background image

Rev. 1.00

22585_EDEBD

A0252-0318-1_EN

10

KBR multicomp F144-3 6DO/12DO

Control and display panel

2  

Control and display panel

multicomp F144-MS-1V1C1TI6DO-3

multicomp F144-MS-1V1C1TI12DO-3

Operating elements:

1   LCD displaying the current status and user prompts 
2   Number of possible controller output lines 
3   Two sensor buttons for parameter configuration 
4   Two sensor buttons for menu selection

1

2

3

4

1

2

3

4

Summary of Contents for F144-MS-1V1C1TI6DO-3

Page 1: ...22585_EDEBDA0252 0318 1_EN Technical reference Your partner for network analysis 4 quadrant controller F144 MS 1V1C1TI6DO 3 F144 MS 1V1C1TI12DO 3 multicomp System I English...

Page 2: ...KBR Kompensationsanlagenbau GmbH Misprints printing errors and technical changes reserved 2 KBR multicomp F144 3 6DO 12DO...

Page 3: ...power is programmed 26 8 3 Start menu window 29 8 4 Stage state window 31 8 5 Service window 32 8 6 Commissioning window 33 8 7 Switching performance window 37 8 8 Error message window 39 8 9 Extras...

Page 4: ...properly install and start up the device to prevent damage This user manual is included in the scope of delivery of the device and must be accessible to the user at all times e g in the switchgear ca...

Page 5: ...en CAUTION means that minor injuries or property damage may occur if the appropriate safety precautions are not taken NOTE is an important piece of information on the product product handling or the r...

Page 6: ...tion may result in the destruction of the device When connecting the device ensure that the data given in the connection chart is complied with see Connection diagram and that the connection cables ar...

Page 7: ...ice is subjected to long term testing before it is delivered For details on product liability please refer to our general terms and conditions for electronic equipment The assured device properties on...

Page 8: ...aving fewer switching operations results in optimum adjustment Even for large systems sensitive controls can be set up with just a few modules Stage ratios do not need to be considered After compensat...

Page 9: ...f the controller used to record the necessary network parameters takes approx 20 ms NOTE Limit for overvoltage switch off measuring voltage 10 taking the mea suring voltage ratio into account This val...

Page 10: ...and display panel multicomp F144 MS 1V1C1TI6DO 3 multicomp F144 MS 1V1C1TI12DO 3 Operating elements 1 LCD displaying the current status and user prompts 2 Number of possible controller output lines 3...

Page 11: ...target cos phi 1 00 cannot be changed Alarm cos phi 0 92 inductive Main transformer current Primary current 1000 A Secondary current 5 A Measuring voltage Primary voltage 400 V Ph Ph corresponds to 2...

Page 12: ...ature measurement On Output 6 12 as stage or fan Fan output Fan switch on temperature 28 C Fan switch off temperature 23 C System switch off temperature 48 C System switch on temperature 43 C Learning...

Page 13: ...tricity supplier regulations for kVA tariff cos phi 1 Primary current and secondary current in accordance with input current transformer Voltage transformer ratio if required NOTE Upon delivery the bu...

Page 14: ...rimary voltage 1 V to 999999 V Ph Ph Secondary voltage 1 V to 999 V Ph Ph Discharge time 20 to 9999 ms Max stage power per switching cycle 0 to 9999 kvar Rot field U L1N L2N L3N L12 L23 L31 Rot field...

Page 15: ...Scanning frequency Automatic fixed 50 Hz fixed 60 Hz Stage power monitored Yes No Reset Run Contrast setting 0 to 10 Brightness setting 0 to 9 Dimmer brightness 0 to 9 Light load limit 15 mA 50 mA Lig...

Page 16: ...e connecting the power supply to the device please note The voltage and frequency must comply with the specifications on the name plate Observe the limits specified in this manual The electrical insta...

Page 17: ...5 A and 1 A transformers switching is done by firmware If you use existing transformers the current paths must always be connected in series The secondary transformer current needs to be at least 15...

Page 18: ...ionsstufe W erkseinstellung L fteranschluss je nach Ausf hrung 6 stufiger oder 12 stufiger Regler Die Stufenausg nge sind Optokopplerausg nge Um einen L fter direkt anzusteuern muss bei Bedarf bauseit...

Page 19: ...schluss oder Kompensationsstufe Werkseinstellung L fteranschluss je nachAusf hrung 6 stufiger oder 12 stufiger Regler Die Stufenausg nge sind Optokopplerausg nge Um einen L fter direkt anzusteuern mus...

Page 20: ...t open please check that Menu on is set for Learning mode in the Extras menu The settings are saved on an EEPROM so that they are not lost in the event of a power failure Switch on a sufficient number...

Page 21: ...1_EN 21 KBR multicomp F144 3 6DO 12DO The first switching operation may take up to 10 seconds The stages are switched in set intervals until compensation occurs The displayed cos phi must increase to...

