Address Words Description
Value
Format
0xD052 2
Percentage of smallest available stage before
stages can be switched off
70-150
unsigned
long
0xD054 2
Alarm relay (not in use)
---
unsigned
long
0xD056 2
Temperature evaluation
0 = off // 1
= on
unsigned
long
Stage parameters
0xD058 2
Output index for the following stage param-
eters (addresses 0xD05A to 0xD06C)
0
unsigned
long
0xD05A 2
Type (not in use)
---
unsigned
long
0xD05C 2
Mode
0 = off // 1
= auto 2
= on
unsigned
long
0xD05E 2
Cabinet number (not in use)
---
unsigned
long
0xD060 2
Detuning factor (not in use)
---
unsigned
long
0xD062 2
Stage power [0.1 kvar]
(c = positive // i = negative)
c99999 –
i99999
unsigned
long
0xD064 2
Discharge time [ms]
0-99999
unsigned
long
0xD066 2
Operating cycles
0-999999 unsigned
long
0xD068 2
Operating hours (not in use)
---
long
0xD06A 2
Total temperature switch-offs
(not in use)
---
long
0xD06C 2
Type of connection of the stage
(bit coded, only 1 bit active)
Bit0:
Delta Bit3:
L3N Bit6:
L31
Bit1:
L1N Bit4:
L12
Bit2:
L2N Bit5:
L23
unsigned
long
Data point description for the Modbus protocol