6.2
Choosing the installation location
DANGER
Risk of fatal injury due to fire or explosions!
Fire caused by flammable or explosive materials in the vicinity of the device can lead to serious injuries.
›
Do not mount the inverter in potentially explosive atmospheres or in the vicinity of highly flammable
materials.
CAUTION
Property damage due to gases that have an abrasive effect on surfaces when they come into contact
with ambient humidity caused by weather conditions.
The device housing can be seriously damaged due to gases in combination with air humidity resulting from
weather conditions (e.g. ammonia, sulphur).
›
If the device is exposed to gases, the installation must be carried out at observable locations.
›
Perform regular visual inspections.
›
Immediately remove any moisture from the housing.
›
Ensure adequate ventilation at the installation location.
›
Immediately remove dirt, especially on vents.
›
Failure to observe these warnings may lead to device damage which is not covered by the manufac-
turer warranty.
NOTE
Access by maintenance personnel for service
Any additional costs arising from unfavourable structural or mounting conditions shall be billed to the cus-
tomer.
Requirements for the installation space
–
As dry as possible, climate-controlled, the waste heat must be able to be dissipated away from the device.
–
Unobstructed air circulation.
–
Observe ambient temperatures according to the data sheet.
–
Observe minimum distances to the sides of the housing; see
–
Accessible from the front and sides without requiring additional resources.
–
At a height at which the display can be read at any time.
–
Do not install outdoors; the device is designed for indoor use only (IP20).
Requirements on the installation surface
–
Must have adequate load-bearing capacity
–
Must be accessible for installation and maintenance
–
Must be made of heat-resistant material (up to 90 °C)
–
Must be flame resistant