21
Kamstrup A/S • 55122412_A1_GB_2019-03
MULTICAL® 803 & ULTRAFLOW®
9.12 Analog inputs, type HC-003-41
Analog module with 2 inputs configurable as
either 4...20 mA or 0...10 V inputs. The inputs
can be scaled according to the connected
sensors. Connect the sensors to the module
via the 2 sets of input terminals 60-58-57 and
60-59-57. The measured values can be read in
the meter’s P1 and P2 registers.
The meter must be supplied by 24 VAC or
230 VAC.
The module requires an external 24 VAC/VDC
power supply for operating the module and the
connected sensors.
9.13 PQT Controller, type HC-003-43
The PQT Controller module with output for
controlling of three-point motor-operated
valve. The module is used for regulating power,
flow and temperature in the installation. The
motor-operated valve is connected to the
terminals 150, 151 and 152. The motor-operated
valve’s direction of rotation can be checked by
short-circuiting the test points Up or Dn.
The meter must be supplied by 24 VAC or
230 VAC.
The module requires an external 24 VAC
power supply for operating the connected
motor-operated valve.