ULTRAFLOW® 54 DN15-125
52
Kamstrup A/S · Technical description · 5512-2464_D1_GB_09.2021
6.11
Electrical connections
6.11.1
Electrical connection of ULTRAFLOW® and MULTICAL®
ULTRAFLOW®
→
MULTICAL®
Blue (ground)
→
11
Red (supply)
→
9
Yellow (signal)
→
10
Table 22. Connection of ULTRAFLOW® and MULTICAL®.
'
Using long signal cables, careful consideration is required in connection with installation. With respect to EMC, there
must be a distance of at least 25 cm between signal cables and all other cables.
6.11.2
Electrical connection of Pulse Transmitter and Pulse Divider
If ULTRAFLOW® and MULTICAL® are connected via Pulse Transmitter, ULTRAFLOW® is galvanically separated from
MULTICAL® and the cable length between ULTRAFLOW® and MULTICAL® can be extended up to 110 m.
<
Flow-info is not possible if Pulse Transmitter/Pulse Divider is used.
If ULTRAFLOW® is connected to other equipment than MULTICAL®, always connect ULTRAFLOW® via Pulse Transmitter
or Pulse Divider. For connection of Pulse Transmitter and Pulse Divider to other calculators, see paragraph
output of Pulse Transmitter and Pulse
ULTRAFLOW®
→
Pulse Transmitter/
Pulse Divider
1)
→
MULTICAL®
Input
Output
Blue (ground)
→
11
11A
→
11
Red (supply)
→
9
9A
→
9
Yellow (signal)
→
10
10A
→
10
Table 23. Connection of ULTRAFLOW® and MULTICAL® via Pulse Transmitter/Pulse Divider.
1)
Pulse Divider is normally not used together with MULTICAL®.