KBR multimax 3D6
V3.00
EDEBD
A0210-3313-1_EN
40
System operation
e.g. in case of definition as pulse counter
Para. (...)
Input
Programming Explanation
Log
address
E..
Fixed logical address
inverse
on / off
Defines whether the input reacts to positive
or negative pulses.
t Pact -> 0
Numerical
value in
sec
Defines the time it takes until the power
drops to 0.
P. value
Numerical
value in
I/kW, MW, m
3
Pulse value according to the energy supplier.
I/U prim/
sec
Numerical
value in
A/V
Transformer ratio
current or voltage
e.g. in case of definition as relay output
Para. (...)
Outputs
Programming Explanation
Log
address
A..
Configurable line can be allocated to a termi-
nal. The terminal is defined in the hardware.
inverse
on / off
Defines if a relay reacts to positive or nega-
tive pulses.
Relay
group
Numerical
value in
sec
Assigns the relay to a relay group (switches
independently of the multimax)
8.4
Clock time / date
In the
Clock time / date
area, you can set the time and date as well as make
settings for daylight saving time.
1.
Select
Main menu > Clock time / date > Enter
.
2.
Start the configuration with
Edit
.
Clock / date Programming
Explanation
Time
Numerical value
in HH:MM:SS
Defines the time if it has not been already
set by an external system (eBus).
Date
Numeri-
cal values in
DD:MM:YYYY
Defines the date if it has not been already
set by an external system (eBus).
Daylight
saving time
AUTO / OFF
AUTO activates the automatic daylight
saving time according to the entries for
Start and End.