- 5 -
KALVIS - 2-30U, -2-40U 2012.02.06
1.
Recommendations
In order the boiler served long and without troubles and you did
not loose the right for guarantee service, please observe the following
main rules:
1.
Boiler installation, adjustment, operator training can be performed
by a firm, attested for such jobs and having qualified specialists or
by representative authorized by manufacturer.
Installation note
has to be done in this certificate, installation report
.
2.
Boiler has to be installed in accordance with recommended or
other diagrams, with 4-way mixing valve or thermostatic 3-way
valve in order, to
ensure temperature that the water returning to
the boiler was of no lower than 60ºC.
Attention: If you fail to meet this requirement, corrosion will occur
due to condensate which will significantly reduce service life of the
body and ceramic tiles.
3.
Optimum operation of the boiler is achieved at close to nominal
power.
4.
If boiler power is too high and it has to be operated at lower than
nominal power,
we recommend to install the boiler with
accumulation capacity.
5.
Use fuel no damper than 25%.
In the case of higher fuel
dampness, boiler power drops, fuel consumption rises.
Note.
This operation manual is compiled following the requirements
provided for in LST EN 12171 Building Heating Systems. Operation,
Maintenance and Use Document Preparation Procedures. Heating
Systems Needing no Trained Operator.