Rev. 1.00
22585_EDEBD
A0252-0318-1_EN
42
KBR multicomp F144-3 6DO/12DO
Description of the display window
Dimmer brightness:
The LCD dimming can be changed in this submenu. Setting range: 0 to 9. The
brightness is reduced after a set time of 15 minutes.
Light load limit:
In this submenu, the light load detection limit can be changed to either 15
mA or 50 mA.
Light load delay:
The light load detection delay time can be changed in this submenu. It can be
varied between 1 and 60 minutes.
Fan relay:
In this submenu, you can set the last stage output (stage 6 or 12, depending
on the device version) as a compensation stage output or fan output.
NOTE
The stage outputs are optocoupler outputs. If direct fan control is required,
install an external switch relay (power supply input max. 30 VDC, max. 35 mA,
switching capacity output 250 VAC / 2A, fl oating).
Switching threshold fan on:
In this submenu, you can change the switch-on threshold for the fan output.
It can be varied between 0 °C and 60 °C.
Switching threshold fan off :
In this submenu, you can change the switch-off threshold for the fan output.
It can be varied between 0 °C and 60 °C.
NOTE
The fan has a run-on time of 30 minutes to prevent unnecessarily frequent
switching.
Switching threshold system off :
In this submenu, the switching threshold for switching off the system can be
varied It can be varied between 0 °C and 60 °C.