Shower Temperature Adjustment (cont.)
Pull out the detent collar.
Turn the detent collar counterclockwise.
Verify the temperature.
If the temperature is greater than 105°F (41°C):
Pull out the detent collar.
Turn the detent collar clockwise.
Verify the temperature.
Repeat the steps above until the desired temperature is achieved.
Troubleshooting Guide
Symptoms
Probable Cause/Recommended
Action
1.
Only hot or cold water from
the water outlet.
A.
Inlet supplies are reversed. See
″
Reversed Inlet Supplies
″
section
of the Installation Guide.
B.
Check filter screens for
blockage. Clear if necessary.
2.
Fluctuating or reduced flow
rate.
A.
External condition variation
such as reduced pressure.
B.
Check filter screens for
blockage. Clear if necessary.
C.
Make sure that the minimum
flow rate is sufficient for supply
conditions.
D.
Make sure that dynamic inlet
pressures are nominally balanced
and sufficient.
E.
Make sure that inlet
temperature differentials are
sufficient.
F.
Service stops are not fully
threaded in. Rotate both service
stops until fully threaded.
G.
Check thermostatic
performance; replace the
thermostatic cartridge, if necessary.
3.
No flow from shower control
water outlet.
A.
Filter screens are blocked. Clear
filter screens.
1048326-2-B
18
Kallista