MULTICAL® 302
54
Kamstrup A/S · Technical Description · 5512-1334_F1_GB_12.2016
8.4.2
Changing the energy unit
If you change the energy unit setting in Setup loop you must be aware that the change can influence the most
significant digits of the display. If for instance you change from GJ with 2 decimals to GJ with 3 decimals, the most
significant digit will disappear. The same applies if you change from kWh without decimals to kWh with 1 decimal. And
conversely the least significant digit disappears if e.g. you change from kWh with 1 decimal to kWh without decimals.
See examples below:
Example 1
GJ with 2 decimals (B=2)
This is an example of how the energy reading E1 can
appear – counted in GJ.
Example 2
GJ with 3 decimals (B=6)
Here the most significant digit has disappeared
compared to example 1. In outlet you receive a
higher resolution.
Example 3
kWh without decimals (B=3)
This is an example of how energy reading E1 can
appear – counted in kWh.
Example 4
kWh with 1 decimal (B=7)
Here the most significant digit has disappeared
compared to example 3. In outlet you receive a
higher resolution.
Example 5
MWh with 3 decimals (B=4)
In principle this is the same resolution as in example
3, but energy is now counted in MWh.
8.5
TEST loop
Test loop is intended for laboratories and others who are to verify the meter (see paragraph 14 for further details on
Test).