III. GUIDELINES FOR PIPE MOUNTING
The CLASSIC 800 is a flow, point lev
el, interface and temperature sensing dev
ice. The sensor tip must be
inserted in the proper location and to the proper depth in order to accurately react to your process
conditions. The following information, including Figures 5 through 9, should be considered as text book
examples for proper installation.
Notes:
Most pipe connections for instrumentation are a v
ariation of a butt-weld-type such as the weldolet or
threadolet shown in Figure 4. The length of this connection must be added to the pipe diameter when
determining the insertion length for the sensor. The Kayden literature refers to this “insertion length”
dimension as the “U” length, Figure 5.
Horizontal Pipe
– Side Mount (Ideal)
As shown in Figure 6a, ensure sensing tip is inserted to a point between 5% and 75% of the inside
diameter of the pipe. Av
oid locations where sediment may accumulate and isolate the sensing tip from the
process.
Horizontal Pipe
– Top Mount
Gas will always collect at the top of any pipe, ensure sensing tip is inserted to a point where it will be
constantly and fully exposed to the desired process media.
Horizontal Pipe
– Bottom Mount
Because sediment will always collect at the bottom of any pipe, ensure sensing tip is inserted to a point
where it will be constantly and fully exposed to the desired process media. Av
oid locations where sediment
may accumulate and ev
entually isolate the sensing tip from the process.
Figure 4 - Threadolet
Figure 5 - Insertion ‘U’ Length
Threadolet
Conforms to ASM EB 1 6.1
B
A
Threadolet
Insertion ‘U’ Length
Figure 6a - Horizontal Pipe,
Side Mounting
Figure 6b - Horizontal Pipe,
Top / Bottom Mounting
35% min to 75% max
50% ideal
35% min to 50% max
5% minimum
50% ideal
75% maximum
25472-1 01 -V1 A-JF00-W0010 Rev 02
Summary of Contents for CLASSIC 800 Series
Page 2: ...25472 101 V1A JF00 W0010 Rev 02...
Page 3: ...25472 101 V1A JF00 W0010 Rev 02...
Page 73: ...kayden com 65 CLASSIC 800 CLASSIC 800 Product Manual Notes 25472 101 V1A JF00 W0010 Rev 02...
Page 74: ...kayden com 66 CLASSIC 800 CLASSIC 800 Product Manual Notes 25472 101 V1A JF00 W0010 Rev 02...