background image

5

Warnings 

(for using R-290 refrigerant only)

1.  Transport of equipment containing flammable refrige-

rants.

See transport regulations

2. Marking of equipment using signs
    See local regulations
3.  Disposal of equipment using flammable refrigerant
    See national regulations.
4. Storage of equipment/appliances
     The storage of equipment should be in accordance with 

the manufacturer’s instructions.

5. Storage of packed (unsold) equipment
     Storage package protection should be constructed 

such thay mechanical damage to the equipment insi-

de the package will not cause a leak of the refrigerant 

charge.

     The maximum number of pieces of equipment permi-

tted to be stored together will be determined by local 

regulations.

6. Information on servicing

1) Check to the area
Prior the beginning work on systems containing flam-

mable refrigerants, safety checks are necessary to en-

sure that the risk of ignition is minimised. For repair 

to the refrigerating system, the following precautions 

shall be complied with the prior to conducting work on 

the system.
2) Work procedure
Work shall be undertaken under a controlled procedu-

re so as to minimise the risk of a flammable gas or va-

pour being present while the work is being performed.
3) General work area
All maintenance staff and others working in the local 

area shall be instructed on the nature of work being 

carried out. Work in confined spaces shall be avoided. 

The area around the workspace shall be sectioned off. 

Ensure that the conditions within the area have been 

made safe by control of flammable refrigerants.
4) Checking for presence of refrigerant
The are shall be checked with an appropiate refrige-

rant detector prior to and during work, to ensure the te-

chnician is aware of potentially flammable atmosphe-

res. Ensure that the leak detection equipment being 

used  is  suitable  for  use  with  flammable  refrigerants, 

i.e. non-sparking, adequately sealed or instrinsically 

safe.
5) Presence of fire extinguisher
If any hot work is to be conducted on the refrigeration 

equipment or any associated parts, appropiate fire ex-

tinguishing equipment shall be available to hand. Have 

a dry powder or CO2 fire extinguisher adjacent to the 

charging area.
6) No ignition sources
No person carrying out work in relation to a refrige-

rantion system which involves exposing any pipe work 

that  contains  or  has  contained  flammable  refrigerant 

shall use any sources of ignition in such a manner that 

it may lead to the risk of fire or explosion. All possible 

ignition sources, incluiding cigarrette smoking, should 

be kept sufficiently far away from the site of installa-

tion, repairing, removing and disposal, during which 

flammable refrigerant can possibly be released to the 

surrounding space. Prior to work takking place, the 

area around the equipment is to be surveyed to make 

sure that there are no flammable hazards or ignition 

risks. No Smoking signs shall be displayed.
7) Ventilated area
Ensure that the area is in the open or that it is ade-

quately ventilated before breaking into the system or 

conducting any hot work. A degree of ventilation shall 

continue during the period that the work is carried out. 

The ventilation should safely disperse any released 

refrigerant and preferably expel it externally into the 

atmosphere.
8) Checks to the refrigeration equipment
Where electrical components are being changed, they 

shall be fit for the purpose and to the correct specifica-

tion. At all times the manufacturer’s maintenance and 

service guidelines shall be followed. If in doubt consult 

the manufacturer’s technical department for assistan-

ce. The following checks shall be applied to installa-

tions using flammable refrigerants:
The charge size is in accordance with the room size 

within which the refrigerant containing parts are ins-

talled;
The ventilation machinery and outlet are operating 

adequately and are not obstructed;
If an indirect refrigerating circuit is being used, the se-

condary circuit shall be checked for the presence of 

refrigerant;
Marking to the equipment continues to be visible and 

legible. Markings and signs that are illegible shall be 

corrected;
Refrigeration pipe or components are installed in a po-

sition where they are unlikely to be exposed to any 

substance which may corrode refrigerant containing 

components, unless the components are constructed 

of materials which are inherently resistant to being co-

rroded or are suitably protectec against being so co-

rroded.
9) Checks to electrical devices
Repair and maintenance to electrical components sha-

ll include intitial safety checks and component inspec-

tion procedures. If a fault exists that could comprise 

safety, then no electrical supply shall be connected to 

the circuit until it is satisfactorily dealt with. If the fault 

cannot be corrected immediately but it is necessary 

to continue operation, an adequate temporary solution 

shall be used. This shall be reported to the owner of 

the equipment so all parties are advised.
Intitial safety checks shall include:
That capacitors are discharged: this shall be done in a 

safe manner to avoid possibility of sparking;

Summary of Contents for KP-35 CP10

Page 1: ...nditioner Thank you for purchasing our Portable Air Conditioner Before using your air conditioner please read this instruction manual carefully and keep it for future reference READ AND SAVE THESE INSTRUCTIONS KP 35 CP10 KP 35 HP10 ...

Page 2: ...nts Safety Precautions 2 Cautions 3 Warnings for using R 290 refrigerant only 4 Preparations 8 Installation 9 Operation 12 Maintenance 15 Faults Diagnosis 16 Design and Compliance Notes 17 Sociable Remark 18 ...

Page 3: ...ower cord or use an extension cord to power the unit DO NOT share a single outlet with other electrical appliances Improper power supply can cause fire or electrical shock DO NOT install your air conditioner in a wet room such as a bathroom or laundry room Too much exposure to water can cause electrical components to short circuit DO NOT install the unit in a location that may be exposed to combust...

