➤ Consult the KAESER service representative before deciding on:
■ the design of the exhaust air ducting
■ the intersection between the machine and the exhaust air duct
■ the length of the ducting
■ the number of duct bends
■ the design of flaps or shutters
Use only motorised ventilation flaps and louvers on variable frequency drive (SFC) only use
flaps or shutters that are operated by a motor.
Flaps or shutters that are opened by the the action of airflow against the force of gravity do not
open sufficiently at low cooling fan speeds.
Further information Further information on installation of exhaust air ducts can be found in chapter 13.3.
5.3 Operating the Machine in an Air System.
If the machine is supplying an air system, the system operating pressure may not exceed 16 bar.
When charging a fully vented air system there is generally a very high rate of airflow through the air
treatment devices. These cannot function correctly under such conditions. Air quality suffers.
To ensure the desired air quality when charging a vented air network, we recommend the installation
of an air main charging system.
➤ Consult KAESER for advice on this subject.
5
Installation and Operating Conditions
5.3
Operating the Machine in an Air System.
32
Service Manual Screw Compressor
SX SIGMA CONTROL BASIC
9_6919 04 E
Summary of Contents for SX
Page 2: ...Original instructions KKW SSX 1 04 en SBA SCHRAUBEN SCB...
Page 6: ...Contents iv Service Manual Screw Compressor SX SIGMA CONTROL BASIC 9_6919 04 E...
Page 8: ...List of Illustrations vi Service Manual Screw Compressor SX SIGMA CONTROL BASIC 9_6919 04 E...
Page 10: ...List of Tables viii Service Manual Screw Compressor SX SIGMA CONTROL BASIC 9_6919 04 E...