V2.00
KBR multicomp F144-3PH
47
19837_EDEBD
A0227-1816-1_EN
Technical data
7. Technical data multicomp F144-3PH
7.1
Measuring and display values
Voltage
Units
[V, kV;] display is switched automatically
Display range
0 V to 999 kV
Measuring range
3-phase 25 … 230 … 280 VAC, 50 / 60 Hz
Electricity
(apparent
current)
Units
[A;kA] display is switched
automatically
Display range
0 A to 999 kA
Measuring range
3-phase 0,03 … 5 … 6 A
Frequency
Power frequency
measurement
measured with power supply correction
Units
[Hz]
Measuring range
40.....62 Hz
Apparent
power
Calculation
Stot , single-phase / 3-phase
Units
kVA
Display range
0 VA to 999 MVA
Active power Calculation
Ptotal , single-phase / 3-phase
Units
kW
Display range
0.00W to 999 MW
Reactive
power
Calculation
®
ind. & cap. Qtotal; Qmiss; distinction between ind./cap.
Units
kvar
Display range
0.00Var to 999 MVar
Power factor Calculation
®
ind. & cap. cosφ; distinction between ind./cap. cosφ in
the display
Display range
CosPhi 0.1ind.
¬
1
®
0.1cap.
Harmonics
Distortion factor (THD) for
voltage; Id for current
Voltage: THD-U
Current: Id
Partial distortion factors 3rd; 5th; 7th; 9th; 11th; 13th; 15th; 17th; 19th;
voltage and current harmonics
Units
[%] for voltage, [A] for current
Measuring range
0% to 100% for voltage, 0 to 999 kA
for current