Page 4: ... away from traffic area and where it will not be tripped over Do not operate unit with a damaged cord plug power fuse or circuit breaker Discard unit or return to an authorized service facility for examination and or repair To reduce the risk of fire or electric shock do not use this fan with any solid state speed control device The appliance shall be installed in accordance with national wiring r...

Page 5: ...ssment authority which authorises their competence to handle refrigerants safely in accordance with an industry recognised assessment specification Servicing shall only be performed as recommended by the equipment manufacturer Maintenance and repair requiring the assistance of other skilled personnel shall be carried out under the supervision of the person competent in the use of flammable refrige...

Page 6: ...e risk of fire or explosion All possible ignition sources incluiding cigarrette smoking should be kept sufficiently far away from the site of installa tion repairing removing and disposal during which flammable refrigerant can possibly be released to the surrounding space Prior to work takking place the area around the equipment is to be surveyed to make sure that there are no flammable hazards or...

Page 7: ...ammable refrige rants Electronic leak detectors shall be used to detect flam mable refrigerants but the sensitivity may not be ade quate or may need re calibration Detection equip ment shall be calibrated in a refrigerant free area Ensure that the detector is not a potential source of ignition and is suitable for the refrigerant used Leak detection equipment shall be set at a percentage of the LFL...

Page 8: ...ipment stating the equipment con tains flammable refrigerant 16 Recovery When removing refrigerant from a system either for servicing or decommissioning it is recommended good practice that all refrigerants are removed safely When transferring refrigerant into cylinders ensure that only appropiate refrigerant recovery cylinders are employed Ensure that the correct number of cylinders to be used ar...

Page 9: ...tically handle both sides panel caster upper air filter behind the grille upper air intake drain outlet air outlet lower air filter lower air intake drain outlet only for pump heating mode power cord buckle power cord outlet power plug socket bottom tray drain outlet FRONT REAR ...

Page 10: ...ommend Installation NOTE All the illustrations in the manual are for explanation purpo se only Your machine may be slightly different The actual shape shall prevail The unit can be controlled by the unit control panel alone or with the remote controller This manual does not include Remote Controller Operations see the Remote Control Illustration packed with the unit for details When there are wide...

Page 11: ...tep Two Install the Exhaust hose assembly to the unit Insert unit adaptor of the Exhaust hose assembly into the lower groove of the air outlet of the unit while the hook of the adaptor is aligned with the hole seat of the air outlet and slide down the Exhaust hose assembly along the arrow direction for installation Unit adaptor Press into Press into Exhaust hose Exhaust hose assembly Window slider...

Page 12: ... into the room Security Bracket 2 Screws 2 Screws Security Bracket or 4 If desired install the security bracket with 2 screws as shown or 5 Insert the window slider adaptor into the hole of the window slider Type 2 Wall Installation optional 1 Cut a 125mm 4 9inch hole into the wall for the Wall Exhaust Adaptor B 2 Secure the Wall Exhaust Adaptor B to the wall using the four Anchors and Screws prov...

Page 13: ...ight FOLLOW ME light COOL mode light MED fan speed light SLEEP light FAN mode light LOW fan speed light Degrees Celsius DRY mode light AUTO fan speed light Degrees Fahrenheit AUTO mode light FILTER light LED display WIRELESS light POWER MANAGEMENT light NOTE The control panel may be look like one of the followings KP 35 CP10 KP 35 HP10 NOTE The unit you purchased may be look like one of the follow...

Page 14: ... The mode indicator light illuminates under the different mode settings Up and Down buttons Used to adjust increasing decreasing tempe rature settings in 1ºC 1ºF or 2ºF increments in a range of 17ºC 62ºF to 30ºC 86ºF or 88ºF or the TIMER setting in a range of 0 24 hrs NOTE The control is capable of displaying tem perature in degrees Fahrenheit or degrees Cel sius To convert from one to the other p...

Page 15: ... or down button to select the desired Auto on start time When the unit is off press the Timer button to initiate the Auto on start program press it again within 5 se conds will initiate the Auto off stop program Press or hold the UP or DOWN button to change the Auto time by 0 5 hour increments up to 10 hours then at 1 hour increments up to 24 hours The control will count down the time remaining un...

Page 16: ... sure to reinstall the bottom drain plug firmly to prevent leakage before using the unit SCALE 0 500 Remove the upper drain plug Continuous drain hose During heating pump mode remove the lower drain plug from the back of the unit install the drain con nector 5 8 universal female mender with 3 4 hose locally purchased For the models without drain connector just attach the drain hose to the hole Pla...

Page 17: ... cloth before wiping around the controls Excess water in or around the controls may cause damage to the unit Faults Diagnosis Please check the machine according to the following form before asking for maintenance Problem Possible Cause Troubleshooting Unit does not turn on when pressing ON OFF button P1 Error Code The Water Collection Tray is full Turn off the unit drain the water from the Water C...

Page 18: ...to the service web site please check for the latest version Energy Rating Information The Energy Rating for this unit is based on an installation using an un extended exhaust duct without window slider adaptor or wall exhaust adaptor A as shown in the Installation section of this manual Unit Temperature Range Mode Temperature Range Cool 17 35ºC 62 95ºF Dry 13 35ºC 55 95ºF Heat pump heat mode 5 30º...

Page 19: ...has established collection systems where electronic waste can be disposed of at least free of charge to the user B When buying a new product the retailer will take back the old product at least free of charge C The manufacturer will take back the old appliance for disposal at least free of charge to the user D As old products contain valuable resources they can be sold to scrap metal dealers Wild ...

Page 20: ......

Reviews: