Decommissioning and dismantling
DANGER
Lethal voltages are still present in the connections and cables of the device even after the device has
been switched off and disconnected!
Severe injuries or death may occur if the cables and/or terminals/busbars in the device are touched.
Only appropriately qualified electricians authorised by the mains supply network operator are permitted
to open and maintain the device.
›
Comply with all safety regulations and current technical connection specifications of the responsible
power supply company.
DANGER
Risk of fatal injury due to electric shock!
The DC isolator switch only disconnects the PV generator from the device. The storage battery is not dis-
connected. Voltage is still present at the DC connector BAT.
Severe injury or death will result if the live connections are touched.
›
Only touch the PV generator cables on the insulation. Do not touch the exposed ends of the cables.
10.1
Switching off the device
WARNING
Risk of burns caused by hot housing components
Housing components can become hot during operation.
›
During operation, only touch the housing cover on the device.
1.
Press and hold the "Set" button (on the bottom of the device). A status bar appears on the display. The "Set"
button must be pressed until this bar is completely filled and the request to operate the DC isolator switch
appears on the display.
2.
The device discharges. The display goes out after about 60 seconds.
3.
Set the DC isolator switch to "0" to prevent unintentional starting.
NOTE
If the display is dark, the device does not necessarily have to be switched off permanently.
›
To prevent the device from starting, the DC switch must be set to "0".
Authorised elec-