Page 22: ...e KF U Commissioning Rot field U Commissioning Main current primary Commissioning Max Stage power per switching cycle Commissioning Enter password Password status Commissioning Main current secondary...

Page 23: ...Attenuation Q miss Error message menu Missing current Error message menu Switching cycle limit exceeded Error message menu Light load operation Error message menu next next next Temperature switch of...

Page 24: ...urrent displays and controller configuration Initialization menu no input possible multicomp F144 3 6 stage or 12 stage multicomp 06 Th Initialization multicomp 12 Th Initialization cos 0 71 IND AAAAA...

Page 25: ...xt Switch perform next Message menu next Service next Extras next Switching performance window influencing switching performance Commissioning window operating parameter entry Error message menu editi...

Page 26: ...initialization as they are adjust ed automatically to ensure correct operation 8 2 Commissioning window if no stage power is programmed During initial startup of the multicomp F144 3 the Commissionin...

Page 27: ...ndary current of the transformer need to be set submenu Iprim Isec These parameters can be found on the nameplate of the current transformer In addition the phase allocation of the transformer needs t...

Page 28: ...e skip the menu item Learning mode activate and enter the power value individually for each stage If you want to activate learning mode ensure that all previous submenu param eters have been configure...

Page 29: ...stage has been switched off manually X the stage s measured stage power does not correspond to the con figured value stage monitoring activated see the Stage monitoring submenu of the Extras menu Pre...

Page 30: ...load is symmetrical Compensation power to achieve the set target cos phi missing The missing compensation power is displayed up to a maximum value of 9999 9 kvar If the value exceeds this limit 9999...

Page 31: ...if they are switched on or off permanently The individual capacitor stages can be selected by pressing W You can change the stage state from Auto Automatic to ff switched off permanently or n switched...

Page 32: ...and simultaneously In addition the value in the menu item Missing comp power maximum can be deleted by pressing and simultaneously resetting the PFC too small message If the set target cos phi is not...

Page 33: ...seconds If no buttons are pressed during this time the controller is then locked again The password can be set or changed by pressing to start entering or to change the entry position to change or set...

Page 34: ...suring voltage under Rot field U These settings apply to a standard network voltage Ph Ph 400 V primary 400 V secondary If you use a voltage transformer configure the pa rameters indicated on the volt...

Page 35: ...by switching operations in quick succession Additionally we recommend setting the maximum stage power to 0 to prevent simultaneous switching of stages Configuring the capacitor stages There are two wa...

Page 36: ...ning mode press U change the setting to es by pressing V then press X to confirm After starting learning mode active flashes and the time remaining until the end of the learning cycle is displayed NOT...

Page 37: ...uld switch on at 100 missing compensation power relative to the small est capacitor stage of the system Hysteresis switch off default setting 100 setting range 70 to 150 This value defines the control...

Page 38: ...the attenuation of the display and control behavior to prevent rapid parame ter changes if compensation power is missing Attenuation U default setting 0 setting range 0 to 9 This value defines the dis...

Page 39: ...menus of this window The following error messages can be configured Alarm submenu Possible actions Off Message Alarm relay Message and relay No measuring voltage No stage power PFC too small THD volt...

Page 40: ...be changed by pressing U to start entering values V to change the setting and X to save it The following submenus are available User language In this submenu you can select the language for the LCD d...

Page 41: ...age is marked with an X in the Start menu window This may be for any of the following reasons and needs to be checked Capacitor faulty Fuse faulty The Reset menu item offers various methods of resetti...

Page 42: ...version as a compensation stage output or fan output NOTE The stage outputs are optocoupler outputs If direct fan control is required install an external switch relay power supply input max 30 VDC max...

Page 43: ...The KBR eBus setting is used for testing purposes If Modbus RTU is selected you can set the transmission parameters here The supported transmission parameters are Baud rate baud 4800 9600 19200 38400...

Page 44: ...or excessive current input and defective contactors Undercompensation all stages are switched on The existing system is insufficiently dimensioned e g due to new inductive consumers Please contact you...

Page 45: ...ce in automatic mode Check the cooling air setting fans temperature monitoring function Check that the controller temperature relay switches the fans on at 28 C Check that the temperature monitoring s...

Page 46: ...permissible value 6 A Frequency Network frequency measurement fNetwork Units Hz Measuring range 41 70 Hz Apparent power Calculation Stot 3 phase Units kVA Display range 0 0 VA to 9999 9 kVA Active po...

Page 47: ...20 ms Harmonics calculation FFT with 128 points over one period Frequency measurement Consumption Voltage measurement between phase Lx N Ly Temperature sensor Analog measurement with PT 1000 11 4 Dev...

Page 48: ...value 6 A Power consumption 0 3 VA at 6 A 0 05 VA at 1 2 A Measuring range 1 measuring range current transformer is configurable Analog input PT 1000 measurement sensor Temperature measurement 10 C t...

