Configuration
P135-f_rem_min
Minimum rated frequency for analogue rated frequency default AIN1 at V_e = 0V. This parameter is evaluated
only if
P130-analogue AIN1
is configured for rated frequency.
By means of parameter
P8-speed displ
, this parameter can be changed from frequency display to speed
display, the number of poles of the motor
P96-no. of poles
being taken into account.
Minimum value:
0 Hz
Maximum value: 3000 Hz
Factory setting:
0 Hz
P136-f_rem_max
Maximum rated frequency for analogue rated frequency default AIN1 at V_e = 10V. This parameter is evaluated
only if
P130-analogue AIN1
is configured for rated frequency.
By means of parameter
P8-speed displ
, this parameter can be changed from frequency display to speed
display, the number of poles of the motor
P96-no. of poles
being taken into account.
Minimum value:
0 Hz
Maximum value: 3000 Hz
Factory setting:
3000 Hz
P137-f_stop_ana
Stop frequency from analogue rated frequency signal; this makes it possible to achieve an automatic motor stop
with counterclockwise rotation of the nominal value potentiometer or analogue voltage 0 V.
The motor is automatically stopped if the rated frequency default at analogue input AIN1 falls below the value of
this parameter. By means of parameter
P8-speed displ
, this parameter can be changed from frequency
display to speed display, the number of poles of the motor
P8-no. of poles
being taken into account.
In this context, also see the parameter
P135-f_rem_min
and
P136-f_rem_max
.
Values:
[0]
off
- no automatic stop
[1]
f_mot_min
- the value from
P41-f_mot_min
is used
Minimum value:
2 Hz
Maximum value: 3000 Hz
Factory setting:
off
P150-end
(display value)
Last parameter number; serves as end mark.
50