13
Kamstrup A/S • 55122412_A1_GB_2019-03
MULTICAL® 803 & ULTRAFLOW®
5.2 Connection of ULTRAFLOW®
ULTRAFLOW® is connected to MULTICAL® 803
via the connection PCB using the terminal
numbers to the right.
ULTRAFLOW®
Wire
Terminal number
V1
Signal ( )
10
+ ( )
9
- ( )
11
V2
Signal ( )
69
+ ( )
9
- ( )
11
5.3 Connection of other flow sensors
Other passive flow sensors with either reed
switch or transistor output can be connected
to MULTICAL® via the terminal numbers to
the right. Be aware of correct mounting of +
and - of flow sensors with transistor outputs.
Flow sensor
Wire
Terminal number
V1
+
10
-
11
V2
+
69
-
11
MULTICAL® 803 can be connected to other flow
sensors with 24 V active pulse outputs by using
connection PCB 6699-045 that is available as
accessory for MULTICAL® 803. See the terminal
numbers to the right. Be aware of correct
mounting of + and -.
Flow sensor
Wire
Terminal number
V1
Signal
10B
-
11B
+ 24 VDC
1
97A
V2
Signal
69B
-
11B
+ 24 VDC
1
97A
1
Requires that MULTICAL® 803 has supply
type C or D.
21 21A
27 28
20A 20
t4
52 52A51A 51
4 8 7 3
2 6 5 1
- +
V1
10
11 9
- +
V2
69
11 9
24V
24V
t3
t2
t1
4 wire
27 28
2 wire
230 VAC
97 98
24 VAC/VDC
-
(+)
V1
10B
11B 97A
-
(+)
V2
69B
79B97A
5535-1745
Figure 1
Conncetion of PCB MULTICAL® 803