407C R 422A R 422D R...

Page 18: ...p to 49 members All mem bers must be in the same network i e a router divides a network The SiteView may be organized by logging into the controller Air Electric Hot Gas DESCRIPTION SiteView provides...

Page 19: ...le Date and Time are pulled from the connected computer 5 460 Day Capacity Load and Suction Pressure are displayed when moving the mouse over the data Days ago DESCRIPTION The Graphing Snapshot shows...

Page 20: ...ile the KE2 Compressor Sequencer s free connectiv ity is still available KE2 Therm recognizes that some customers prefer the simplicity and convenience of KE2 Smart Access to enjoy the benefits of the...

Reviews: