background image

KE2 Compressor 

Sequencer

Quick Start Guide

Q.2.43 April 2018

Page 6

© Copyright 2018 KE2 Therm Solutions, Inc., Washington, Missouri 63090

Setpoint 

Description

Range / Options

Default

Digit

al 

In

puts

DIg IN 1, 2, 3 mODE

Sets the function of the Digital Input

HG Defr Req, 2nd Pres, Comp Mod, Oil Safety 

Sw, Hi Pres Switch, Sys Off

Disabled

DIg IN 1, 2, 3 STATE

Sets whether the switch activates with Open or Closed Open  / Closed

Closed

Sensor Of

fsets

Aux TEmP OFFSET

An offset added or subtracted from the auxiliary tem-

perature sensor reading, if needed

-5 to 5 Fº / -2.8 to 2.8K

0 Fº/K

SuCT PRESSuRE OFFSET An offset added or subtracted from the suction line 

pressure transducer reading, if needed

-5 to 5 Fº / -2.8 to 2.8K 

0 Fº/K

SuCT TEmP OFFSET

An offset added or subtracted from the suction tem-

perature sensor reading, if needed

-5 to 5 Fº / -2.8 to 2.8K

0 Fº/K

DISCH TEmP OFFSET

The offset added or subtracted from the discharge 

temperature sensor reading, if needed

-5 to 5 Fº / -2.8 to 2.8K 

0 ºF/K 

DISCH PRESS OFFSET

An offset added or subtracted from the discharge 

pressure transducer reading, if needed

-5 to 5 Fº / -2.8 to 2.8K 

0 ºF/K 

Alarms

mAx DISCH PRES

Turns system of when exceeded

100 to 500 psig

450 psig

mIN SuCTION SH

The lowest acceptable superheat. Turns system off 

when exceeded

5 to 50 ºF   /  2.8 to 27.8K

15 ºF 

 8.3K

mAx SuCTION SH

The highest acceptable superheat

25 to 200 ºF   / 13.9 to 111.1K

50 ºF 

 

27.8K

mIN/mAx SH DELAy

The amount of time, in minutes, before an alarm is 

initiated when the minimum or maximum superheat 

setting is surpassed.

0 to 254 minutes

Disabled

mAx DISCH TEmP

The maximum discharge temperature before an alarm 

is initiated. Turns off system when exceeded.

25 to 300ºF  /-3.9 to 148.9 ºC

268 

ºF

/

131.1ºC

 

mAx DISCH TEmP 

DELAy

The amount of time, in minutes, before an alarm is 

initiated when the Maximum Discharge Temperature 

setting is surpassed.

0 to 254 minutes

Disabled

mAx DIS PRS DELAy

The amount of time, in minutes, before an alarm is 

initiated when the Maximum Discharge Pressure set-

ting is surpassed.

0 to 254 minutes

Disabled

Setpoints - 

Continued

Manual  Menu

Name

Description

Range 

Default

mANuAL CONTROL
CLEAR ALARmS

Clear all active alarms

FACTORy RESET

Reset the controller to the factory default setpoints

Reset

WEB PASSWORD RESET

Reset the web password to the factory default

Reset

KE2 SmART ACCESS mODE

Turn KE2 Smart Access on or off

Disable, Enable

Disable

DHCP mODE

Turn DHCP mode on or off

Disable, Enable

Disable

Summary of Contents for 21710

Page 1: ...KE2 Compressor Se quencer can limit the amount of defrost load as dictated by the site s electrical requirements Part Numbers Controllers Accessories Part Number Description KE2 Compressor Sequencer 2...

Page 2: ...SH 0 150 psia pressure transducer for suction header T1 Suction 50 to 150 F Tempera ture sensor for suction header T2 Air Optional 50 to 150 F tempera ture sensor for space temperature Allows floating...

Page 3: ...ntroller wired and ready Superheat 0 0 F Suct Pressure 96 2 F Suct Temp 87 7 F Computer Tablet or Smart Phone Option A Option B Option C NOTE Computer requires Static IP See bulletin Q 5 11 This will...

Page 4: ...Superheat Superheat as calculated by the controller T1 Suction Temp Suction temperature as measured by the controller Saturation temp Saturation temperature as calculated by the controller Only one of...

Page 5: ...nloader for Cmp 3 Unloader for Cmp 4 Disabled Only one digital compressor Digital Comp ON OFF requires a solid state relay Comp HP per relay labels the HP of each compressor 0 1 to 50 HP None Defrost...

Page 6: ...Max Disch Pres Turns system of when exceeded 100 to 500 psig 450 psig Min Suction SH The lowest acceptable superheat Turns system off when exceeded 5 to 50 F 2 8 to 27 8K 15 F 8 3K Max Suction SH The...

Page 7: ...aximumDischarge Pressure Delay All stages will be turned off The controller will send a notification to the email address or phone number provided in the Address for Alerts field on the Settings page...

Page 8: ...luminated The controller will scroll High Superheat across the front panel High Discharge Pressure If the discharge pressure is above the Max Disch Pres Maximum Discharge Pressure for longer than the...

Page 9: ...e superheat reading is main taining above the Min Safety Suction Superheat the alarm will be cleared The controller will send a notification to the email address or phone number provided in the Addres...

Page 10: ...r to a system consisting of fixed speed compressors with or without unloading capabilities and one digital scroll the controller requires the user to assign a relay output for each compressor stage av...

Page 11: ...be sent If multiple digital inputs are selected for compressor module any compressor module input will control in manner described above Compressor Module If the Digital Input receives an Inactive si...

Page 12: ...ENTER for 3 seconds to save change To change settings To save setting changes To move through controller menus To return to Main Menu Indicator lights Red light critical alarm system is not running Am...

Page 13: ...splays number of users currently viewing this specific controller s webpage System alarms and messages are displayed DESCRIPTION Displays real time system information and shows the interaction of mult...

Page 14: ...tions Customer information is displayed Use to customize the User Name and Password from the default setting The KE2 Smart Access Settings are provided by KE2 Therm and are only needed when using KE2...

Page 15: ...d must be provided The default User Name ke2admin The default Password ke2admin For security reasons the User Name and Password should be changed from the default Once you are logged in go to the Sett...

Page 16: ...ld also be changed Network settings may be changed to match customer s environment IP address is Enabled or Disabled Enabled if selected IP is Dynamic Disabled if selected IP is Static Prevents unauth...

Page 17: ...Comp 5 Relay 2 5 Dropdown Options All Relay Options the same as Relay 1 except the list of Unloaders for the compressor never includes the active compressor R 404A R 507 R 407A R 407C R 422A R 422D R...

Page 18: ...p to 49 members All mem bers must be in the same network i e a router divides a network The SiteView may be organized by logging into the controller Air Electric Hot Gas DESCRIPTION SiteView provides...

Page 19: ...le Date and Time are pulled from the connected computer 5 460 Day Capacity Load and Suction Pressure are displayed when moving the mouse over the data Days ago DESCRIPTION The Graphing Snapshot shows...

Page 20: ...ile the KE2 Compressor Sequencer s free connectiv ity is still available KE2 Therm recognizes that some customers prefer the simplicity and convenience of KE2 Smart Access to enjoy the benefits of the...

Reviews: