background image

7

Ensure that the refrigeration system is earthed prior 

to charging the system with refrigerant.
Label the system when charging is complete (if not 

already).
Extreme care shall be taken not to overfill the refri-

geration system. Prior to recharging the system it 

shall be pressure tested with OFN. The system shall 

be leak tested on completion of charging but prior to 

commissioning. A follow up leak test shall be carried 

out prior to leaving the site.

14. Decommissioning

Before carrying out this procedure, it is essential that 

the technician is completely familiar with the equip-

ment and all its detail. It is recommended good prac-

tice that all refrigerants are recovered safely. Prior to 

the task being carried out, an oil and refrigerant sam-

ple shall be taken in case analysis is required prior 

to re-use of reclaimed refrigerant. It is essential that 

electrical power is available before the task is com-

menced.
a) Become familiar with the equipment and its ope-

ration.
b) Isolate system electrically.
c) Before attempting the procedure ensure that:
Mechanical handling equipment is available, is requi-

red, for handling refrigerant cylinders;
All personal protective equipment is available and be-

ing used correctly;
The recovery process is supervised at all times by a 

competent person;
Recovery equipment and cylinders conform to the 

appropiate standards.
d) Pump down refrigerant system, if possible.
e) If a vacuum is not possible, make a manifold so 

that refrigerant can be removed from various part of 

the system.
f) Make sure that cylinder is situated on the scales 

before recovery takes place.
g) Start the recovery machine and operate in accor-

dance with manufacturer’s instructions.
h) Do not overfill cylinders. (No more than 80% volu-

me liquid charge).
i) Do not exceed the maximum working pressure of 

the cylinder, even temporarily.
j) When the cylinders have been filled correctly and 

the process completed, make sure that the cylinders 

and the equipment are removed from site promptly 

and all isolation valves on the equipment are closed 

off.
k) Recovered refrigerant shall not be charged into 

another refrigeration system unless it has been clea-

ned and checked.

15. Labelling
       Equipment shall be labelled stating that it has been 

de-commissioned and emptied of refrigerant. The la-

bel shall be dated and signed. Ensure that there are 

labels on the equipment stating the equipment con-

tains flammable refrigerant.

16. Recovery

When removing refrigerant from a system, either for 

servicing or decommissioning, it is recommended 

good practice that all refrigerants are removed safely.
When transferring refrigerant into cylinders, ensure 

that only appropiate refrigerant recovery cylinders 

are employed.
Ensure that the correct number of cylinders to be 

used are designated for the recovered refrigerant 

and labelled for that refrigerant (i.e. special cylinders 

for the recovery of refrigerant). Cylinders shall be 

complete with pressure relief valve and associated 

shut-off valves in good working order. Empty reco-

very cylinders are evacuated and, if possible, cooled 

before recovery occurs.
The recovery equipment shall be in good working or-

der to set of instructions concerning the equipment 

that is at hand and shall be suitable for the recovery 

of flammable refrigerants. In addition, a set of calibra-

ted weighing scales shall be available and in good 

working order. Hoses shall be complete with leak-free 

disconnect couplings and in good condition. Before 

using the recovery machine, check that it is in satis-

factory working order, has ben properly maintained 

and that any associated electrical components are 

sealed to prevent ignition in the event of a refrigerant 

release. Consult manufacturer if in doubt.
The recovered refrigerant shall be returned to the re-

frigerant supplier in the correct recovery cylinder, and 

the relevant Waste Transfer Note arranged. Do not 

mix refrigerants in recovery units and especially not in 

cylinders. If compressors or compressor oils are to be 

removed, ensure that they have been evacuated to 

and acceptable level to make certain that flammable 

refrigerant does not remain within the lubricant. The 

evacuation process shall be carried out prior to retur-

ning the compressor to the suppliers. Only electric 

heating to the compressor body shall be employed 

to accelerate this process. When oil is drained from a 

system, it shall be carried out safely.

Note About Fluorinated Gasses
-  Fluorinated greenhose gases are contained in hermeti-

cally sealed equipment. For specific information on the 

type, the amount and tje CO2 equivalent in tonnes of 

the fluorinated greenhose gas (on some models), plea-

se refer to the relevant label on the unit itself.

-  Installation, service, maintenance and repair of this unit 

mus be performed by a certified technician.

-  Product uninstallation and recycling must be performed 

by a certified technician.

Warnings 

(for using R-290 refrigerant only)

Summary of Contents for KP-35 CP10

Page 1: ...nditioner Thank you for purchasing our Portable Air Conditioner Before using your air conditioner please read this instruction manual carefully and keep it for future reference READ AND SAVE THESE INSTRUCTIONS KP 35 CP10 KP 35 HP10 ...

Page 2: ...nts Safety Precautions 2 Cautions 3 Warnings for using R 290 refrigerant only 4 Preparations 8 Installation 9 Operation 12 Maintenance 15 Faults Diagnosis 16 Design and Compliance Notes 17 Sociable Remark 18 ...

Page 3: ...ower cord or use an extension cord to power the unit DO NOT share a single outlet with other electrical appliances Improper power supply can cause fire or electrical shock DO NOT install your air conditioner in a wet room such as a bathroom or laundry room Too much exposure to water can cause electrical components to short circuit DO NOT install the unit in a location that may be exposed to combust...

Page 4: ... away from traffic area and where it will not be tripped over Do not operate unit with a damaged cord plug power fuse or circuit breaker Discard unit or return to an authorized service facility for examination and or repair To reduce the risk of fire or electric shock do not use this fan with any solid state speed control device The appliance shall be installed in accordance with national wiring r...

Page 5: ...ssment authority which authorises their competence to handle refrigerants safely in accordance with an industry recognised assessment specification Servicing shall only be performed as recommended by the equipment manufacturer Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrige...

Page 6: ...e risk of fire or explosion All possible ignition sources incluiding cigarrette smoking should be kept sufficiently far away from the site of installa tion repairing removing and disposal during which flammable refrigerant can possibly be released to the surrounding space Prior to work takking place the area around the equipment is to be surveyed to make sure that there are no flammable hazards or...

Page 7: ...ammable refrige rants Electronic leak detectors shall be used to detect flam mable refrigerants but the sensitivity may not be ade quate or may need re calibration Detection equip ment shall be calibrated in a refrigerant free area Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used Leak detection equipment shall be set at a percentage of the LFL...

Page 8: ...ipment stating the equipment con tains flammable refrigerant 16 Recovery When removing refrigerant from a system either for servicing or decommissioning it is recommended good practice that all refrigerants are removed safely When transferring refrigerant into cylinders ensure that only appropiate refrigerant recovery cylinders are employed Ensure that the correct number of cylinders to be used ar...

Page 9: ...tically handle both sides panel caster upper air filter behind the grille upper air intake drain outlet air outlet lower air filter lower air intake drain outlet only for pump heating mode power cord buckle power cord outlet power plug socket bottom tray drain outlet FRONT REAR ...

Page 10: ...ommend Installation NOTE All the illustrations in the manual are for explanation purpo se only Your machine may be slightly different The actual shape shall prevail The unit can be controlled by the unit control panel alone or with the remote controller This manual does not include Remote Controller Operations see the Remote Control Illustration packed with the unit for details When there are wide...

Page 11: ...tep Two Install the Exhaust hose assembly to the unit Insert unit adaptor of the Exhaust hose assembly into the lower groove of the air outlet of the unit while the hook of the adaptor is aligned with the hole seat of the air outlet and slide down the Exhaust hose assembly along the arrow direction for installation Unit adaptor Press into Press into Exhaust hose Exhaust hose assembly Window slider...

Page 12: ... into the room Security Bracket 2 Screws 2 Screws Security Bracket or 4 If desired install the security bracket with 2 screws as shown or 5 Insert the window slider adaptor into the hole of the window slider Type 2 Wall Installation optional 1 Cut a 125mm 4 9inch hole into the wall for the Wall Exhaust Adaptor B 2 Secure the Wall Exhaust Adaptor B to the wall using the four Anchors and Screws prov...

Page 13: ...ight FOLLOW ME light COOL mode light MED fan speed light SLEEP light FAN mode light LOW fan speed light Degrees Celsius DRY mode light AUTO fan speed light Degrees Fahrenheit AUTO mode light FILTER light LED display WIRELESS light POWER MANAGEMENT light NOTE The control panel may be look like one of the followings KP 35 CP10 KP 35 HP10 NOTE The unit you purchased may be look like one of the follow...

Page 14: ... The mode indicator light illuminates under the different mode settings Up and Down buttons Used to adjust increasing decreasing tempe rature settings in 1ºC 1ºF or 2ºF increments in a range of 17ºC 62ºF to 30ºC 86ºF or 88ºF or the TIMER setting in a range of 0 24 hrs NOTE The control is capable of displaying tem perature in degrees Fahrenheit or degrees Cel sius To convert from one to the other p...

Page 15: ... or down button to select the desired Auto on start time When the unit is off press the Timer button to initiate the Auto on start program press it again within 5 se conds will initiate the Auto off stop program Press or hold the UP or DOWN button to change the Auto time by 0 5 hour increments up to 10 hours then at 1 hour increments up to 24 hours The control will count down the time remaining un...

Page 16: ... sure to reinstall the bottom drain plug firmly to prevent leakage before using the unit SCALE 0 500 Remove the upper drain plug Continuous drain hose During heating pump mode remove the lower drain plug from the back of the unit install the drain con nector 5 8 universal female mender with 3 4 hose locally purchased For the models without drain connector just attach the drain hose to the hole Pla...

Page 17: ... cloth before wiping around the controls Excess water in or around the controls may cause damage to the unit Faults Diagnosis Please check the machine according to the following form before asking for maintenance Problem Possible Cause Troubleshooting Unit does not turn on when pressing ON OFF button P1 Error Code The Water Collection Tray is full Turn off the unit drain the water from the Water C...

Page 18: ...to the service web site please check for the latest version Energy Rating Information The Energy Rating for this unit is based on an installation using an un extended exhaust duct without window slider adaptor or wall exhaust adaptor A as shown in the Installation section of this manual Unit Temperature Range Mode Temperature Range Cool 17 35ºC 62 95ºF Dry 13 35ºC 55 95ºF Heat pump heat mode 5 30º...

Page 19: ...has established collection systems where electronic waste can be disposed of at least free of charge to the user B When buying a new product the retailer will take back the old product at least free of charge C The manufacturer will take back the old appliance for disposal at least free of charge to the user D As old products contain valuable resources they can be sold to scrap metal dealers Wild ...

Page 20: ......

Reviews: