KBR multicomp F144-3PH
V2.00
52
19837_EDEBD
A0227-1816-1_EN
Setting ranges
7.10 setting ranges
Primary voltage
1 V to 999999 V Ph-Ph
Secondary voltage
1 V to 999999 V Ph-Ph
Zero-point creator
On, Off
Scanning frequency
Auto, 50 Hz, 60 Hz
Primary current
1 A to 999999 A
Secondary current
1 A oder 5 A
Phase I
0°, 120°, 240°
Consumption target Cosφ 1.2
ind. 0.50 to cap. 0.50
Recovery target cosφ
ind. 0.50 to cap. 0.50
FTS alarm cosφ
ind. 0.50 to cap. 0.50
Stage power
0 to 9999.9 kvar inductive or capacitive
Type of connection
3-phase, phase-phase, single-phase
Discharge time
10 ms to 999.99 sec (thyro < 1 second)
Max. switching capacity per switching operation
0 to 999999 kVar
Contrast settings
00% to 99%
Brightness setting
00% to 99%
Dimming time
1 to 255 minutes
Dimming brightness
00% to 99%
Language selection text display
German, English
Hysteresis connection
70 to 150 %
Hysteresis disconnection
70 to 150 %
Idle time
0 to 999.99 sec.
Alarm delay FTS
1 to 9999 sec.
Switching interval
10 to 999.99 sec.
Attenuation coefficient current
0 to 9
Attenuation coefficient voltage
0 to 9
Attenuation coefficient Qmiss
0 to 9
Temperature measurement
active, inactive
Switching threshold for switching on fan 0 to 70°C
Switching threshold for switching off fan 0 to 70°C
Switching threshold for switching on stages 0 to 70°C
Switching threshold for switching off stages 0 to 70°C
Overvoltage switch-off limit
Up to 150%, dependent on primary voltage
Low load limit
0.01 to 9999.99 (in A)
Low load delay
1 to 60 Minutes
Average current limit
1 to 9999 (in A)
averaging time 8 minutes,
cannot be configured on the device
Operating cycle limit
0 to 999999
THD limit
0 to 100%, (0% = deactivated)
I d limit
0 to 100%, (0% = deactivated)
Reset parameters
Reset to factory settings (default settings)
Password
4-digits, numerical (9999, meaning
all functions are accessible)