MULTICAL®
603
Kamstrup
A/S
∙
Technical
description
∙
5512
‐
2029_A1_GB_06.2017
107
Temperature
sensor
error
The
error
can
be
due
to
the
sensor
being
disconnected
or
short
‐
circuited.
An
erroneous
ΔΘ
alone
will
not
be
considered
a
temperature
sensor
error.
In
case
of
an
error
in
one
or
more
temperature
sensors
(t1,
t2
and
t3),
the
value
of
the
serial
communication
of
the
sensor
in
question
will
be
0.00
°C
(lowest
valid
temperature)
or
185.00
°C
(highest
valid
temperature)
respectively,
depending
on
the
measurement
being
below
range
(sensor
short
‐
circuited)
or
above
range
(sensor
disconnected).
The
display
reading
of
the
sensor
in
question
shows
lines
in
the
three
digits
to
the
far
right
in
the
display,
independent
of
the
cause
of
the
error
‐
decimal
points
are
not
included.
The
display
readings
of
ΔΘ
and
current
power
will
also
show
three
lines
for
errors
in
one
or
more
temperature
sensors.
In
serial
communication,
the
value
will
be
0.00
K
and
0.0
kW.
Information
codes
in
transport
state
The
meter
leaves
the
factory
in
transport
state,
i.e.
the
info
codes
are
active
in
the
display,
but
not
in
the
meter's
data
logger.
This
prevents
the
counting
of
info
events
and
the
saving
of
non
‐
relevant
data
in
the
info
log
during
transportation.
The
first
time
the
meter
registers
flow
after
the
installation,
the
info
code
automatically
becomes
active.