Page 49: ...Fuse protection NONE Always short circuit current trans former terminals k and l before opening the circuit Input control voltage Fuse protection max 6 A BUS connection Connection material To ensure p...

Page 50: ...1997 07 3K5 3Z11 IEC721 3 3 3K5 3Z11 Operating tempera ture 5 C 55 C Humidity 5 95 non condensing Storage temperature 25 C to 70 C Operating altitude up to max 2000 m above sea level Electrical safety...

Page 51: ...80 72 00 86 40 100 80 108 00 115 10 129 60 144 00 172 80 180 00 216 00 259 20 288 00 360 00 432 00 504 00 576 00 648 00 720 00 4 x 1 5 4 x 1 5 4 x 1 5 4 x 1 5 4 x 1 5 4 x 1 5 4 x 1 5 4 x 2 5 4 x 2 5...

Page 52: ...52 KBR multicomp F144 3 6DO 12DO 13 Data point description for the Modbus protocol multicomp F144 3 13 1 Modbus commands supported 13 2 Data formats 13 3 Interface parameters 13 4 Device settings 13 5...

Page 53: ...8 Address 0 1 2 3 Contents 0x12 0x34 0x56 0x78 Rule for byte sequence MSB before LSB float Format Complies with the IEEE 754 standard Representation 4 bytes Accuracy 24 bits represent 7 decimal points...

Page 54: ...ue of 130 127 3 The mantissa has the following value 10010000000000000000000 The decimal point can be found at the left end of the mantissa preceded by a 1 This position does not appear in the hexadec...

Page 55: ...1 0 1 0 1 0 1 1 0 1 0 1 0 0 1 1 1 1 1 1 1 Hex 42 35 6A 7F Exponent 10000100 bin 132 dec Exp 132 127 5 Mantissa S 0 Sign positive 01101010110101001111111 bin Decimal point added to the first position...

Page 56: ...0x04 command read input registers as shown in Table 1 Writing is not possible at present Address Words Description Value Format 0xD002 2 Primary transformer measuring voltage 0 999999 V float 0xD004 2...

Page 57: ...witch off when the value falls below the threshold 0 700 unsigned long 0xD02e 2 Temperature 0 1 C that triggers the stages when the value falls below the threshold 0 700 unsigned long 0xD030 2 Tempera...

Page 58: ...t Qmiss 0 9 unsigned long 0xD058 2 0xd05A 2 0xD05C 2 0xD05E 2 0xD060 2 Extras 0xD062 2 0xD064 2 Light load limit A 0 015 or 0 05 float 0xD066 2 Time until light load switch off in minutes 1 60 unsigne...

Page 59: ...rge time ms 20 9999 unsigned long 0xD088 2 Operating cycles 0 999999 unsigned long 0xD08A 2 0 unsigned long 0xD08C 2 0 unsigned long 0xD08E 2 0 unsigned long 0xD090 2 Base index for the following stag...

Page 60: ...gned long 0xD0DE 2 0 unsigned long 0xD0E0 2 Base index for the following stage parameters addresses 0xD0E0 to 0xD0EE 6 stage 7 unsigned long 0xD0EE 2 0 unsigned long 0xD0F0 2 Base index for the follow...

Page 61: ...0xD130 to 0xD13E 11 stage 12 unsigned long 0xD13E 2 0 unsigned long Request 01 04 D0 01 00 02 xx xx in which 01 Device address 04 Command D0 01 Read from register 0xD002 Measuring voltage primary tra...

Page 62: ...t 0x0012 2 THD float 0x0014 2 Temperature C float 0x0016 2 Overtemperature switch off float 0x0018 2 Voltage 3rd harmonic float 0x001a 2 Voltage 5th harmonic float 0x001c 2 Voltage 7th harmonic float...

Page 63: ...Light load operation Bit 05 set Voltage harmonics limit reached Bit 06 set Operating cycle limit reached Bit 07 set PFC too small Error messages Bit 00 set No stage power relay set Bit 01 set System...

Page 64: ...xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx xx yy yy where 01 Device address 04 Command 4C 76 data bytes xx...

Page 65: ...n is read in the process The device supplies the Basic Device Identification Regular and Extended Device Identification are optional according to the Modbus definition Example Modbus RTU Request 01 2B...

Page 66: ...Modbus definition 00 No further information follows no additional telex required 00 Next object ID 03 Number of objects 00 Object ID 00 08 Length of the text of ID 00 4B 42 52 20 47 6D 62 48 KBR GmbH...

Page 67: ...Rev 1 00 Notes 22585_EDEBDA0252 0318 1_EN KBR multicomp F144 3 6DO 12DO...

Page 68: ...22585_EDEBDA0252 0318 1_EN Am Kiefernschlag 7 D 91126 Schwabach Germany T 49 0 9122 6373 0 F 49 0 9122 6373 83 El info kbr de www kbr de KBR Kompensationsanlagenbau GmbH...

Reviews: