V3.00
KBR multimax 3D6
EDEBD
A0210-3313-1_EN
51
Technical data
10.2.3 Power supply
Power supply
85 to 265V AC/DC; 50/60Hz
Power consumption
15 VA
10.2.4 Hardware inputs
Digital
inputs
As pulse counter
input 1 to 5
Digital input for floating contact
S
0
compatible
pulse length ≥ 30ms
As status input
Digital input for floating contact
S
0
compatible, e.g. for
synchronization of measuring period;
pulse length ≥ 250ms
10.2.5 Electrical connection
Connection elements
Screw terminals
Max. permissible cross-section of
connecting cables
2.5 mm
2
Input power
supply
Fuse protection
F1: Recommendation 1A slow-blowing
< fuse < 4 A slow-blowing
KBR eBus
connection
Connection
material
For proper operation please only use
shielded twisted-pair cables; e.g. I-Y(St)
Y 2x2x0.8
Pulse inputs
Connection and
cables
ensure proper polarity!
Synchro-
nous input
Connection and
cables
ensure proper polarity!
KBR eBus
connection
via RS485
Terminal 90 ( )
Terminal 91 (A)
Terminal 92 (B)