Interval
Maintenance task
see chapter
Up to 1,000 h
Check the air filter.
Clean the cooler.
Cooler:
Clean the filter mat.
Control cabinet:
Clean the filter mat.
Up to 3,000 h
Maintain the drive belt.
Change the air filter element.
Cooler:
Change the filter mat.
Control cabinet:
Change the filter mat.
Up to 3,000 h
At least annually
Change the oil filter.
Change the oil separator cartridge.
Up to 6,000 h
Replace the drive belts.
Change the cooling oil.
Annually
Check that all electrical connections are tight.
–
Check the pressure relief valve.
Check the overheating safety shutdown function.
Check the cooler for leaks.
h = operating hours
Tab. 42 Regular maintenance tasks
10.2.4 Cooling Oil: Change Interval
Duty cycles and ambient conditions are important criteria for the number and length of the change
intervals.
KAESER Service will support you in determining suitable intervals and provide information on
the possibilities of oil analysis.
➤ Please observe national regulations regarding the use of cooling oil in oil-injected rotary screw
compressors.
➤ Check operating conditions and adjust intervals as necessary; log the results in table 43 for future
reference.
Maximum permissible oil change interval
[operating hours/year]
SIGMA FLUID
Favourable operating
conditions*
Unfavourable operat‐
ing conditions
My operating condi‐
tions
S-460
6 000**/2
4 000/1
MOL
3 000/1
2 000/1
* Cool to moderate ambient temperatures, low humidity, high duty cycle
** Changing intervals of >6000 operating hours are not permissible without an oil analysis.
10 Maintenance
10.2 Maintenance Schedule
9_6919 04 E
Service Manual Screw Compressor
SX SIGMA CONTROL BASIC
51
Summary of Contents for SX
Page 2: ...Original instructions KKW SSX 1 04 en SBA SCHRAUBEN SCB...
Page 6: ...Contents iv Service Manual Screw Compressor SX SIGMA CONTROL BASIC 9_6919 04 E...
Page 8: ...List of Illustrations vi Service Manual Screw Compressor SX SIGMA CONTROL BASIC 9_6919 04 E...
Page 10: ...List of Tables viii Service Manual Screw Compressor SX SIGMA CONTROL BASIC 9_6919 04 E...