MULTICAL® 801
Kamstrup A/S · Technical Description · 5512-571_R1_GB _11.2016
35
Application no. 3
2-string system with 2 flow meters
Heat energy: E1 = V1(T1-T2)k
T1:Inlet or T2:Outlet
Tap water energy: E6 = V2 (T3-T4)k
T3:Inlet
T3 is measured or programmed
T4 is programmed
Flow meter V1 is placed in inlet or outlet as selected
during PROG.
Mass: M1 = V1 (Kmass t1) or
Mass: M1 = V1 (Kmass t2) depending on inlet/outlet
programming.Mass: M2 = V2 (Kmass t3)*
Application no. 4
2 heating circuits with joint inlet pipe
Heat energy #1: E1 = V1(T1-T2)k
T2:Outlet
Heat energy #2: E7 = V2(T1-T3)k
T3:Outlet
T3 is measured or programmed
Mass: M1 = V1 (Kmass t1)
Mass: M2 = V2 (Kmass t3)*
Application no. 5
Open system with tapping from outlet pipe
Heat energy: E1 = V1(T1-T2)k
T1:Inlet
Tap water energy: E5 = V2 (T2-T3)k
T2:Inlet
T3 is measured or programmed
Mass: M1 = V1 (Kmass t1)
Mass: M2 = V2 (Kmass t2)