Configuration
B 3.9 Description of the individual parameters
The square brackets [ ] behind the entries indicate the numerical value; this is displayed numerically in the oper-
ating language (see
P5-Language
). If a natural language (German, English ...) is chosen, the corresponding
text appears instead.
B 3.10 Basic parameters
P1-f_rated
Rated frequency value (speed preselection) for the motor (input on control panel).
By means of parameter
P8-speed displ
, this parameter can be changed from frequency display to speed
display. The number of motor poles
P96-no. of poles
is taken into account. Here, only values between
the min. frequency P41-f-mot-min and the max. frequency P42-f-mot-max can be set.
Minimum value:
30 Hz
Maximum value: 3000 Hz
Factory setting:
50 Hz
P3-para level
Indicates the operating state
Values:
[0]
Operation
- only basic and display values (P1...P39) are accessible.
[1]
Parameter
- all parameters P1 to P150 are accessible
Factory setting:
[0]
Operation
P4-display
Selection of the standard display in the normal state
Values:
[0]
Combi display
- Combination display consisting of actual motor values
P14-f_motor
,
P15-V_motor
and
P17-i_mot app
[1]
f_out_act
- Inverter output frequency (
P13-f_out_act
)
[2]
V_motor
- Voltage at motor (
P15-V_motor
)
[3]
I_mot_app
- Apparent current through motor (
P17-I_mot_app
)
[4]
I_mot_real
- Real current through motor (
P18-I_mot_real
)
[5]
V circ
- Voltage at intermediate circuit (
P16-V_circ
)
[6]
P_real
- Real power (
P19-P_real
)
[7]
Norm_value
- Standard factor * output frequency (
P6-F_norm
*
P13-f_off_act
)
Factory setting:
[0]
Combi display
P5-language
Selection of the language which is to be used for operation
Values:
[0]
numerical
- only numerical display without text information
[1]
German
[2]
English
Factory setting:
[1]
German
P6-F_norm
Determination of the factor for the standard value display (norm_value =
P6-F_norm * P13-f_off_act
).
This factor is evaluated only if
P4-display
is set to
norm_value
. With the standard value display, the out-
put frequency can be converted into a process variable via the standard factor and can be displayed. A display
in, e.g. m/s can thus be shown.
Minimum value:
0.01
Maximum value: 500.00
Factory setting:
1.00