
MULTICAL® 801
56
Kamstrup A/S · Technical Description · 5512-571_R1_GB_11_2016
EE=13 T1-T2 tariff (
∆
t)
If the current T1-T2 (
∆
t) is lower than TL2 but exceeds TL3, heat energy is counted in TA2 parallel to the main register.
If the current cooling falls below or is equal to TL3, heat energy is counted in TA3 parallel with the main register.
∆
t
≥
TL2
Accumulation in main register only
TL3
<
TL2
TL3
<
∆
t
<
TL2
Accumulation in TA2 and main register
∆
t
≤
TL3
Accumulation in TA3 and main register
Setting up tariff limits TL3 must always be lower than TL2.
The T1-T2 tariff can be used as a basis for weighted user charge. Low
∆
t (small difference between inlet and outlet
temperatures) is uneconomical for the heat supplier.
EE=14 Inlet tariff
If the current inlet temperature (T1) exceeds TL2 but is lower than or equal to TL3, heat energy is counted in TA2
parallel to the main register. If the current inlet temperature exceeds TL3, heat energy is counted in TA3 parallel to
the main register.
T1
≤
TL2
Accumulation in main register only
TL3
>
TL2
TL3
≥
P
>
TL2
Accumulation in TA2 and main register
T1
>
TL3
Accumulation in TA3 and main register
Setting up data TL3 must always include a higher value than TL2.
The inlet temperature tariff can be used as a basis for billing consumers who are guaranteed a certain inlet
temperature. If the “guaranteed” minimum temperature is entered as TL3, the payable consumption is accumulated
in TA3.
EE=15 Outlet temperature tariff
If the current outlet temperature (T2) exceeds TL2 but is lower than or equal to TL3, heat energy is counted in TA2
parallel to the main register. If the current outlet temperature exceeds TL3, heat energy is counted in TA3 parallel
to the main register.
T2
≤
TL2
Accumulation in main register only
TL3
>
TL2
TL3
≥
T2
>
TL2
Accumulation in TA2 and main register
T2
>
TL3
Accumulation in TA3 and main register
Setting up data TL3 must always be bigger than TL2.
The outlet temperature tariff can be used as a basis for weighted user charge. A high outlet temperature indicates
insufficient heat utilization, which is uneconomical for the heat supplier.