SX 3
SX 4
SX 6
SX 8
Weight [kg]
140
140
145
155
Tab. 4 Machine weight
2.4 Temperature
SX 3
SX 4
SX 6
SX 8
Minimum cut-in tempera‐
ture [°C]
3
3
3
3
Typical airend discharge
temperature during opera‐
tion [°C]
65–100
65–100
65–100
65–100
Maximum airend dis‐
charge temperature (auto‐
matic safety shut-down)
[°C]
110
110
110
110
Tab. 5 Temperature
2.5 Ambient conditions
SX 3
SX 4
SX 6
SX 8
Maximum altitude AMSL*
[m]
1000
1000
1000
1000
Permissible ambient tem‐
perature [°C]
3–45
3–45
3–45
3–45
Cooling air temperature
[°C]
3–45
3–45
3–45
3–45
Inlet air temperature [°C]
3–45
3–45
3–45
3–45
Maximum relative humidi‐
ty of inlet air
* Higher altitudes are permissible only after consultation with the manufacturer.
Tab. 6 Ambient conditions