background image

2400 – 4400 VFX DECORATIVE AERATOR

MANUAL

884170 / 2021.1.1

14

TROUBLESHOOTING TIPS

The following is provided to help diagnose a probable source of trouble� It is a guideline only and may not show all causes for all problems� 

For additional troubleshooting help, contact your local distributor or visit 

kascomarine�com

 for additional guidance� 

Note: you may need to refer to your owner’s manual that was provided with your control panel for additional control panel settings and adjust

-

ments�

“My Aerator trips the ground fault interrupter in the C-25, C-85, or C-95.” 

This is the most common symptom of several possible problems� To correctly diagnose the problem, you will need to collect more information� 

A Ground Fault Interrupter (GFI) breaker that trips can indicate an electrical service problem, water contamination in the unit and/or cord, bad 

breaker, control box problems, motor problems, etc. Try to find out the answers to these questions before you contact Kasco to narrow down 

the problem:

•  How long does it take to trip the breaker? 

•  Does it always take the same amount of time to trip? 

•  How many times has it tripped? 

•  Have there been any electrical problems in the area recently? 

“My Aerator seems to run slowly.” 

This can also be a symptom of several possible problems� There could be an electrical problem where the unit is not getting the proper volt-

age� This could also indicate a problem with the motor of the unit, which needs to be looked at by an Authorized Repair Center� Check that the 

unit is receiving the proper voltage, and, if so, contact Kasco for further steps� 

“My Aerator hums, but will not start. When I spin the prop with a stick, it starts up.” 

(single phase units only) This indicates a problem with the Starting Capacitor� Each Kasco aerator is equipped with a Starting Capacitor to 

get the unit going when it is first plugged in. If it is operating but not spinning and can be started by spinning the prop with a stick, the Starting 

Capacitor needs to be replaced by an Authorized Repair Center� 

“My Aerator turns itself off and back on without the timer and without tripping the GFI breaker.” 

(single phase units only) Each Kasco aerator has a Thermal Overload built in that will turn the unit off when it overheats� Once the unit 

has cooled down, it will start back up� If you are noticing these symptoms, the unit should be unplugged immediately because the Thermal 

Overload will continue to turn on and off until it burns out and damages the motor� The unit should be unplugged and taken out of the water to 

find the cause of the problem. The problem could be one of many, such as, low water levels, build-up on the unit to prevent heat dissipation, 

something inhibiting the free rotation of the shaft, etc� If something is caught in the unit or there is a build-up of algae, calcium or organic 

matter on the unit, remove the debris and, if caught early enough, the unit should be fine. Contact a Kasco representative before restarting 

the unit� 

“My Aerator flow seems to fluctuate and/or be less than usual.” 

This can occur because of a few different reasons� Most of the time, this symptom is caused by the unit being clogged with debris� A mat of 

weeds, many leaves, plastic bags, etc� can clog up the unit and cause it to be starved of water� If the unit does not have the proper amount of 

water, the flow or pattern will fluctuate up and down and look sporadic. If you are seeing these symptoms, unplug the unit and clean away the 

debris that is clogging up the screen� Another possibility if these symptoms are noticed is a chipped or damaged prop that is causing the unit 

to wobble and not pump properly� When the unit is unplugged, check the prop for damages and replace if damage is found� 

“The GFI breaker trips randomly and sporadically. Sometimes it is a few hours of operation, other times it can be days or weeks.” 

This is referred to as a Nuisance Trip� This usually occurs when the unit is installed a great distance from the initial electric service on the 

property where the ground stake is placed� It is caused by either induced current in the ground wire or a base voltage difference due to soil 

pH levels� To resolve the problem, contact an electrician and install a local grounding stake� This may eliminate the induced current and any 

base voltage differences� This problem can also be caused by a bad breaker or receptacle or having unbalanced incoming voltage lines�

Back to Contents

Summary of Contents for 2400VFX

Page 1: ...FX Decorative Aerator 2400VFX 3400VFX 3400HVFX 4400VFX 4400HVFX 800 Deere Rd Prescott WI 54021 715 262 4488 sales kascomarine com www kascomarine com Document number 884170 Operation Maintenance Manua...

Page 2: ...rd to either side of the float If you have a light kit make sure that the unit cord is tied to one side of the float and the light cord to the other for balance It is extremely important to test the G...

Page 3: ...conductor and or a grounding type attachment plug To reduce the risk of electrical shock be certain the unit is properly connected to the Kasco supplied control panel refer to the instructions include...

Page 4: ...210 4 1 4 split washers 7 840537 5 1 4 3 4 OD flat washer 10 251300 6 1 4 20 x 1 3 4 hex head screw 3 475630 7 Bottom screen section 3 361540 8 1 4 20 nut 3 840536 9 8 nut 6 771034 10 8 flat washer 12...

Page 5: ...with legs 2 Lock washer goes between bolt and flat washer Tighten down in 4 places 3 4 5 9 10 11 12 10 3 Turn over Bring bottom screen sections together 8 4 5 5 6 ASSEMBLY INSTRUCTIONS 4 Tighten down...

Page 6: ...by sinking them further below the surface UNIT INSTALLATION INSTRUCTIONS After unit is installed in the water connect the power cord to a properly installed Kasco control panel C 85 C 95 etc with buil...

Page 7: ...onnect switch to provide circuit protection and a disconnection means C 85 panel requires at least a 30amp protected circuit feeding the panel C 95 panel requires at least a 40 amp protected circuit f...

Page 8: ...n the ON position 2 If the GFCI tests okay restore power by pushing the RESET button back in THE RESET BUTTON MUST BE PUSHED FIRMLY AND FULLY INTO PLACE UNTIL IT LOCKS AND REMAINS DEPRESSED AFTER PRES...

Page 9: ...ippers to the outer ring position for the entire period that the aerator is to be turned ON i e 15min for each tripper on the 24 hour dial When the tripper is pushed to the inside the switch is in the...

Page 10: ...50 5A Prop 2400VFX 1 240595 5B Prop 3400VFX 3400HVFX 1 340595 5C Prop 4400VFX 4400HVFX 1 440600 6A Top disk 2400VFX 1 241025 6B Top disk 3400VFX 3400HVFX 1 241035 6C Top disk 4400VFX 4400HVFX 1 241045...

Page 11: ...unit upside down if it will sit for a long period of time to ensure continued oil lubrication of seals units that sit upright for many months or years have a greater likelihood of seals drying out CLE...

Page 12: ...riginal receipt and registering the equipment online at kascomarine com under the Warranty Information section Once warranty coverage has been established the unit may be sent to Kasco Marine or any K...

Page 13: ...t before the work is performed All estimates that are rejected for repair will be destroyed unless otherwise directed by the customer Rejected equipment can be returned at the customer s expense for s...

Page 14: ...aker single phase units only Each Kasco aerator has a Thermal Overload built in that will turn the unit off when it overheats Once the unit has cooled down it will start back up If you are noticing th...

Page 15: ...customer to ship and pay freight to Kasco Note Contact Information should be that of the person or company to contact for repair information Company name Contact name First name Last name Address Str...

Reviews: