Technical data
10.2.8 Environmental conditions / electrical safety
Ambient
conditions
Standards
DIN EN 60721-3-3/A2: 1997-07; 3K5+3Z11;
(IEC721-3-3; 3K5+3Z11)
Operating
temperature
-5°C … +55°C
Humidity
5% … 95%
Storage
temperature
-25°C … +70°C
Electrical
safety
Standards and
amendments
DIN EN 61010-1: Aug. 2002 (IEC1010-1/A2)
Protection
class
I, in accordance with DIN EN 61010-/August
2002
Overvoltage
category
CAT III: Relay CAT II
Protection
type
IP20 in accordance with DIN EN 40050 part 9:
1993-05
Electromag-
netic compat-
ibility
DIN EN 61000-6-2: 2000-03; (IEC 61000-6-2)
DIN EN 61000-6-3: 2000-03; (IEC 61000-6-3);
2005 - 06
50.0
5.00
61.00
45.00
90.00
106.00
multimax 3D6-ESBSDS-5DI6RO1DO
All dimensions in mm. Not suitable for taking measurements.