KE2 Compressor 

Sequencer

Quick Start Guide

Safety Features :  

Alarm Name

Description 

Low Suction 

Pressure Cut-Out

System is ON

•  If System is On and the pressure goes below Cut Out Pressure setpoint, all compressor relays will be de-energized. The 

controller will maintain current off state until pressure rises Suct Press Diff above the Suction Pressure setpoint as long as the 

min Comp Offtime has been satisfied 

System is OFF

• The system may be turned off at any time by using one of three methods: Digital Input, Manual Menu, or Setpoints webpage. 

After receiving the System Off command the controller will turn off all but the largest capacity compressor. It will continue 

to run until the pressure goes below Cut Out Pressure or max Pump Out Time has been reached. If a Digital Scroll has been 

selected it will always be the last compressor on. The controller will maintain current System Off state until signal has been 

removed and pressure rises Suct Press Diff above the Suction Pressure setpoint as long as the min Comp Offtime has been 

satisfied

minimum 

Safety Suction 

Superheat

 Stand Alone Operation

• The controller will send a notification to the email address or phone number provided in the Address for Alerts field on the 

Settings page of the controller.

• The Amber LED on the front Panel will be illuminated

• The controller will scroll Min Safety Suc SH across the front panel

utilizing KE2 Evaporator Efficiency controllers

• The compressor sequencer will utilize the superheat of the KE2 Evap controllers with EEVs to assist in raising the superheat at 

the rack using the following sequence:

-  Every 5 minutes the Superheat Setpoint of each KE2 Evap controller will be increased 1 degree 

-  If the superheat is able to be maintained 2 degrees above the Min Safety Suc SH the compressor sequencer will lower the 

superheat 1 degree every 5 minutes until the setpoint has returned to its original value.

- Once all of the KE2 Evap controllers have been returned to their original setpoint values and the superheat reading is main-

taining above the Min Safety Suction Superheat the alarm will be cleared.

• The controller will send a notification to the email address or phone number provided in the Address for Alerts field on the 

Settings page of the controller.

• The Amber LED on the front Panel will be illuminated

• The controller will scroll Min Safety Suc SH across the front panel

maximum Safety 

Suction Temp

Stand Alone Operation

• The controller will send a notification to the email address or phone number provided in the Address for Alerts field on the 

Settings page of the controller.

• The Amber LED on the front Panel will be illuminated

• The controller will scroll Max Safety Suc Tmp across the front panel
utilizing KE2 Evaporator Efficiency controllers

• The compressor sequencer will utilize the superheat of the KE2 Evap controllers with EEVs to assist in lowering the suction 

temperature at the rack using the following sequence:

 - Every 5 minutes the Superheat setpoint of each KE2 Evap controller will be lowered 1 degree

 - If the temperature decreases the compressor sequencer will increase the superheat 1 degree every 5 minutes until the 

setpoint has returned to within 2 degrees of its original value.

- Once all of the controllers have been returned to their original setpoint value and the suction temperature reading is main-

taining itself below the Max Safety Suction Temp the alarm will be cleared.

• The controller will send a notification to the email address or phone number provided in the Address for Alerts field on the 

Settings page of the controller.

• The Amber LED on the front Panel will be illuminated

• The controller will scroll Min Safety Suc SH across the front panel

maximum Safety 

Pressure

If the discharge pressure is above the Max Safety Pressure for the time provided in the Max Dis Temp Delay:

•  The controller will unload the next stage to attempt to reduce the pressure

- Wait the time defined by Min Comp Switch Time, then unload next stage

-  Continue to unload until all stages are off

• The controller will send a notification to the email address or phone number provided in the Address for Alerts field on the 

Settings page of the controller.

• The Amber LED on the front Panel will be illuminated

• The controller will scroll Max Safety Pres across the front panel

Summary of Contents for 21710

Page 1: ...KE2 Compressor Se quencer can limit the amount of defrost load as dictated by the site s electrical requirements Part Numbers Controllers Accessories Part Number Description KE2 Compressor Sequencer 2...

Page 2: ...SH 0 150 psia pressure transducer for suction header T1 Suction 50 to 150 F Tempera ture sensor for suction header T2 Air Optional 50 to 150 F tempera ture sensor for space temperature Allows floating...

Page 3: ...ntroller wired and ready Superheat 0 0 F Suct Pressure 96 2 F Suct Temp 87 7 F Computer Tablet or Smart Phone Option A Option B Option C NOTE Computer requires Static IP See bulletin Q 5 11 This will...

Page 4: ...Superheat Superheat as calculated by the controller T1 Suction Temp Suction temperature as measured by the controller Saturation temp Saturation temperature as calculated by the controller Only one of...

Page 5: ...nloader for Cmp 3 Unloader for Cmp 4 Disabled Only one digital compressor Digital Comp ON OFF requires a solid state relay Comp HP per relay labels the HP of each compressor 0 1 to 50 HP None Defrost...

Page 6: ...Max Disch Pres Turns system of when exceeded 100 to 500 psig 450 psig Min Suction SH The lowest acceptable superheat Turns system off when exceeded 5 to 50 F 2 8 to 27 8K 15 F 8 3K Max Suction SH The...

Page 7: ...aximumDischarge Pressure Delay All stages will be turned off The controller will send a notification to the email address or phone number provided in the Address for Alerts field on the Settings page...

Page 8: ...luminated The controller will scroll High Superheat across the front panel High Discharge Pressure If the discharge pressure is above the Max Disch Pres Maximum Discharge Pressure for longer than the...

Page 9: ...e superheat reading is main taining above the Min Safety Suction Superheat the alarm will be cleared The controller will send a notification to the email address or phone number provided in the Addres...

Page 10: ...r to a system consisting of fixed speed compressors with or without unloading capabilities and one digital scroll the controller requires the user to assign a relay output for each compressor stage av...

Page 11: ...be sent If multiple digital inputs are selected for compressor module any compressor module input will control in manner described above Compressor Module If the Digital Input receives an Inactive si...

Page 12: ...ENTER for 3 seconds to save change To change settings To save setting changes To move through controller menus To return to Main Menu Indicator lights Red light critical alarm system is not running Am...

Page 13: ...splays number of users currently viewing this specific controller s webpage System alarms and messages are displayed DESCRIPTION Displays real time system information and shows the interaction of mult...

Page 14: ...tions Customer information is displayed Use to customize the User Name and Password from the default setting The KE2 Smart Access Settings are provided by KE2 Therm and are only needed when using KE2...

Page 15: ...d must be provided The default User Name ke2admin The default Password ke2admin For security reasons the User Name and Password should be changed from the default Once you are logged in go to the Sett...

Page 16: ...ld also be changed Network settings may be changed to match customer s environment IP address is Enabled or Disabled Enabled if selected IP is Dynamic Disabled if selected IP is Static Prevents unauth...

Page 17: ...Comp 5 Relay 2 5 Dropdown Options All Relay Options the same as Relay 1 except the list of Unloaders for the compressor never includes the active compressor R 404A R 507 R 407A R 407C R 422A R 422D R...

Page 18: ...p to 49 members All mem bers must be in the same network i e a router divides a network The SiteView may be organized by logging into the controller Air Electric Hot Gas DESCRIPTION SiteView provides...

Page 19: ...le Date and Time are pulled from the connected computer 5 460 Day Capacity Load and Suction Pressure are displayed when moving the mouse over the data Days ago DESCRIPTION The Graphing Snapshot shows...

Page 20: ...ile the KE2 Compressor Sequencer s free connectiv ity is still available KE2 Therm recognizes that some customers prefer the simplicity and convenience of KE2 Smart Access to enjoy the benefits of the...

Reviews: