KBR multicomp F144-3PH
V2.00
62
19837_EDEBD
A0227-1816-1_EN
5 Device settings
The settings are read with the 0x04 command (read input registers) in accordance with
table 1. Writing is not possible at the moment.
Address Words Description
Value
Format
0xD002 2
Measuring voltage primary transformer
(applies to all three phases)
unsigned
long
0xD004 2
Measuring voltage secondary transformer
(applies to all three phases)
unsigned
long
0xD006 2
Measuring current primary transformer
(applies to all three phases)
unsigned
long
0xD008 2
Measuring current secondary transformer
(applies to all three phases)
unsigned
long
0xD00A 2
Frequency correction
(0=auto // 1=50Hz // 2=60Hz)
0-2
unsigned
long
0xD00C 2
Average current value,
averaging time in min
1-15
unsigned
long
0xD00E 2
Attenuation voltage
0-9
unsigned
long
0xD010 2
Attenuation current
0-9
unsigned
long
0xD012 2
Primary transformer induced current
(not available)
---
unsigned
long
0xD014 2
Secondary transformer induced current
(not available)
---
unsigned
long
0xD016 2
Connected phase voltage measurement
(not available)
---
unsigned
long
0xD018 2
Connected phase current measurement
(0-120-240)
0=0°//
1=120°//
2=240°
unsigned
long
0xD01a 2
Daylight saving time (not available)
unsigned
long
0xD01c 2
Switching standard time
--> daylight saving time (not available)
unsigned
long
0xD01e 2
Switching daylight saving time -
-> standard time (not available)
unsigned
long
0xD020 2
Threshold value for voltage dip
(not available)
---
float
0xD022 2
Attenuation for missing compensation power 0-9
unsigned
long
0xD024 2
free
---
float
Data point description for the Modbus protocol