2.2.31 Address
It is used to identify the unit in use in the central control system.
[Operation Instructions]
Go to the
FUNCTION
page and locate “
Address
to set
the address.
[Notes]
(a) It indicates the address of the control and is intended for the group control.
(b) It will not be memorized upon power failure.
(c) The address range is [0,125] and [127,253]
(d) The default address is 1 for the initial use.
2.2.32 Gate-Controller(Gate-Ctrl.)
On
” or “
Off
” based on the actual condition.
[Operation Instructions]
Go to the
FUNCTION
page and locate “
Gate-Controller
”, then, configure it through the Up/Down key
, “
On
” or “
Off
”.
[Notes]
(a) When it is activated, the control will check the card is inserted or not. If inserted, the control will run
normally; if not, the control will turn off the unit and back to the homepage. In this case, any key operation
is ineffective (except for the combined key operation), or a dialogue box will pop up, warning"
Keycard
uninserted!
".
(b) It will not be memorized upon power failure.
2.3 Parameter Setting (Parameter Set)
2.3.1 User Parameter Setting
out temperature for heating, and water tank temperature etc.