2. Safety
6
2.4.1
Installation of the Heat Pure in combination with
combustible materials (e.g. a wooden wall)
When installing the Heat Pure, make sure to respect the recommended
distance from any combustible building materials:
Combustible building materials behind the fire must also be shielded or
insulated by insulation material. The minimum thickness (A) of the
insulation material depends on the model and type of Heat Pure. Refer to
Table 1 for the required minimum insulation thickness.
The distance from the back of the Heat Pure (or the side if the fire is built
into an alcove) to the insulation material must be a minimum of 10 cm.
Combustible material
insulation
combustible building material
A