Configuration
Par.
Indication Description
Value
range,
Unit
Factory
Change
No.
in display
physical value
setting
display
U/f characteristic (ASM motor)
P60
V_boost
Startup voltage at f=0
3%V_nom
, 1...50
V~
3%V_nom
I P M
P61
f1
1st characteristic point frequency
f_nom
, 30... 3000
Hz
f_nom
I P M
P62
V1
1st characteristic point voltage
V_nom
, 1... 250
V~
V_nom
I P M
P63
f2
2nd characteristic point frequency
f_nom
, 30... 3000
Hz
f_nom
I P M
P64
V2
2nd characteristic point voltage
V_nom
, 1... 250
V~
V_nom
I P M
P65
f3
3rd characteristic point frequency
f_nom
, 30... 3000
Hz
f_nom
I P M
P66
V3
3rd characteristic point voltage
V_nom
, 1... 250
V~
V_nom
I P M
Control
P70
control
Control principle speed control
U/f,I*R,slip, speed
-
U/f-Tab
.
I P M
P71
I*R factor
I*R compensation gain factor
off, 0.1 ... 30
V/A
off
I P M *
P72
loadcomp
Load compensation gain factor
off, 0.1 ... 40
%/A~
off
I P M *
P73
komp-t_filt
I*R and load compensation. Filter time 1 ... 1000
ms
20
I P M *
P75
slipkomp
Slip compensation gain factor
off, 0.1 ... 10.0
%/A~
off
I P M *
P76
slip-t_filt
Slip compensation filter time
1... 1000
ms
20
I P M *
P77
I-limtr-KP
Current limitation P-component
2 ... 200
%
40
I P
P78
I-limtr-t_n
Current limitation I-component reset time 1 ... 999,
without I-part
ms 10
I
P
P79
V-contr-KP
Voltage control V_WR P-component
5...100
%
20
I P
P80
V-contr-t_n
Voltage control I-component reset time 5 ... 999,
without I-part
ms
10
I P
P81
N-contr-KP
Speed control P-component
5 ... 500
%
50
I P M *
P82
N-contr-t_n
Speed control I-component reset time 5 ... 999,
without I-part
ms 250
I
P M
*
P83
N-contr-t_v
Speed control D-component derivative time
without D-part
, 1...300
ms
30
I P M *
P84
N-contr-t_fil
Speed control T1-element for D-component 1 ... 300
ms
200
I P M *
Monitoring
P85
motor prot.
Monitoring motor temperature
off, PTC, KTY
-
PTC
I P
P86
R_protect
Resistance value for sensor KTY
500...4000
W
1200
I P *
Rated motor data (according to rating plate)
P90
motortype
Motor design
ASM, BLDC, BLDCS
-
no motor
S P
P91
f_mot_nom
Rated motor frequency
30 ... 3000
Hz
50
S P
P92
V_mot_nom
Rated motor voltage
0 ... 250
V~
30
S P
P93
I_mot_nom
Rated motor current
0.5 ... 8.0
A~
1.0
S P
P94
cos phi
Cosine phi at nominal load
20 ... 100
%
85
S P
P96
no.of poles
Number of poles
2, 4, 6, 8
-
2
S P
Device parameters:
ext. brake resistance
P100
R_ext_brake
Resistance of external brake resistor
internal
, 27 ... 100
ohm
internal
S P
P101
P_ext_brake
Power of external brake resistor
150 ... 1000
W
150
S P *
Motor coding
P102
motorcoding
Motor coding, number of motors
off, 2...4 motors
off
S P
Fixed frequencies
P104
fixfreq.FF1
Fixed frequency FF1 (select with IN5,IN6) 30 ... 3000
Hz
100
I P
P105
fixfreq.FF2
Fixed frequency FF2
30 ... 3000
Hz
100
I P
P106
fixfreq.FF3
Fixed frequency FF3
30 ... 3000
Hz
100
I P
P107
fixfreq.FF4
Fixed frequency FF4
30 ... 3000
Hz
100
I P
Remote control:
P110
input IN1
Function digital input IN1
off, start/stop, start pulse
-
off
S P
P111
input IN2
Function digital input IN2
off
, stop, reset, FF, left
-
off
S P
P112
input IN3
Function digital input IN3
see input DE2
-
off
S P
P113
input IN4
Function digital input IN4
see input DE2
-
off
S P
P120
relay REL1
Function relay output REL1
off
, various status signals
-
f_rated
.
I P
P121
relay REL2
Function relay output REL2
see relay REL1
-
overload
I P
P122
relay REL3
Function relay output REL3
see relay REL1
-
standstill
I P
P123
relay REL4
Function relay output REL4
see relay REL1
-
failure
I P
P125
I_warning
var. current limit for relay output
0.4...12
A~
0.4
I P
P130
analog AIN1
Function analogue input AIN1
off
,
rated frequency
-
off
S P
P131
analog AIN2
Function analogue input AIN2
off
,
torque
-
off
S P
P132
analog Aou1
Function analogue output AOUT1
off
, various values
-
I_mot_real
S P
P133
analog Aou2
Function analogue output AOUT2
off
, various values
-
f_mot
S P
P135
f_rem_min
min. rated freq. of analogue input
0.. 3000
Hz
0
I P
P136
f_rem_max
max. rated freq. of analogue input
0.. 3000
Hz
3000
I P
P137
f_stop_ana
Stop via analogue signal
off,
1... 3000
Hz
off
I P
P150
End
End mark
-
-
-
32