69
KaDeck
3.26
Versatile air conditioning for offices and administration buildings
Installation and operating instructions
6.19 Parameter list for control PCB
Function
Standard
parameter
(Rev. 1.19)
Min.
Max.
Unit
KaDeck
parameters
P000 Software version
-
0
255
-
-
P001 Base setpoint for setpoint entry ± 3K
22
8
32
°C
22
P002 Switching on / off hysteresis for valves
3
0
255
K/10
10
P003 Neutral zone in a 4-pipe system (only in automatic mode)
3
0
255
K/10
5
P004 Cooling without fan assistance (natural convection)
0
0
255
K/10
0
P005 Heating without fan assistance (natural convection)
5
0
255
K/10
3
P006 Fan On/Off hysteresis (only in ventilation mode)
5
0
255
K/10
5
P007 P-band, heating
15
0
100
K/10
17
P008 P-band, cooling
20
0
100
K/10
20
P009 Offset to the base setpoint for setpoint input ± 3K
3
0
10
K
3
P010 Clip-on sensor: Limit temperature to activate fan stages 1 and 2 in heating mode
29
0
255
°C
26
P011 Clip-on sensor: Limit temperature to activate fan stages 3 and 4 in heating mode
31
0
255
°C
28
P012 Clip-on sensor: limit temperature to activate fan stage 5 in heating mode
33
0
255
°C
30
P013 Clip-on sensor: hysteresis for limit temperatures P010, P011, P012, P014
10
0
255
K/10
10
P014 Clip-on sensor: limit value temperature to activate the fan stages in cooling mode
18
0
255
°C
18
P015 Function of input AI1
0
0
19
-
0
P016 Function of input AI2
0
0
19
-
0
P017 Function of input AI3
0
0
9
-
0
P018 Raise temperature of cooling setpoint in Eco mode
30
0
255
K/10
30
P019 Lower temperature of heating setpoint in Eco mode
30
0
255
K/10
30
P020 ADC limit coefficient
6
0
15
-
6
P021 ADC average coefficient
6
0
15
-
6
P022 Activation/disabling of sun symbol in Comfort mode
0
0
1
-
0
P023 Difference for compensation during cooling
0
-99
127
K/10
0
P024 Coefficient for compensation during heating
0
-20
20
1/10
0
P025 Difference for compensation during heating
0
-99
127
K/10
0
P026 Coefficient for compensation during heating
0
-20
20
1/10
0
P027 Fan setting: maximum run-time for manual fan mode
0
0
255
Min.
0
P028 Flushing function: Fan stage during the flushing function
2
1
5
-
2
P029 Activation of continuous fan mode
0
0
1
-
0
P030 Ventilate temperature activation
12
0
255
°C
12
P031 Ventilation interval
27
0
255
°C
27
P032 Flushing function: maximum idle time of fan
15
0
255
Min.
15
P033 Flushing function: duration of flushing function
240
0
255
s
120
P034 Flushing function: activation in operating modes
0
0
3
-
3
P035 Time the fan runs at Stage 1 after change of operating mode
0
0
255
s
0
P036 Type of setpoint setting
0
0
1
-
0
P037 Display
1
0
7
-
1
P038 Lock/disable function on control unit
64
0
255
-
72
P039 Function of digital output V2 (in 2-pipe system)
0
0
3
-
0
P040 Valve actuation by means of pulse width modulation
0
0
1
-
0
P041 Reset time of PI controller to actuate the fan in automatic fan mode
0
0
20
Min.
0
P042 Fan setting: lock and activate fan stages
0
0
127
-
0
P043 Function of digital input DI1
1
0
14
-
12
Summary of Contents for KaDeck